Study guide
2.9 Direct, In-Line, Pressure, Cartridge & Diatomaceous Earth Filtration
Colorado Water/Wastewater Operator Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: State Laws, Regulations & CCWP Certification
1.1 CDPHE CCWP Program & Regulatory Framework (Regulation 100 / 5 CCR 1003-2) 1.2 Facility Classification & Operator in Responsible Charge (ORC) Requirements 1.3 Certification Levels, Education, Experience & Exam Eligibility (Class D-A, Grade 1-4, Class S/T) 1.4 License Renewal, Training Units (TUs) & Mandatory Regulatory Training 1.5 Colorado Primary Drinking Water Regulations (Regulation 11) & Compliance 1.6 Colorado Discharge Permit System (Regulations 61/62), DMRs & Biosolids Reporting
2 Chapter 2: Source Water & Drinking Water Treatment Processes
2.1 Raw Water Sources, High-Altitude Characteristics & Reservoir Quality 2.2 Coagulation Chemistry, Rapid Mixing & Chemical Dosing (Alum, Ferric, Polymers) 2.3 Flocculation & Sedimentation Basin Design, Operation & Settling Zones 2.4 Granular Media Filtration, Backwash Procedures & Turbidity Standards 2.5 Advanced Treatment: Membranes, Softening, GAC/PAC Adsorption & Aeration 2.6 Groundwater Sources, Well Hydraulics, Static and Pumping Levels & Specific Capacity 2.7 Source Water Characteristics, Contaminant Categories & Watershed Protection Plans 2.8 Pretreatment: Presedimentation, Aeration, Algae Control & Taste-and-Odor Management 2.9 Direct, In-Line, Pressure, Cartridge & Diatomaceous Earth Filtration 2.10 Lime-Soda Softening, Ion Exchange & Water Stabilization 2.11 Water Treatment Plant Residuals: Lagoons, Drying Beds, Land Application & Recycle
3 Chapter 3: Disinfection & Chemical Addition
3.1 Chlorine Chemistry: Hypochlorous Acid, Free/Combined Residual & Breakpoint Chlorination 3.2 Disinfection Kinetics, Baffle Factors, T10 & CT Compliance Calculations 3.3 Disinfection Byproducts (TTHMs, HAA5s) & Stage 1/2 DBP Rules 3.4 Alternative Disinfection: Chloramination, Ultraviolet (UV) Light & Chlorine Dioxide 3.5 Corrosion Control, Lead & Copper Rule Revisions (LCRR) & Fluoridation Practices
4 Chapter 4: Water Treatment Plant Equipment, Instrumentation & Maintenance
4.1 Raw Water Intakes, Screening Equipment & Raw Water Pumping 4.2 Chemical Feed Equipment: Feeders, Day Tanks, Carrier Water & Feed-Rate Calibration 4.3 Chlorination Equipment: Gas Systems, Vacuum Regulators, Hypochlorite Storage & Onsite Generation 4.4 Filter Underdrains, Support Gravel, Surface Wash, Air Scour & Filter-to-Waste 4.5 Plant Process Control, SCADA and PLC Systems, Alarm Management & Records of Operation 4.6 Preventive, Corrective and Predictive Maintenance, Work Orders & Asset Management
5 Chapter 5: Wastewater Treatment Principles & Biological Processes
5.1 Preliminary Treatment: Bar Screens, Shredders, Grit Chambers & Flow Equalization 5.2 Primary Clarification, Solids Separation & Scum Removal Mechanics 5.3 Activated Sludge Fundamentals: Aerobic Microbiology, DO Control & Biomass Growth 5.4 Return & Waste Activated Sludge Management (RAS/WAS Operations & Sludge Age) 5.5 Activated Sludge Troubleshooting: Bulking, Nocardia Foaming, Rising Sludge & Pin Floc 5.6 Wastewater Characteristics, Organic and Hydraulic Loading, Diurnal Flow & Septicity 5.7 Activated Sludge Arrangements: Conventional, Complete Mix, Step Feed, Contact Stabilization, Extended Aeration, Oxidation Ditch, SBR & MBR 5.8 Aeration Systems: Blowers, Diffusers, Surface Aerators, Oxygen Transfer & Altitude Effects
6 Chapter 6: Advanced Wastewater Treatment & Solids Management
6.1 Biological Nutrient Removal: Nitrification, Denitrification & Anoxic Zones 6.2 Biological & Chemical Phosphorus Removal (EBPR & Coagulant Precipitation) 6.3 Sludge Thickening, Aerobic & Anaerobic Digestion (Mesophilic/Thermophilic) 6.4 Dewatering Equipment (Centrifuges, Belt Filter Presses) & Biosolids Standards (Reg 64) 6.5 Pond & Lagoon Operations, Trickling Filters & Rotating Biological Contactors (RBCs) 6.6 Secondary Clarification: Overflow and Solids Loading Rates, RAS Rate Setting & Clarifier Diagnostics 6.7 Tertiary Filtration, Effluent Polishing & Wastewater Disinfection with Chlorine, Dechlorination and UV 6.8 Effluent Disposal, Rapid Infiltration Basins, Colorado Water Reuse Law & Regulation 84
