Study guide
2.11 Water Treatment Plant Residuals: Lagoons, Drying Beds, Land Application & Recycle
Colorado Water/Wastewater Operator Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: State Laws, Regulations & CCWP Certification
1.1 CDPHE CCWP Program & Regulatory Framework (Regulation 100 / 5 CCR 1003-2) 1.2 Facility Classification & Operator in Responsible Charge (ORC) Requirements 1.3 Certification Levels, Education, Experience & Exam Eligibility (Class D-A, Grade 1-4, Class S/T) 1.4 License Renewal, Training Units (TUs) & Mandatory Regulatory Training 1.5 Colorado Primary Drinking Water Regulations (Regulation 11) & Compliance 1.6 Colorado Discharge Permit System (Regulations 61/62), DMRs & Biosolids Reporting
2 Chapter 2: Source Water & Drinking Water Treatment Processes
2.1 Raw Water Sources, High-Altitude Characteristics & Reservoir Quality 2.2 Coagulation Chemistry, Rapid Mixing & Chemical Dosing (Alum, Ferric, Polymers) 2.3 Flocculation & Sedimentation Basin Design, Operation & Settling Zones 2.4 Granular Media Filtration, Backwash Procedures & Turbidity Standards 2.5 Advanced Treatment: Membranes, Softening, GAC/PAC Adsorption & Aeration 2.6 Groundwater Sources, Well Hydraulics, Static and Pumping Levels & Specific Capacity 2.7 Source Water Characteristics, Contaminant Categories & Watershed Protection Plans 2.8 Pretreatment: Presedimentation, Aeration, Algae Control & Taste-and-Odor Management 2.9 Direct, In-Line, Pressure, Cartridge & Diatomaceous Earth Filtration 2.10 Lime-Soda Softening, Ion Exchange & Water Stabilization 2.11 Water Treatment Plant Residuals: Lagoons, Drying Beds, Land Application & Recycle
3 Chapter 3: Disinfection & Chemical Addition
3.1 Chlorine Chemistry: Hypochlorous Acid, Free/Combined Residual & Breakpoint Chlorination 3.2 Disinfection Kinetics, Baffle Factors, T10 & CT Compliance Calculations 3.3 Disinfection Byproducts (TTHMs, HAA5s) & Stage 1/2 DBP Rules 3.4 Alternative Disinfection: Chloramination, Ultraviolet (UV) Light & Chlorine Dioxide 3.5 Corrosion Control, Lead & Copper Rule Revisions (LCRR) & Fluoridation Practices
4 Chapter 4: Water Treatment Plant Equipment, Instrumentation & Maintenance
4.1 Raw Water Intakes, Screening Equipment & Raw Water Pumping 4.2 Chemical Feed Equipment: Feeders, Day Tanks, Carrier Water & Feed-Rate Calibration 4.3 Chlorination Equipment: Gas Systems, Vacuum Regulators, Hypochlorite Storage & Onsite Generation 4.4 Filter Underdrains, Support Gravel, Surface Wash, Air Scour & Filter-to-Waste 4.5 Plant Process Control, SCADA and PLC Systems, Alarm Management & Records of Operation 4.6 Preventive, Corrective and Predictive Maintenance, Work Orders & Asset Management
5 Chapter 5: Wastewater Treatment Principles & Biological Processes
5.1 Preliminary Treatment: Bar Screens, Shredders, Grit Chambers & Flow Equalization 5.2 Primary Clarification, Solids Separation & Scum Removal Mechanics 5.3 Activated Sludge Fundamentals: Aerobic Microbiology, DO Control & Biomass Growth 5.4 Return & Waste Activated Sludge Management (RAS/WAS Operations & Sludge Age) 5.5 Activated Sludge Troubleshooting: Bulking, Nocardia Foaming, Rising Sludge & Pin Floc 5.6 Wastewater Characteristics, Organic and Hydraulic Loading, Diurnal Flow & Septicity 5.7 Activated Sludge Arrangements: Conventional, Complete Mix, Step Feed, Contact Stabilization, Extended Aeration, Oxidation Ditch, SBR & MBR 5.8 Aeration Systems: Blowers, Diffusers, Surface Aerators, Oxygen Transfer & Altitude Effects
6 Chapter 6: Advanced Wastewater Treatment & Solids Management
6.1 Biological Nutrient Removal: Nitrification, Denitrification & Anoxic Zones 6.2 Biological & Chemical Phosphorus Removal (EBPR & Coagulant Precipitation) 6.3 Sludge Thickening, Aerobic & Anaerobic Digestion (Mesophilic/Thermophilic) 6.4 Dewatering Equipment (Centrifuges, Belt Filter Presses) & Biosolids Standards (Reg 64) 6.5 Pond & Lagoon Operations, Trickling Filters & Rotating Biological Contactors (RBCs) 6.6 Secondary Clarification: Overflow and Solids Loading Rates, RAS Rate Setting & Clarifier Diagnostics 6.7 Tertiary Filtration, Effluent Polishing & Wastewater Disinfection with Chlorine, Dechlorination and UV 6.8 Effluent Disposal, Rapid Infiltration Basins, Colorado Water Reuse Law & Regulation 84
