2.8 Pretreatment: Presedimentation, Aeration, Algae Control & Taste-and-Odor Management
Colorado Water/Wastewater Operator Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: State Laws, Regulations & CCWP Certification
1.1 CDPHE CCWP Program & Regulatory Framework (Regulation 100 / 5 CCR 1003-2) 1.2 Facility Classification & Operator in Responsible Charge (ORC) Requirements 1.3 Certification Levels, Education, Experience & Exam Eligibility (Class D-A, Grade 1-4, Class S/T) 1.4 License Renewal, Training Units (TUs) & Mandatory Regulatory Training 1.5 Colorado Primary Drinking Water Regulations (Regulation 11) & Compliance 1.6 Colorado Discharge Permit System (Regulations 61/62), DMRs & Biosolids Reporting
2 Chapter 2: Source Water & Drinking Water Treatment Processes
2.1 Raw Water Sources, High-Altitude Characteristics & Reservoir Quality 2.2 Coagulation Chemistry, Rapid Mixing & Chemical Dosing (Alum, Ferric, Polymers) 2.3 Flocculation & Sedimentation Basin Design, Operation & Settling Zones 2.4 Granular Media Filtration, Backwash Procedures & Turbidity Standards 2.5 Advanced Treatment: Membranes, Softening, GAC/PAC Adsorption & Aeration 2.6 Groundwater Sources, Well Hydraulics, Static and Pumping Levels & Specific Capacity 2.7 Source Water Characteristics, Contaminant Categories & Watershed Protection Plans 2.8 Pretreatment: Presedimentation, Aeration, Algae Control & Taste-and-Odor Management 2.9 Direct, In-Line, Pressure, Cartridge & Diatomaceous Earth Filtration 2.10 Lime-Soda Softening, Ion Exchange & Water Stabilization 2.11 Water Treatment Plant Residuals: Lagoons, Drying Beds, Land Application & Recycle
3 Chapter 3: Disinfection & Chemical Addition
3.1 Chlorine Chemistry: Hypochlorous Acid, Free/Combined Residual & Breakpoint Chlorination 3.2 Disinfection Kinetics, Baffle Factors, T10 & CT Compliance Calculations 3.3 Disinfection Byproducts (TTHMs, HAA5s) & Stage 1/2 DBP Rules 3.4 Alternative Disinfection: Chloramination, Ultraviolet (UV) Light & Chlorine Dioxide 3.5 Corrosion Control, Lead & Copper Rule Revisions (LCRR) & Fluoridation Practices
4 Chapter 4: Water Treatment Plant Equipment, Instrumentation & Maintenance
4.1 Raw Water Intakes, Screening Equipment & Raw Water Pumping 4.2 Chemical Feed Equipment: Feeders, Day Tanks, Carrier Water & Feed-Rate Calibration 4.3 Chlorination Equipment: Gas Systems, Vacuum Regulators, Hypochlorite Storage & Onsite Generation 4.4 Filter Underdrains, Support Gravel, Surface Wash, Air Scour & Filter-to-Waste 4.5 Plant Process Control, SCADA and PLC Systems, Alarm Management & Records of Operation 4.6 Preventive, Corrective and Predictive Maintenance, Work Orders & Asset Management
5 Chapter 5: Wastewater Treatment Principles & Biological Processes
5.1 Preliminary Treatment: Bar Screens, Shredders, Grit Chambers & Flow Equalization 5.2 Primary Clarification, Solids Separation & Scum Removal Mechanics 5.3 Activated Sludge Fundamentals: Aerobic Microbiology, DO Control & Biomass Growth 5.4 Return & Waste Activated Sludge Management (RAS/WAS Operations & Sludge Age) 5.5 Activated Sludge Troubleshooting: Bulking, Nocardia Foaming, Rising Sludge & Pin Floc 5.6 Wastewater Characteristics, Organic and Hydraulic Loading, Diurnal Flow & Septicity 5.7 Activated Sludge Arrangements: Conventional, Complete Mix, Step Feed, Contact Stabilization, Extended Aeration, Oxidation Ditch, SBR & MBR 5.8 Aeration Systems: Blowers, Diffusers, Surface Aerators, Oxygen Transfer & Altitude Effects
6 Chapter 6: Advanced Wastewater Treatment & Solids Management
6.1 Biological Nutrient Removal: Nitrification, Denitrification & Anoxic Zones 6.2 Biological & Chemical Phosphorus Removal (EBPR & Coagulant Precipitation) 6.3 Sludge Thickening, Aerobic & Anaerobic Digestion (Mesophilic/Thermophilic) 6.4 Dewatering Equipment (Centrifuges, Belt Filter Presses) & Biosolids Standards (Reg 64) 6.5 Pond & Lagoon Operations, Trickling Filters & Rotating Biological Contactors (RBCs) 6.6 Secondary Clarification: Overflow and Solids Loading Rates, RAS Rate Setting & Clarifier Diagnostics 6.7 Tertiary Filtration, Effluent Polishing & Wastewater Disinfection with Chlorine, Dechlorination and UV 6.8 Effluent Disposal, Rapid Infiltration Basins, Colorado Water Reuse Law & Regulation 84
