Study guide
3.5 Corrosion Control, Lead & Copper Rule Revisions (LCRR) & Fluoridation Practices
Colorado Water/Wastewater Operator Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: State Laws, Regulations & CCWP Certification
1.1 CDPHE CCWP Program & Regulatory Framework (Regulation 100 / 5 CCR 1003-2) 1.2 Facility Classification & Operator in Responsible Charge (ORC) Requirements 1.3 Certification Levels, Education, Experience & Exam Eligibility (Class D-A, Grade 1-4, Class S/T) 1.4 License Renewal, Training Units (TUs) & Mandatory Regulatory Training 1.5 Colorado Primary Drinking Water Regulations (Regulation 11) & Compliance 1.6 Colorado Discharge Permit System (Regulations 61/62), DMRs & Biosolids Reporting
2 Chapter 2: Source Water & Drinking Water Treatment Processes
2.1 Raw Water Sources, High-Altitude Characteristics & Reservoir Quality 2.2 Coagulation Chemistry, Rapid Mixing & Chemical Dosing (Alum, Ferric, Polymers) 2.3 Flocculation & Sedimentation Basin Design, Operation & Settling Zones 2.4 Granular Media Filtration, Backwash Procedures & Turbidity Standards 2.5 Advanced Treatment: Membranes, Softening, GAC/PAC Adsorption & Aeration 2.6 Groundwater Sources, Well Hydraulics, Static and Pumping Levels & Specific Capacity 2.7 Source Water Characteristics, Contaminant Categories & Watershed Protection Plans 2.8 Pretreatment: Presedimentation, Aeration, Algae Control & Taste-and-Odor Management 2.9 Direct, In-Line, Pressure, Cartridge & Diatomaceous Earth Filtration 2.10 Lime-Soda Softening, Ion Exchange & Water Stabilization 2.11 Water Treatment Plant Residuals: Lagoons, Drying Beds, Land Application & Recycle
3 Chapter 3: Disinfection & Chemical Addition
3.1 Chlorine Chemistry: Hypochlorous Acid, Free/Combined Residual & Breakpoint Chlorination 3.2 Disinfection Kinetics, Baffle Factors, T10 & CT Compliance Calculations 3.3 Disinfection Byproducts (TTHMs, HAA5s) & Stage 1/2 DBP Rules 3.4 Alternative Disinfection: Chloramination, Ultraviolet (UV) Light & Chlorine Dioxide 3.5 Corrosion Control, Lead & Copper Rule Revisions (LCRR) & Fluoridation Practices
4 Chapter 4: Water Treatment Plant Equipment, Instrumentation & Maintenance
4.1 Raw Water Intakes, Screening Equipment & Raw Water Pumping 4.2 Chemical Feed Equipment: Feeders, Day Tanks, Carrier Water & Feed-Rate Calibration 4.3 Chlorination Equipment: Gas Systems, Vacuum Regulators, Hypochlorite Storage & Onsite Generation 4.4 Filter Underdrains, Support Gravel, Surface Wash, Air Scour & Filter-to-Waste 4.5 Plant Process Control, SCADA and PLC Systems, Alarm Management & Records of Operation 4.6 Preventive, Corrective and Predictive Maintenance, Work Orders & Asset Management
5 Chapter 5: Wastewater Treatment Principles & Biological Processes
5.1 Preliminary Treatment: Bar Screens, Shredders, Grit Chambers & Flow Equalization 5.2 Primary Clarification, Solids Separation & Scum Removal Mechanics 5.3 Activated Sludge Fundamentals: Aerobic Microbiology, DO Control & Biomass Growth 5.4 Return & Waste Activated Sludge Management (RAS/WAS Operations & Sludge Age) 5.5 Activated Sludge Troubleshooting: Bulking, Nocardia Foaming, Rising Sludge & Pin Floc 5.6 Wastewater Characteristics, Organic and Hydraulic Loading, Diurnal Flow & Septicity 5.7 Activated Sludge Arrangements: Conventional, Complete Mix, Step Feed, Contact Stabilization, Extended Aeration, Oxidation Ditch, SBR & MBR 5.8 Aeration Systems: Blowers, Diffusers, Surface Aerators, Oxygen Transfer & Altitude Effects
6 Chapter 6: Advanced Wastewater Treatment & Solids Management