7 Chapter 7: Water Distribution Systems
7.1 Distribution Hydraulics, Pressure Zones, Static Head & Friction Headloss 7.2 Finished Water Storage Tanks, Standpipes, Mixing & Water Age Control 7.3 Distribution Piping, Valves (Gate, Butterfly, PRV), Hydrants & Main Flushing 7.4 Cross-Connection Control, Hazard Assessment & Backflow Preventers (RPZ, DCVA, PVB, Air Gap) 7.5 Water Main Installation, Trenching, Repair, Pressure Testing & Disinfection (AWWA C651) 7.6 Network Layout, Pressure Zones, Demand Patterns, Fire Flow & the Hydraulic Grade Line 7.7 Fire Hydrants, Dry Barrel Operation, Fire Flow Testing & Unidirectional Flushing 7.8 Booster Pump Stations, Hydropneumatic Systems, Controls & Surge Protection 7.9 Customer and Master Metering, Meter Sizing, Accuracy Testing, AMR & AMI 7.10 System Mapping, GIS, As-Builts, Operational Analysis & the AWWA Water Audit 7.11 Service Line Installation, Wet Tapping, Curb Stops & the Lead Service Line Inventory 7.12 Leak Detection, District Metered Areas, Minimum Night Flow & Pressure Management 7.13 Storage Facility Inspection, Sanitary Defects, Water Age Control, Cleaning & AWWA C652 Disinfection 7.14 Utility Locating, Colorado 811 Damage Prevention, the APWA Color Code & New Construction Inspection 7.15 Well and Wellhead Maintenance, Sanitary Condition, Rehabilitation & AWWA C654 Disinfection 7.16 Booster Chlorination, Remote Chemical Feed, Chemical Storage, Security & Supply Management 7.17 Distribution Sampling Technique, Chlorine Residual Monitoring & Nitrification Control in Chloraminated Systems
8 Chapter 8: Wastewater Collection Systems
8.1 Gravity Collection Systems: Flow Velocities, Slopes, Pipe Materials & Manholes 8.2 Wastewater Lift Stations: Wet Wells, Submersible Pumps, Level Controls & Force Mains 8.3 Inflow and Infiltration (I&I) Sources, Flow Monitoring, Smoke Testing & CCTV Inspection 8.4 Collection Maintenance: Hydraulic Jetting, Mechanical Rodding & FOG/Root Mitigation 8.5 Sanitary Sewer Overflows (SSOs): Root Causes, Containment, Reporting & Mitigation 8.6 Lift Station Electrical Devices, Level Detection, Telemetry, Gas Detection & Capacity Adjustment 8.7 Lift Station Configurations, Preventive Maintenance, Wet Well Cleaning, Troubleshooting & Emergency Bypass Pumping 8.8 Collection System Rehabilitation: CIPP, Pipe Bursting, Sliplining, Grouting, Manhole Repair & Tap Defects 8.9 Excavation, Hydro Excavation, Bedding and Haunching, Grade Control & Sewer Acceptance Testing 8.10 Collection System Flow Monitoring, Area-Velocity Metering, Weirs and Flumes & Capacity Assessment
9 Chapter 9: Pumps, Motors & Utility Mechanics
9.1 Centrifugal Pumps: Volutes, Impellers, Packing Seals & Mechanical Seals 9.2 Positive Displacement Pumps (Peristaltic, Diaphragm, Progressive Cavity) & Dosing Systems 9.3 Pump Performance Curves, System Head Curves, Cavitation & NPSH Calculations 9.4 Electric Motors (Single/Three Phase), Controls, Variable Frequency Drives (VFDs) & Power 9.5 Flow Meters (Venturi, Magnetic, Ultrasonic), Online Analyzers, PLCs & SCADA Telemetry 9.6 Air Compressors, Conveyors, Hoists and Cranes, Service Piping & Standby Power Generation 9.7 Valve Types and Duties, Air Release and Air-Vacuum Valves, Water Hammer & Surge Control
10 Chapter 10: Laboratory Analysis & Water Quality Monitoring
10.1 Regulatory Sampling Procedures, Chain of Custody, Holding Times & Preservation Techniques 10.2 Physical & Chemical Drinking Water Testing: Turbidity, pH, Alkalinity, Hardness & Chlorine (DPD) 10.3 Wastewater Laboratory Analysis: BOD5, COD, Total Suspended Solids (TSS) & Settleometry 10.4 Microbiological Testing: Total Coliform, E. coli (Colilert, Membrane Filtration) & QA/QC 10.5 Bench-Scale Jar Testing, Coagulant Optimization & Streaming Current Monitoring 10.6 Laboratory Equipment, Calibration and Verification, QA/QC Program & Certified Laboratory Requirements 10.7 Nutrient Series, Metals Sampling, Whole Effluent Toxicity & Electrode Measurements (DO, pH, ORP, H2S)
11 Chapter 11: Operator Mathematics & Applied Calculations