7 Chapter 7: Water Distribution Systems
7.1 Distribution Hydraulics, Pressure Zones, Static Head & Friction Headloss 7.2 Finished Water Storage Tanks, Standpipes, Mixing & Water Age Control 7.3 Distribution Piping, Valves (Gate, Butterfly, PRV), Hydrants & Main Flushing 7.4 Cross-Connection Control, Hazard Assessment & Backflow Preventers (RPZ, DCVA, PVB, Air Gap) 7.5 Water Main Installation, Trenching, Repair, Pressure Testing & Disinfection (AWWA C651) 7.6 Network Layout, Pressure Zones, Demand Patterns, Fire Flow & the Hydraulic Grade Line 7.7 Fire Hydrants, Dry Barrel Operation, Fire Flow Testing & Unidirectional Flushing 7.8 Booster Pump Stations, Hydropneumatic Systems, Controls & Surge Protection 7.9 Customer and Master Metering, Meter Sizing, Accuracy Testing, AMR & AMI 7.10 System Mapping, GIS, As-Builts, Operational Analysis & the AWWA Water Audit 7.11 Service Line Installation, Wet Tapping, Curb Stops & the Lead Service Line Inventory 7.12 Leak Detection, District Metered Areas, Minimum Night Flow & Pressure Management 7.13 Storage Facility Inspection, Sanitary Defects, Water Age Control, Cleaning & AWWA C652 Disinfection 7.14 Utility Locating, Colorado 811 Damage Prevention, the APWA Color Code & New Construction Inspection 7.15 Well and Wellhead Maintenance, Sanitary Condition, Rehabilitation & AWWA C654 Disinfection 7.16 Booster Chlorination, Remote Chemical Feed, Chemical Storage, Security & Supply Management 7.17 Distribution Sampling Technique, Chlorine Residual Monitoring & Nitrification Control in Chloraminated Systems
8 Chapter 8: Wastewater Collection Systems
8.1 Gravity Collection Systems: Flow Velocities, Slopes, Pipe Materials & Manholes 8.2 Wastewater Lift Stations: Wet Wells, Submersible Pumps, Level Controls & Force Mains 8.3 Inflow and Infiltration (I&I) Sources, Flow Monitoring, Smoke Testing & CCTV Inspection 8.4 Collection Maintenance: Hydraulic Jetting, Mechanical Rodding & FOG/Root Mitigation 8.5 Sanitary Sewer Overflows (SSOs): Root Causes, Containment, Reporting & Mitigation 8.6 Lift Station Electrical Devices, Level Detection, Telemetry, Gas Detection & Capacity Adjustment 8.7 Lift Station Configurations, Preventive Maintenance, Wet Well Cleaning, Troubleshooting & Emergency Bypass Pumping 8.8 Collection System Rehabilitation: CIPP, Pipe Bursting, Sliplining, Grouting, Manhole Repair & Tap Defects 8.9 Excavation, Hydro Excavation, Bedding and Haunching, Grade Control & Sewer Acceptance Testing 8.10 Collection System Flow Monitoring, Area-Velocity Metering, Weirs and Flumes & Capacity Assessment
9 Chapter 9: Pumps, Motors & Utility Mechanics
9.1 Centrifugal Pumps: Volutes, Impellers, Packing Seals & Mechanical Seals 9.2 Positive Displacement Pumps (Peristaltic, Diaphragm, Progressive Cavity) & Dosing Systems 9.3 Pump Performance Curves, System Head Curves, Cavitation & NPSH Calculations 9.4 Electric Motors (Single/Three Phase), Controls, Variable Frequency Drives (VFDs) & Power 9.5 Flow Meters (Venturi, Magnetic, Ultrasonic), Online Analyzers, PLCs & SCADA Telemetry 9.6 Air Compressors, Conveyors, Hoists and Cranes, Service Piping & Standby Power Generation 9.7 Valve Types and Duties, Air Release and Air-Vacuum Valves, Water Hammer & Surge Control
10 Chapter 10: Laboratory Analysis & Water Quality Monitoring
10.1 Regulatory Sampling Procedures, Chain of Custody, Holding Times & Preservation Techniques 10.2 Physical & Chemical Drinking Water Testing: Turbidity, pH, Alkalinity, Hardness & Chlorine (DPD) 10.3 Wastewater Laboratory Analysis: BOD5, COD, Total Suspended Solids (TSS) & Settleometry 10.4 Microbiological Testing: Total Coliform, E. coli (Colilert, Membrane Filtration) & QA/QC 10.5 Bench-Scale Jar Testing, Coagulant Optimization & Streaming Current Monitoring 10.6 Laboratory Equipment, Calibration and Verification, QA/QC Program & Certified Laboratory Requirements 10.7 Nutrient Series, Metals Sampling, Whole Effluent Toxicity & Electrode Measurements (DO, pH, ORP, H2S)
11 Chapter 11: Operator Mathematics & Applied Calculations