6.1 Biological Nutrient Removal: Nitrification, Denitrification & Anoxic Zones 6.2 Biological & Chemical Phosphorus Removal (EBPR & Coagulant Precipitation) 6.3 Sludge Thickening, Aerobic & Anaerobic Digestion (Mesophilic/Thermophilic) 6.4 Dewatering Equipment (Centrifuges, Belt Filter Presses) & Biosolids Standards (Reg 64) 6.5 Pond & Lagoon Operations, Trickling Filters & Rotating Biological Contactors (RBCs) 6.6 Secondary Clarification: Overflow and Solids Loading Rates, RAS Rate Setting & Clarifier Diagnostics 6.7 Tertiary Filtration, Effluent Polishing & Wastewater Disinfection with Chlorine, Dechlorination and UV 6.8 Effluent Disposal, Rapid Infiltration Basins, Colorado Water Reuse Law & Regulation 84
7 Chapter 7: Water Distribution Systems
7.1 Distribution Hydraulics, Pressure Zones, Static Head & Friction Headloss 7.2 Finished Water Storage Tanks, Standpipes, Mixing & Water Age Control 7.3 Distribution Piping, Valves (Gate, Butterfly, PRV), Hydrants & Main Flushing 7.4 Cross-Connection Control, Hazard Assessment & Backflow Preventers (RPZ, DCVA, PVB, Air Gap) 7.5 Water Main Installation, Trenching, Repair, Pressure Testing & Disinfection (AWWA C651) 7.6 Network Layout, Pressure Zones, Demand Patterns, Fire Flow & the Hydraulic Grade Line 7.7 Fire Hydrants, Dry Barrel Operation, Fire Flow Testing & Unidirectional Flushing 7.8 Booster Pump Stations, Hydropneumatic Systems, Controls & Surge Protection 7.9 Customer and Master Metering, Meter Sizing, Accuracy Testing, AMR & AMI 7.10 System Mapping, GIS, As-Builts, Operational Analysis & the AWWA Water Audit 7.11 Service Line Installation, Wet Tapping, Curb Stops & the Lead Service Line Inventory 7.12 Leak Detection, District Metered Areas, Minimum Night Flow & Pressure Management 7.13 Storage Facility Inspection, Sanitary Defects, Water Age Control, Cleaning & AWWA C652 Disinfection 7.14 Utility Locating, Colorado 811 Damage Prevention, the APWA Color Code & New Construction Inspection 7.15 Well and Wellhead Maintenance, Sanitary Condition, Rehabilitation & AWWA C654 Disinfection 7.16 Booster Chlorination, Remote Chemical Feed, Chemical Storage, Security & Supply Management 7.17 Distribution Sampling Technique, Chlorine Residual Monitoring & Nitrification Control in Chloraminated Systems
8 Chapter 8: Wastewater Collection Systems
8.1 Gravity Collection Systems: Flow Velocities, Slopes, Pipe Materials & Manholes 8.2 Wastewater Lift Stations: Wet Wells, Submersible Pumps, Level Controls & Force Mains 8.3 Inflow and Infiltration (I&I) Sources, Flow Monitoring, Smoke Testing & CCTV Inspection 8.4 Collection Maintenance: Hydraulic Jetting, Mechanical Rodding & FOG/Root Mitigation 8.5 Sanitary Sewer Overflows (SSOs): Root Causes, Containment, Reporting & Mitigation 8.6 Lift Station Electrical Devices, Level Detection, Telemetry, Gas Detection & Capacity Adjustment 8.7 Lift Station Configurations, Preventive Maintenance, Wet Well Cleaning, Troubleshooting & Emergency Bypass Pumping 8.8 Collection System Rehabilitation: CIPP, Pipe Bursting, Sliplining, Grouting, Manhole Repair & Tap Defects 8.9 Excavation, Hydro Excavation, Bedding and Haunching, Grade Control & Sewer Acceptance Testing 8.10 Collection System Flow Monitoring, Area-Velocity Metering, Weirs and Flumes & Capacity Assessment
9 Chapter 9: Pumps, Motors & Utility Mechanics
9.1 Centrifugal Pumps: Volutes, Impellers, Packing Seals & Mechanical Seals 9.2 Positive Displacement Pumps (Peristaltic, Diaphragm, Progressive Cavity) & Dosing Systems 9.3 Pump Performance Curves, System Head Curves, Cavitation & NPSH Calculations 9.4 Electric Motors (Single/Three Phase), Controls, Variable Frequency Drives (VFDs) & Power 9.5 Flow Meters (Venturi, Magnetic, Ultrasonic), Online Analyzers, PLCs & SCADA Telemetry 9.6 Air Compressors, Conveyors, Hoists and Cranes, Service Piping & Standby Power Generation 9.7 Valve Types and Duties, Air Release and Air-Vacuum Valves, Water Hammer & Surge Control
10 Chapter 10: Laboratory Analysis & Water Quality Monitoring