11.1 Core Conversions, Geometric Area, Pipe Volume & Continuous Flow Rate (MGD, GPM, cfs) 11.2 Chemical Dosage, The Standard "Pounds Formula", Active Chemical & Solution Purity 11.3 Hydraulic Retention Time (HRT), Surface Overflow Rate (SOR) & Weir Overflow Rates 11.4 Process Control Calculations: F/M Ratio, MCRT/Solids Retention Time (SRT) & Sludge Volume Index (SVI) 11.5 Distribution Pressure, Static vs Dynamic Head, Water Horsepower & Wire-to-Water Efficiency 11.6 CT Calculations: Baffling Factors, T10, Temperature and pH Corrections & Multi-Segment Compliance
12 Chapter 12: Safety, Emergency Operations & Compliance
12.1 Permit-Required Confined Space (PRCS) Entry, Atmospheric Testing (O2/LEL/H2S/CO) & Rescue 12.2 Control of Hazardous Energy: Lockout/Tagout (LOTO), Arc Flash & Electrical Safety 12.3 Chemical Safety: Chlorine Gas Handling, Ton Cylinders, Sulfur Dioxide, Ammonia & SDS/GHS 12.4 Trenching & Excavation: Soil Classification, Sloping, Shoring, Shielding & Competent Person Rules 12.5 Emergency Action Plans, Security Vulnerability, Spill Containment & CDPHE Tier 1/2/3 Public Notice 12.6 Work Zone Traffic Control, PPE, Fall Protection, Fire Extinguishers, First Aid & Bloodborne Pathogens 12.7 Standard Operating Procedures, Operating Records, Regulatory Reporting, Customer Complaints & Supervisory Duties
2.9 Direct, In-Line, Pressure, Cartridge & Diatomaceous Earth Filtration
Key Takeaways Explain This Topic AI
Direct filtration omits the sedimentation basin, so it is limited to consistently high-quality raw water, generally under about 10 NTU turbidity and 40 units of color.
In-line filtration omits both flocculation and sedimentation, feeding coagulant directly ahead of the filter, and it demands the cleanest raw water of all the granular media options.
Pressure filters run inside a closed steel vessel, so the operator cannot see the media and must rely on differential pressure and effluent turbidity for control.
Diatomaceous earth filtration builds a precoat cake on a septum and requires continuous body feed, and it is restricted to raw water below about 10 NTU with low algae.
Bag and cartridge filters for Surface Water Treatment Rule compliance are challenge-tested for Cryptosporidium credit and must be changed on differential pressure, never washed and reused.
Last updated: August 2026
Filtration alternatives to the conventional train
Conventional treatment — coagulation, flocculation, sedimentation, filtration — is the general-purpose answer and is covered elsewhere in this guide. But Colorado has hundreds of small systems drawing from clear mountain streams, springs, and reservoirs where a full conventional plant is neither necessary nor affordable. Regulation 100's classification table lists these alternatives separately for exactly that reason, and the WPI outline expects an operator to know which one fits a source.
- The family tree Coagulant fed
- |
- +-----------------+------------------+------------------+
- | | | |
- CONVENTIONAL DIRECT IN-LINE NO COAGULANT
- rapid mix rapid mix rapid mix (slow sand, DE,
- flocculation flocculation (no floc) bag/cartridge,
- sedimentation (NO sed.) (no sed.) membranes)
- filtration filtration filtration
Each step to the right removes a unit process and therefore removes a buffer. The raw water must be correspondingly better.
Direct filtration
Direct filtration feeds coagulant, mixes, flocculates, and sends the water straight to the filters with no sedimentation basin . All the solids removal happens in the media.
Suitability limits generally cited:
- Parameter Practical limit for direct filtration
- Turbidity Consistently below roughly 10 to 15 NTU
- Color Below roughly 40 color units
- Algae Low counts; blooms rapidly plug filters
- Total organic carbon Low; high TOC needs enhanced coagulation and settling
Operating differences that matter:
Coagulant doses are lower than conventional practice, because the goal is a small, filterable pinpoint floc rather than a large settleable one. Overdosing a direct filtration plant blinds the filter surface and collapses run length.
Filter run lengths are shorter and backwash frequency higher, because everything the coagulant captures ends up in the bed.