11.1 Core Conversions, Geometric Area, Pipe Volume & Continuous Flow Rate (MGD, GPM, cfs) 11.2 Chemical Dosage, The Standard "Pounds Formula", Active Chemical & Solution Purity 11.3 Hydraulic Retention Time (HRT), Surface Overflow Rate (SOR) & Weir Overflow Rates 11.4 Process Control Calculations: F/M Ratio, MCRT/Solids Retention Time (SRT) & Sludge Volume Index (SVI) 11.5 Distribution Pressure, Static vs Dynamic Head, Water Horsepower & Wire-to-Water Efficiency 11.6 CT Calculations: Baffling Factors, T10, Temperature and pH Corrections & Multi-Segment Compliance
12 Chapter 12: Safety, Emergency Operations & Compliance
12.1 Permit-Required Confined Space (PRCS) Entry, Atmospheric Testing (O2/LEL/H2S/CO) & Rescue 12.2 Control of Hazardous Energy: Lockout/Tagout (LOTO), Arc Flash & Electrical Safety 12.3 Chemical Safety: Chlorine Gas Handling, Ton Cylinders, Sulfur Dioxide, Ammonia & SDS/GHS 12.4 Trenching & Excavation: Soil Classification, Sloping, Shoring, Shielding & Competent Person Rules 12.5 Emergency Action Plans, Security Vulnerability, Spill Containment & CDPHE Tier 1/2/3 Public Notice 12.6 Work Zone Traffic Control, PPE, Fall Protection, Fire Extinguishers, First Aid & Bloodborne Pathogens 12.7 Standard Operating Procedures, Operating Records, Regulatory Reporting, Customer Complaints & Supervisory Duties
2.11 Water Treatment Plant Residuals: Lagoons, Drying Beds, Land Application & Recycle
Key Takeaways Explain This Topic AI
A conventional surface water plant generates coagulation sludge, filter backwash water, sedimentation basin washwater, and, at softening plants, calcium carbonate sludge.
Alum sludge is gelatinous and difficult to dewater, typically leaving basins at 0.5 to 2 percent solids, while lime softening sludge dewaters readily and can reach 50 percent solids or more.
The Filter Backwash Recycle Rule requires spent filter backwash, thickener supernatant, and liquids from dewatering to be returned upstream of the primary coagulant addition point unless the state approves an alternative.
Drying beds and lagoons rely on evaporation and decanting and work well in Colorado's arid climate, though freezing and thawing also conditions sludge and improves dewaterability.
Residuals discharged to a receiving stream require a CDPS permit, and land application or landfill disposal requires characterization for metals and, for radionuclide-bearing residuals, for radioactivity.
Last updated: August 2026
Every gallon treated produces a residual
A drinking water plant does not destroy contaminants; it concentrates them. Understanding what leaves the plant in the solids stream, and where it goes, is a listed WPI job task and a genuine compliance exposure — a plant that quietly dumps basin sludge to a storm drain has created an unpermitted discharge.
Residual streams from a conventional plant
Stream Source Typical volume Character
Coagulation sludge Sedimentation basin blowdown 0.3 - 1 percent of plant flow Gelatinous alum or ferric floc plus raw water solids
- Filter backwash water Filter washing 2 - 5 percent of plant flow Dilute, 20 - 1,000 mg/L solids
- Filter-to-waste Post-backwash ripening Small Dilute
- Softening sludge Lime softening basins Large mass Calcium carbonate, magnesium hydroxide
- Membrane concentrate NF/RO reject 15 - 30 percent of feed High TDS brine
- Brine Ion exchange regeneration Small volume Very high chloride and TDS
- Spent media and carbon Filter and GAC changeout Occasional Solid waste
Alum sludge is the hardest of these to handle. Aluminum hydroxide floc is a gelatinous, highly hydrated solid that holds water tenaciously. It typically leaves a sedimentation basin at 0.5 to 2 percent solids , which is 98 to 99.5 percent water, and it resists mechanical dewatering. Ferric sludge behaves similarly but is somewhat easier. Lime softening sludge , by contrast, is crystalline calcium carbonate that thickens and dewaters readily, sometimes reaching 50 percent solids or more on a drying bed, and it can often be reused — as agricultural liming agent, as feedstock for lime recalcining at large plants, or as a soil amendment.