10.1 Regulatory Sampling Procedures, Chain of Custody, Holding Times & Preservation Techniques 10.2 Physical & Chemical Drinking Water Testing: Turbidity, pH, Alkalinity, Hardness & Chlorine (DPD) 10.3 Wastewater Laboratory Analysis: BOD5, COD, Total Suspended Solids (TSS) & Settleometry 10.4 Microbiological Testing: Total Coliform, E. coli (Colilert, Membrane Filtration) & QA/QC 10.5 Bench-Scale Jar Testing, Coagulant Optimization & Streaming Current Monitoring 10.6 Laboratory Equipment, Calibration and Verification, QA/QC Program & Certified Laboratory Requirements 10.7 Nutrient Series, Metals Sampling, Whole Effluent Toxicity & Electrode Measurements (DO, pH, ORP, H2S)
11 Chapter 11: Operator Mathematics & Applied Calculations
11.1 Core Conversions, Geometric Area, Pipe Volume & Continuous Flow Rate (MGD, GPM, cfs) 11.2 Chemical Dosage, The Standard "Pounds Formula", Active Chemical & Solution Purity 11.3 Hydraulic Retention Time (HRT), Surface Overflow Rate (SOR) & Weir Overflow Rates 11.4 Process Control Calculations: F/M Ratio, MCRT/Solids Retention Time (SRT) & Sludge Volume Index (SVI) 11.5 Distribution Pressure, Static vs Dynamic Head, Water Horsepower & Wire-to-Water Efficiency 11.6 CT Calculations: Baffling Factors, T10, Temperature and pH Corrections & Multi-Segment Compliance
12 Chapter 12: Safety, Emergency Operations & Compliance
12.1 Permit-Required Confined Space (PRCS) Entry, Atmospheric Testing (O2/LEL/H2S/CO) & Rescue 12.2 Control of Hazardous Energy: Lockout/Tagout (LOTO), Arc Flash & Electrical Safety 12.3 Chemical Safety: Chlorine Gas Handling, Ton Cylinders, Sulfur Dioxide, Ammonia & SDS/GHS 12.4 Trenching & Excavation: Soil Classification, Sloping, Shoring, Shielding & Competent Person Rules 12.5 Emergency Action Plans, Security Vulnerability, Spill Containment & CDPHE Tier 1/2/3 Public Notice 12.6 Work Zone Traffic Control, PPE, Fall Protection, Fire Extinguishers, First Aid & Bloodborne Pathogens 12.7 Standard Operating Procedures, Operating Records, Regulatory Reporting, Customer Complaints & Supervisory Duties
3.5 Corrosion Control, Lead & Copper Rule Revisions (LCRR) & Fluoridation Practices
Key Takeaways Explain This Topic AI
The Lead and Copper Rule (LCR/LCRR) establishes Action Levels of 0.015 mg/L (15 µg/L) for lead and 1.3 mg/L for copper, evaluated at the 90th percentile of tap samples.
Optimal Corrosion Control Treatment (OCCT) protects public health via pH/alkalinity adjustment or orthophosphate passivation to form insoluble lead/copper mineral films.
The Langelier Saturation Index (LSI = pH - pHs) indicates whether water tends to precipitate protective calcium carbonate scale (LSI > 0) or dissolve scale and corrode pipes (LSI < 0).
The recommended optimal fluoride concentration for community water fluoridation is 0.7 mg/L to prevent dental caries while minimizing fluorosis.
Fluorosilicic acid (H2SiF6), sodium fluorosilicate (Na2SiF6), and sodium fluoride (NaF) are the three approved fluoridation chemicals, governed by a primary MCL of 4.0 mg/L.
Last updated: August 2026
Corrosion Control, Lead & Copper Rule Revisions (LCRR) & Fluoridation Practices
Water leaving a treatment plant must be chemically stable. Corrosive water degrades distribution infrastructure, dissolves toxic heavy metals from customer plumbing, and creates aesthetic red/black water complaints. Concurrently, public water systems adjust finished water chemistry to support dental public health through community water fluoridation .
1. Lead and Copper Rule Framework (LCR, LCRR & LCRI)
Under EPA regulations and CDPHE Regulation 11 , lead and copper are regulated via treatment technique Action Levels (AL) rather than standard Maximum Contaminant Levels (MCLs), because these contaminants originate predominantly in customer service lines and indoor plumbing rather than raw water sources.
Core Regulatory Thresholds
Lead Action Level: 0.015 mg/L (15 μ g/L or 15 ppb) \mathbf{0.015\text{ mg/L (15 }\mu\text{g/L or 15 ppb)}} 0.015 mg/L (15 μ g/L or 15 ppb) .