7 Chapter 7: Water Distribution Systems
7.1 Distribution Hydraulics, Pressure Zones, Static Head & Friction Headloss 7.2 Finished Water Storage Tanks, Standpipes, Mixing & Water Age Control 7.3 Distribution Piping, Valves (Gate, Butterfly, PRV), Hydrants & Main Flushing 7.4 Cross-Connection Control, Hazard Assessment & Backflow Preventers (RPZ, DCVA, PVB, Air Gap) 7.5 Water Main Installation, Trenching, Repair, Pressure Testing & Disinfection (AWWA C651) 7.6 Network Layout, Pressure Zones, Demand Patterns, Fire Flow & the Hydraulic Grade Line 7.7 Fire Hydrants, Dry Barrel Operation, Fire Flow Testing & Unidirectional Flushing 7.8 Booster Pump Stations, Hydropneumatic Systems, Controls & Surge Protection 7.9 Customer and Master Metering, Meter Sizing, Accuracy Testing, AMR & AMI 7.10 System Mapping, GIS, As-Builts, Operational Analysis & the AWWA Water Audit 7.11 Service Line Installation, Wet Tapping, Curb Stops & the Lead Service Line Inventory 7.12 Leak Detection, District Metered Areas, Minimum Night Flow & Pressure Management 7.13 Storage Facility Inspection, Sanitary Defects, Water Age Control, Cleaning & AWWA C652 Disinfection 7.14 Utility Locating, Colorado 811 Damage Prevention, the APWA Color Code & New Construction Inspection 7.15 Well and Wellhead Maintenance, Sanitary Condition, Rehabilitation & AWWA C654 Disinfection 7.16 Booster Chlorination, Remote Chemical Feed, Chemical Storage, Security & Supply Management 7.17 Distribution Sampling Technique, Chlorine Residual Monitoring & Nitrification Control in Chloraminated Systems
8 Chapter 8: Wastewater Collection Systems
8.1 Gravity Collection Systems: Flow Velocities, Slopes, Pipe Materials & Manholes 8.2 Wastewater Lift Stations: Wet Wells, Submersible Pumps, Level Controls & Force Mains 8.3 Inflow and Infiltration (I&I) Sources, Flow Monitoring, Smoke Testing & CCTV Inspection 8.4 Collection Maintenance: Hydraulic Jetting, Mechanical Rodding & FOG/Root Mitigation 8.5 Sanitary Sewer Overflows (SSOs): Root Causes, Containment, Reporting & Mitigation 8.6 Lift Station Electrical Devices, Level Detection, Telemetry, Gas Detection & Capacity Adjustment 8.7 Lift Station Configurations, Preventive Maintenance, Wet Well Cleaning, Troubleshooting & Emergency Bypass Pumping 8.8 Collection System Rehabilitation: CIPP, Pipe Bursting, Sliplining, Grouting, Manhole Repair & Tap Defects 8.9 Excavation, Hydro Excavation, Bedding and Haunching, Grade Control & Sewer Acceptance Testing 8.10 Collection System Flow Monitoring, Area-Velocity Metering, Weirs and Flumes & Capacity Assessment
9 Chapter 9: Pumps, Motors & Utility Mechanics
9.1 Centrifugal Pumps: Volutes, Impellers, Packing Seals & Mechanical Seals 9.2 Positive Displacement Pumps (Peristaltic, Diaphragm, Progressive Cavity) & Dosing Systems 9.3 Pump Performance Curves, System Head Curves, Cavitation & NPSH Calculations 9.4 Electric Motors (Single/Three Phase), Controls, Variable Frequency Drives (VFDs) & Power 9.5 Flow Meters (Venturi, Magnetic, Ultrasonic), Online Analyzers, PLCs & SCADA Telemetry 9.6 Air Compressors, Conveyors, Hoists and Cranes, Service Piping & Standby Power Generation 9.7 Valve Types and Duties, Air Release and Air-Vacuum Valves, Water Hammer & Surge Control
10 Chapter 10: Laboratory Analysis & Water Quality Monitoring
10.1 Regulatory Sampling Procedures, Chain of Custody, Holding Times & Preservation Techniques 10.2 Physical & Chemical Drinking Water Testing: Turbidity, pH, Alkalinity, Hardness & Chlorine (DPD) 10.3 Wastewater Laboratory Analysis: BOD5, COD, Total Suspended Solids (TSS) & Settleometry 10.4 Microbiological Testing: Total Coliform, E. coli (Colilert, Membrane Filtration) & QA/QC 10.5 Bench-Scale Jar Testing, Coagulant Optimization & Streaming Current Monitoring 10.6 Laboratory Equipment, Calibration and Verification, QA/QC Program & Certified Laboratory Requirements 10.7 Nutrient Series, Metals Sampling, Whole Effluent Toxicity & Electrode Measurements (DO, pH, ORP, H2S)