Sludge quantity is estimated with the pounds formula applied to what was removed and what was added:
lbs/day of solids ≈ (flow, MGD) × (turbidity or suspended solids removed + coagulant contribution, mg/L) × 8.34
A common exam approximation credits roughly 0.44 pounds of dry solids per pound of alum fed, plus the raw water suspended solids removed.
Handling and treatment
Equalization comes first: backwash and basin blowdown arrive as short, high-rate slugs, and a washwater recovery or equalization basin converts them to a steady flow the rest of the residuals system can handle.
Gravity thickening in a circular thickener with a slow-turning rake concentrates alum sludge from around 1 percent to perhaps 2 to 4 percent solids and produces a clear supernatant. Polymer conditioning improves both the settled solids concentration and supernatant clarity.
Drying beds are sand or paved beds where sludge is spread in layers and dewatered by drainage plus evaporation . They are cheap, need no mechanical equipment, and work particularly well in Colorado's high, dry, sunny climate. Their limitations are land area and weather dependence. One useful Colorado phenomenon: freeze-thaw conditioning . When alum sludge freezes, the ice crystals rupture the gelatinous floc structure irreversibly, and on thawing the sludge releases water readily and can reach 20 percent solids or more. Beds that operate through a Colorado winter often dewater far better than the same beds in a mild climate.
Lagoons are larger earthen basins operated on fill, settle, decant, and dry cycles. They provide storage as well as dewatering, and cleanout may be on a multi-year cycle.
Mechanical dewatering — belt filter presses, centrifuges, plate-and-frame presses, and screw presses — is used where land is unavailable. Plate-and-frame presses achieve the highest cake solids on alum sludge, often 30 to 40 percent, but they are batch machines with high labor and polymer demand.
The Filter Backwash Recycle Rule
Recycling residual liquids is attractive — it recovers water, which matters in Colorado — but it also returns concentrated pathogens and solids to the head of the plant. The federal Filter Backwash Recycle Rule (FBRR) governs the practice for systems using conventional or direct filtration, and Colorado implements it through Regulation 11.
The core requirement: spent filter backwash water, thickener supernatant, and liquids from dewatering processes must be returned to a location upstream of the primary coagulant addition point , unless the state specifically approves an alternative location. The reason is simple and is the whole point of the rule: recycled flow must pass through all the plant's treatment processes, especially coagulation and filtration, so that any Cryptosporidium oocysts concentrated in the residuals are removed rather than short-circuited into the clearwell.
Systems must also keep records of the recycle location, flow rate, and duration, and be prepared to demonstrate that the recycle does not degrade finished water quality. Operationally, the recycle stream is fed back at a controlled, steady rate — generally not more than about 10 percent of raw water flow — because slugging a plant with concentrated backwash upsets coagulation, spikes turbidity, and can drive filter breakthrough.
Disposal pathways
Discharge to a receiving stream. This is a point-source discharge and requires a CDPS permit under Regulation 61, with limits typically on total suspended solids, pH, and sometimes aluminum, iron, and manganese. Untreated basin blowdown almost never meets those limits.
Discharge to the sanitary sewer. Common and often the simplest route, but requires the receiving wastewater utility's agreement. Alum sludge can upset a wastewater plant's solids handling, and ion exchange brine can jeopardize the wastewater plant's own chloride and total dissolved solids limits.
Landfill. Dewatered cake goes to a permitted solid waste facility. The landfill will require a paint filter liquids test pass and characterization; residuals bearing radium or uranium from groundwater treatment may be classified as technologically enhanced naturally occurring radioactive material (TENORM) and require special handling.
Land application. Alum and lime residuals can be applied to agricultural land as a soil amendment. Lime residual is genuinely valuable for raising soil pH. Alum residual can bind soil phosphorus, which is beneficial where phosphorus runoff is a concern and detrimental where crops need available phosphorus. Site approval, agronomic rates, buffer distances, and metals characterization apply.
Beneficial reuse. Lime recalcining recovers quicklime at very large softening plants; calcium carbonate residual is sold as agricultural lime; some alum residuals are used in topsoil blends and turf establishment.
On-site disposal and composting. Monofills on plant property and co-composting with organics are both listed in the WPI outline as options an operator may be managing.
What the operator actually monitors
Basin blowdown frequency and duration , set so the sludge blanket never rises into the settled water and never becomes so deep that it goes septic and releases manganese and taste and odor compounds back into the water.
Thickener underflow solids and supernatant turbidity , which tell you whether polymer dose and rake speed are right.
Drying bed loading depth and turnover schedule.
Recycle flow rate as a percentage of raw water flow , and the resulting effect on settled water turbidity.
Cake solids and polymer dose where mechanical dewatering is used.
Records — quantities produced, hauled, and applied, and the analytical characterization supporting each disposal route.