Lead Trigger Level (LCRR): 0.010 mg/L (10 μ g/L or 10 ppb) \mathbf{0.010\text{ mg/L (10 }\mu\text{g/L or 10 ppb)}} 0.010 mg/L (10 μ g/L or 10 ppb) — Mandates progressive corrosion control planning and goal-based lead service line replacement.
Copper Action Level: 1.3 mg/L (1,300 μ g/L or 1.3 ppm) \mathbf{1.3\text{ mg/L (1,300 }\mu\text{g/L or 1.3 ppm)}} 1.3 mg/L (1,300 μ g/L or 1.3 ppm) .
90th Percentile Compliance Determination
Compliance is evaluated based on the 90th percentile concentration of 1-liter, first-draw tap water samples collected from high-risk customer homes (Tier 1 sites with confirmed Lead Service Lines [LSL], lead pipes, or copper pipes with lead solder installed between 1983 and 1986) after a minimum 6-hour stagnation period. 90th Percentile Rank = Total Number of Valid Samples × 0.90 \text{90th Percentile Rank} = \text{Total Number of Valid Samples} \times 0.90 90th Percentile Rank = Total Number of Valid Samples × 0.90
To determine compliance:
Sort all sample results in ascending order (from lowest to highest concentration).
Calculate the rank position ( N × 0.90 N \times 0.90 N × 0.90 ).
If the concentration at the 90th percentile rank exceeds 0.015 mg/L 0.015\text{ mg/L} 0.015 mg/L for lead or 1.3 mg/L 1.3\text{ mg/L} 1.3 mg/L for copper, an Action Level Exceedance (ALE) occurs. Example (20 Samples): Rank = 20 x 0.90 = 18th sample value.
If the 18th sorted sample is 0.018 mg/L Lead -> System exceeds 0.015 mg/L Action Level.
Mandatory Actions Following an Action Level Exceedance:
Monitor water quality parameters (WQPs) including pH, alkalinity, calcium, and inhibitor residual.
Submit an Optimal Corrosion Control Treatment (OCCT) recommendation to CDPHE.
Deliver mandatory public education materials to all consumers within 60 days (and public notice within 24 hours for lead exceedances under updated rules).
Accelerate mandatory Lead Service Line (LSL) replacement programs.
Loading diagram... Corrosion Control Mechanisms & Municipal Fluoridation Architecture
2. Optimal Corrosion Control Treatment (OCCT) Mechanisms
Corrosion in water distribution systems is an electrochemical process where metals give up electrons to water (anodic reaction), dissolving metal ions into solution. Utilities control internal pipe corrosion through two primary strategies:
Strategy A: Calcium Carbonate ( CaCO 3 \text{CaCO}_3 CaCO 3 ) Precipitation / Saturation Control
Utilities adjust water pH, calcium hardness, and alkalinity to deposit a thin, protective eggshell layer of calcium carbonate scale along pipe interiors.
Langelier Saturation Index (LSI): LSI = pH − pH s \text{LSI} = \text{pH} - \text{pH}_s LSI = pH − pH s Where pH \text{pH} pH is measured water pH and pH s \text{pH}_s pH s is the theoretical saturation pH where water is in thermodynamic equilibrium with CaCO 3 \text{CaCO}_3 CaCO 3 .
LSI = 0.0 \text{LSI} = 0.0 LSI = 0.0 : Water is in perfect chemical equilibrium; neither scale-forming nor corrosive.
LSI > 0.0 \text{LSI} > 0.0 LSI > 0.0 (Positive): Water is supersaturated with CaCO 3 \text{CaCO}_3 CaCO 3 ; tends to precipitate protective scale.
LSI < 0.0 \text{LSI} < 0.0 LSI < 0.0 (Negative): Water is undersaturated (aggressive); tends to dissolve calcium scale and corrode plumbing metals.
Ryznar Stability Index (RSI): RSI = 2 ( pH s ) − pH \text{RSI} = 2(\text{pH}_s) - \text{pH} RSI = 2 ( pH s ) − pH . Values < 6.5 < 6.5 < 6.5 indicate scale-forming water; values > 7.0 > 7.0 > 7.0 indicate corrosive water.