11 Chapter 11: Operator Mathematics & Applied Calculations
11.1 Core Conversions, Geometric Area, Pipe Volume & Continuous Flow Rate (MGD, GPM, cfs) 11.2 Chemical Dosage, The Standard "Pounds Formula", Active Chemical & Solution Purity 11.3 Hydraulic Retention Time (HRT), Surface Overflow Rate (SOR) & Weir Overflow Rates 11.4 Process Control Calculations: F/M Ratio, MCRT/Solids Retention Time (SRT) & Sludge Volume Index (SVI) 11.5 Distribution Pressure, Static vs Dynamic Head, Water Horsepower & Wire-to-Water Efficiency 11.6 CT Calculations: Baffling Factors, T10, Temperature and pH Corrections & Multi-Segment Compliance
12 Chapter 12: Safety, Emergency Operations & Compliance
12.1 Permit-Required Confined Space (PRCS) Entry, Atmospheric Testing (O2/LEL/H2S/CO) & Rescue 12.2 Control of Hazardous Energy: Lockout/Tagout (LOTO), Arc Flash & Electrical Safety 12.3 Chemical Safety: Chlorine Gas Handling, Ton Cylinders, Sulfur Dioxide, Ammonia & SDS/GHS 12.4 Trenching & Excavation: Soil Classification, Sloping, Shoring, Shielding & Competent Person Rules 12.5 Emergency Action Plans, Security Vulnerability, Spill Containment & CDPHE Tier 1/2/3 Public Notice 12.6 Work Zone Traffic Control, PPE, Fall Protection, Fire Extinguishers, First Aid & Bloodborne Pathogens 12.7 Standard Operating Procedures, Operating Records, Regulatory Reporting, Customer Complaints & Supervisory Duties
2.8 Pretreatment: Presedimentation, Aeration, Algae Control & Taste-and-Odor Management
Key Takeaways Explain This Topic AI
Presedimentation removes heavy sand and silt ahead of coagulation, protecting pumps and reducing coagulant demand during high-turbidity runoff events.
Aeration adds oxygen and strips volatile compounds, so it removes carbon dioxide, hydrogen sulfide, methane, radon, and volatile organics and oxidizes iron and manganese.
Potassium permanganate is fed at the intake or raw water line so oxidation is complete before filtration, and overdosing produces pink water and manganese greensand breakthrough.
Powdered activated carbon is dosed as early as possible for contact time but must not be fed at the same point as an oxidant or free chlorine, because each destroys the benefit of the other.
Geosmin and 2-methylisoborneol are detectable at nanograms per liter, are not health hazards, and are best removed by activated carbon or ozone rather than by chlorination.
Last updated: August 2026
Everything that happens before coagulation
Pretreatment is the set of unit processes applied to raw water before the main coagulation, flocculation, sedimentation, and filtration train. Its purpose is to reduce the load on the plant, remove constituents that the main train handles badly, and stabilize a variable source so process control downstream can be steady.
Presedimentation and roughing
Presedimentation is plain gravity settling of raw water, with no coagulant, in a basin or reservoir ahead of the plant. It is standard practice on rivers carrying heavy sand and silt, and its value in Colorado shows up during spring runoff and after wildfire when raw turbidity can jump from 5 NTU to several hundred in hours.
Benefits are concrete:
Removes abrasive sand that would otherwise destroy pump impellers, chemical feed check valves, and meter internals.
Cuts coagulant demand, because the coagulant no longer has to sweep out the fraction that settles on its own.
Buffers turbidity spikes, giving the operator time to adjust dose.
Provides equalization storage during intake interruptions.
Roughing filters — coarse gravel or crushed rock beds operated at low rates — do the same job where basin space is unavailable, and are common ahead of slow sand filters.
Screening ahead of everything removes trash, leaves, and aquatic organisms. Bar racks with 1 to 3 inch openings handle debris; traveling water screens with fine mesh remove leaves, fish, and mussels; microstrainers with 20 to 60 micron fabric remove algae.