Filter aid polymer , fed just ahead of the filters at fractions of a milligram per liter, strengthens floc so it penetrates the bed rather than mudballing at the surface.
There is no settled-water turbidity to watch, so the operator's only warning of a coagulation problem is the filter effluent itself. Continuous filter effluent turbidity monitoring and streaming current or jar testing become the primary controls.
In-line filtration removes flocculation as well; coagulant is injected in the pipe just ahead of the filters and floc forms in the media. It requires the cleanest and steadiest raw water of any coagulant-based process and leaves the operator no reaction time at all.
Pressure filters
A pressure filter is the same granular media bed, but installed inside a closed cylindrical steel vessel — vertical or horizontal — operated under system pressure. Because water enters and leaves under pressure, no repumping is needed after filtration, which is why pressure filters are so common on small groundwater iron and manganese systems and on pool and industrial applications.
Advantages: compact, skid mounted, low capital cost, no intermediate pumping.
Disadvantages, and every one of them is an exam point:
You cannot see the media. There is no visual inspection of the bed surface, no watching the backwash, no checking for mudballs or media loss without opening the vessel.
Air binding and short-circuiting are hard to detect except through headloss trends.
Backwash is limited by vessel geometry and available flow, and inadequate backwash leads to cemented media.
Higher differential pressure can be forced across a fouled bed , which pushes floc and turbidity through rather than triggering a backwash the way a gravity filter's declining rate would.
For that last reason, pressure filters used for Surface Water Treatment Rule compliance are viewed cautiously by regulators, and continuous effluent turbidity monitoring plus a hard differential pressure setpoint substitute for the operator's eyes.
Diatomaceous earth filtration
Diatomaceous earth (DE) filtration uses the fossilized skeletons of diatoms as a filter medium built up as a precoat cake on a septum — a rigid porous element of wire cloth, porous stone, or synthetic fabric.
The operating cycle:
Precoat. A slurry of DE is recirculated until roughly 0.1 to 0.2 pounds per square foot of septum area has deposited as a uniform cake, typically 1/8 inch thick.
Filtration with body feed. DE is continuously metered into the influent so fresh medium deposits along with the captured solids. Without body feed the cake blinds almost immediately. Body feed rate is proportional to raw water solids.
Backwash and recoat. When terminal headloss is reached, flow stops, the cake sloughs off, and the cycle restarts with a fresh precoat.
DE filtration removes Giardia cysts very effectively and is credited under the Surface Water Treatment Rules, but it is limited to low-turbidity raw water, generally below about 10 NTU , with low algae and low color, and it is essentially a batch process requiring careful operator attention. Regulation 100 classifies slow sand and diatomaceous earth plants as Class C below 350 gpm.
Safety: DE is a crystalline silica dust hazard. Handling requires respiratory protection, dust control, and adherence to the silica standard.
Bag and cartridge filtration
Cartridge filters are disposable pleated or wound elements in a housing; bag filters are fabric bags in a basket. Both are widely used on small systems and as pretreatment ahead of membranes and UV.
Key operating principles:
Absolute versus nominal rating. A nominal 5 micron cartridge removes "most" particles at that size; an absolute rating is a verified removal efficiency and is what regulators require for pathogen credit.
For Surface Water Treatment Rule compliance , bag and cartridge filters must be challenge tested by the manufacturer to establish a Cryptosporidium log removal credit under LT2, and the system must operate them within the tested conditions. Regulation 100 classifies compliance bag or cartridge filtration as Class C or B depending on flow, while non-SWTR use is treated as sediment pre-filtration at Class D or C.
Change-out is triggered by differential pressure , not by a calendar. A typical terminal differential is 15 to 25 psid, with the manufacturer's maximum being the hard limit — exceeding it can rupture the element and dump captured solids downstream.
Elements are not cleaned and reused. Backwashing or washing a cartridge destroys the pore structure and voids any removal credit.
Pretreatment matters. Cartridges plug quickly on water with appreciable turbidity or iron, which is why bags are often installed upstream as a roughing stage.
Sanitary handling. Change-outs open the treated water side of the barrier. Disinfect the housing, wear clean gloves, and follow with a chlorine flush and, where required, bacteriological clearance.
Choosing between them
- Raw water condition Best fit
- Variable turbidity above 15 NTU, seasonal spikes Conventional with sedimentation
- Consistently below 10 NTU, low color and algae Direct filtration
- Very clean, extremely steady In-line filtration
- Groundwater iron and manganese, small system Pressure filter with oxidation
- Clean surface water, small system, skilled operator Diatomaceous earth
- Very small system, low turbidity, minimal staffing Bag or cartridge with challenge-tested credit
The unifying principle is simple: the fewer barriers upstream of the filter, the better and steadier the raw water must be, and the more the operator must rely on continuous instrumentation rather than observation.