Strategy B: Chemical Passivation via Phosphate Inhibitors
In soft or low-alkalinity waters where calcium carbonate precipitation is impractical, utilities add orthophosphate ( PO 4 3 − \text{PO}_4^{3-} PO 4 3 − ) (fed as phosphoric acid H 3 PO 4 \text{H}_3\text{PO}_4 H 3 PO 4 , monosodium phosphate, or zinc orthophosphate). Orthophosphate chemically reacts with dissolved lead and copper ions to form a micro-crystalline, insoluble mineral passivation layer (e.g., lead hydroxyapatite Pb 5 ( PO 4 ) 3 OH \text{Pb}_5(\text{PO}_4)_3\text{OH} Pb 5 ( PO 4 ) 3 OH and pyromorphite ) that shields the pipe wall from the flowing water. Target residual concentrations typically range from 1.0 to 3.0 mg/L as PO 4 \text{PO}_4 PO 4 .
Common Chemicals for pH and Alkalinity Adjustment
Chemical Name Formula Form / Purity Effect on Water Chemistry Operational Handling & Safety
Sodium Hydroxide (Caustic Soda) NaOH \text{NaOH} NaOH 25% or 50% Liquid Solution Increases pH rapidly; negligible effect on alkalinity Highly caustic; 50% solution freezes at 54°F (12°C) , requiring heated storage tanks and heat-traced feed lines.
Hydrated Lime Ca(OH) 2 \text{Ca(OH)}_2 Ca(OH) 2 Dry Powder (90% pure) Increases pH, calcium hardness, and alkalinity Insoluble grit requires slaker tanks; creates turbidity if overfed; airborne dust hazard.
Sodium Carbonate (Soda Ash) Na 2 CO 3 \text{Na}_2\text{CO}_3 Na 2 CO 3 Dry Powder / Granular Increases pH and carbonate alkalinity Safe to handle; dissolves easily in solution tanks; no added calcium.
Sodium Bicarbonate NaHCO 3 \text{NaHCO}_3 NaHCO 3 Dry Powder Increases bicarbonate alkalinity with minimal effect on pH Excellent buffering agent for low-alkalinity mountain source waters.
3. Community Water Fluoridation Practices
Community water fluoridation is the controlled addition of a fluoride compound to public drinking water to achieve an optimal concentration that prevents dental caries (tooth decay).
Public Health Benchmarks & Regulatory Limits
CDC / U.S. Public Health Service Optimal Concentration: 0.7 mg/L \mathbf{0.7\text{ mg/L}} 0.7 mg/L (standardized nationwide to balance cavity prevention against enamel fluorosis).
EPA Primary Maximum Contaminant Level (MCL): 4.0 mg/L \mathbf{4.0\text{ mg/L}} 4.0 mg/L (enforceable health standard to prevent crippling skeletal fluorosis).
EPA Secondary Maximum Contaminant Level (SMCL): 2.0 mg/L \mathbf{2.0\text{ mg/L}} 2.0 mg/L (non-enforceable aesthetic/cosmetic guideline to protect children from dental fluorosis / enamel mottling).
Approved Fluoride Chemicals
Fluorosilicic Acid (Hydrofluorosilicic Acid, H 2 SiF 6 \text{H}_2\text{SiF}_6 H 2 SiF 6 ):
Straw-yellow, fuming, highly corrosive liquid supplied at 23% to 25% active strength .
Specific gravity is approximately 1.21 (weighs ≈ 10.2 lb/gal \approx 10.2\text{ lb/gal} ≈ 10.2 lb/gal ).
Delivers 79.2% fluoride ion within the pure active molecule.
Most common chemical in medium and large water treatment plants; fed directly neat using peristaltic or diaphragm metering pumps from day tanks on load cells/scales.
Sodium Fluoride ( NaF \text{NaF} NaF ):
White crystalline powder or coarse granules ( 98% pure , containing 45.2% available fluoride ion ).
Predominantly fed using downflow saturators : water passes through a bed of granular NaF \text{NaF} NaF to produce a constant, self-limiting 4.0% saturated solution (18,000 mg/L F⁻) at room temperature ( 77 ∘ F 77^\circ\text{F} 7 7 ∘ F ).
Sodium Fluorosilicate ( Na 2 SiF 6 \text{Na}_2\text{SiF}_6 Na 2 SiF 6 ):
White, odorless powder ( 98.5% pure , containing 60.7% available fluoride ion ).
Fed via gravimetric or volumetric dry chemical feeders with mechanical dissolving tanks.
Safety, Interlocks, and Operational Monitoring
Feed Interlocks: Fluoride chemical feed pumps must be electrically interlocked with primary raw/finished water flow meters so the pump cannot operate if water flow ceases, preventing dangerous chemical overfeeds.
Daily Testing: Operators must test finished water fluoride concentrations daily using the SPADNS colorimetric method or an Ion-Selective Electrode (ISE) probe.