Aeration
Aeration transfers gases in both directions across the air and water interface. It adds oxygen and strips volatile gases. That single sentence explains everything it can do:
- Aeration accomplishes Mechanism
- Oxidize dissolved iron and manganese Adds O2
- Remove carbon dioxide (raises pH) Strips CO2
- Remove hydrogen sulfide (rotten-egg odor) Strips H2S
- Remove methane and radon Strips dissolved gas
- Remove volatile organic compounds Strips VOCs
- Reduce some tastes and odors Strips volatile compounds
It cannot remove nonvolatile material: hardness, nitrate, arsenic, fluoride, and total dissolved solids pass straight through.
Three families of equipment appear on the exam:
Waterfall or gravity aerators — cascade, tray (often with coke or ceramic media), and spray nozzles. Water is broken into thin films or droplets falling through air. Tray aerators are the classic groundwater iron and manganese unit.
Diffused aerators — compressed air released through diffusers at the bottom of a contact basin. Effective and enclosed, so off-gas can be controlled, but energy intensive.
Packed tower (air stripping) aerators — water distributed over high-surface-area packing with a countercurrent air stream. This is the workhorse for VOC and radon removal, and the air-to-water ratio is the main control variable.
Aeration side effects an operator must anticipate: stripping CO2 raises pH , which can shift the corrosion balance and change coagulation chemistry; adding oxygen makes the water more corrosive to iron pipe; open aerators are an entry point for airborne contamination , so they need screening and housekeeping; and in cold Colorado weather, exposed cascade aerators ice up .
Oxidation for iron, manganese, and taste and odor
Where aeration is too slow — manganese in particular oxidizes very slowly with oxygen alone below pH 9 — a chemical oxidant is fed at the intake or raw water line so reaction and precipitation are complete before the filters.
Oxidant Typical use Cautions
Chlorine Iron oxidation, disinfection credit, algae control Reacts with TOC to form THMs and HAAs; destroys PAC capacity
Potassium permanganate (KMnO4) Manganese and iron, taste and odor Overdose gives pink water and manganese passing filters; feed point must allow full reaction
Chlorine dioxide Manganese, taste and odor, low THM formation Chlorite and chlorate byproducts are regulated
Ozone Taste and odor, color, manganese, disinfection Forms bromate where bromide is present; requires biologically active filtration downstream
Oxygen (aeration) Iron; manganese only at high pH Slow for manganese
Potassium permanganate deserves particular attention because it is heavily tested. It is a purple crystalline solid mixed into solution and fed by metering pump. Correct dosing turns the raw water faintly pink, and the color must disappear before the water reaches the filters. Persistent pink water leaving a filter means the dose is too high — excess permanganate is passing through and will produce pink water complaints and, on manganese greensand, will bleed manganese. Underdosing leaves soluble manganese that oxidizes later in the distribution system and produces black water complaints. Manganese greensand filters are regenerated with permanganate, either continuously or intermittently.
Taste and odor
The two compounds responsible for most earthy and musty complaints are geosmin and 2-methylisoborneol (MIB) , produced by cyanobacteria and actinomycetes. Human threshold detection is in the range of 5 to 10 nanograms per liter — parts per trillion — which is why customers can taste something no routine analysis will show. Neither compound is a health hazard, but complaints about them dominate customer contact during late-summer reservoir blooms.
Effective responses, roughly in order of practicality:
Change the intake depth to draw below the bloom.
Powdered activated carbon (PAC) , dosed typically 5 to 30 mg/L.
Ozone or chlorine dioxide oxidation.
Granular activated carbon as a filter cap or post-filter adsorber for chronic problems.
Reservoir management — copper sulfate algaecide (with care for aquatic life and for releasing cell contents), aeration or destratification, and nutrient control in the watershed.
Chlorine is the wrong tool. Chlorinating a bloom lyses algal cells, releasing intracellular geosmin, MIB, and potentially cyanotoxins, and simultaneously reacts with the organic load to raise THM and HAA formation. Prechlorination for taste and odor almost always makes complaints worse.
PAC feed point rules
PAC needs contact time to adsorb, so it is dosed as early as practical — at the intake, in the presedimentation basin, or at the rapid mix. Two constraints govern:
Never feed PAC and an oxidant at the same point. Free chlorine, permanganate, or ozone will consume the carbon's adsorption capacity, and the carbon will consume the oxidant. Separate the feed points, or feed PAC first with the oxidant well downstream.
PAC is removed with the floc , so it must be fed upstream of coagulation and settling. Dosing after sedimentation loads the filters with black carbon fines and risks carbon breakthrough into the clearwell.
Housekeeping matters: dry PAC is a combustible dust and a slip hazard when wet, and its handling area needs dust control, bonding and grounding on transfer equipment, and no ignition sources.