Study guide

9.7 Valve Types and Duties, Air Release and Air-Vacuum Valves, Water Hammer & Surge Control

Colorado Water/Wastewater Operator Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: State Laws, Regulations & CCWP Certification

1.1 CDPHE CCWP Program & Regulatory Framework (Regulation 100 / 5 CCR 1003-2) 1.2 Facility Classification & Operator in Responsible Charge (ORC) Requirements 1.3 Certification Levels, Education, Experience & Exam Eligibility (Class D-A, Grade 1-4, Class S/T) 1.4 License Renewal, Training Units (TUs) & Mandatory Regulatory Training 1.5 Colorado Primary Drinking Water Regulations (Regulation 11) & Compliance 1.6 Colorado Discharge Permit System (Regulations 61/62), DMRs & Biosolids Reporting

2 Chapter 2: Source Water & Drinking Water Treatment Processes

2.1 Raw Water Sources, High-Altitude Characteristics & Reservoir Quality 2.2 Coagulation Chemistry, Rapid Mixing & Chemical Dosing (Alum, Ferric, Polymers) 2.3 Flocculation & Sedimentation Basin Design, Operation & Settling Zones 2.4 Granular Media Filtration, Backwash Procedures & Turbidity Standards 2.5 Advanced Treatment: Membranes, Softening, GAC/PAC Adsorption & Aeration 2.6 Groundwater Sources, Well Hydraulics, Static and Pumping Levels & Specific Capacity 2.7 Source Water Characteristics, Contaminant Categories & Watershed Protection Plans 2.8 Pretreatment: Presedimentation, Aeration, Algae Control & Taste-and-Odor Management 2.9 Direct, In-Line, Pressure, Cartridge & Diatomaceous Earth Filtration 2.10 Lime-Soda Softening, Ion Exchange & Water Stabilization 2.11 Water Treatment Plant Residuals: Lagoons, Drying Beds, Land Application & Recycle

3 Chapter 3: Disinfection & Chemical Addition

3.1 Chlorine Chemistry: Hypochlorous Acid, Free/Combined Residual & Breakpoint Chlorination 3.2 Disinfection Kinetics, Baffle Factors, T10 & CT Compliance Calculations 3.3 Disinfection Byproducts (TTHMs, HAA5s) & Stage 1/2 DBP Rules 3.4 Alternative Disinfection: Chloramination, Ultraviolet (UV) Light & Chlorine Dioxide 3.5 Corrosion Control, Lead & Copper Rule Revisions (LCRR) & Fluoridation Practices

4 Chapter 4: Water Treatment Plant Equipment, Instrumentation & Maintenance

4.1 Raw Water Intakes, Screening Equipment & Raw Water Pumping 4.2 Chemical Feed Equipment: Feeders, Day Tanks, Carrier Water & Feed-Rate Calibration 4.3 Chlorination Equipment: Gas Systems, Vacuum Regulators, Hypochlorite Storage & Onsite Generation 4.4 Filter Underdrains, Support Gravel, Surface Wash, Air Scour & Filter-to-Waste 4.5 Plant Process Control, SCADA and PLC Systems, Alarm Management & Records of Operation 4.6 Preventive, Corrective and Predictive Maintenance, Work Orders & Asset Management

5 Chapter 5: Wastewater Treatment Principles & Biological Processes

5.1 Preliminary Treatment: Bar Screens, Shredders, Grit Chambers & Flow Equalization 5.2 Primary Clarification, Solids Separation & Scum Removal Mechanics 5.3 Activated Sludge Fundamentals: Aerobic Microbiology, DO Control & Biomass Growth 5.4 Return & Waste Activated Sludge Management (RAS/WAS Operations & Sludge Age) 5.5 Activated Sludge Troubleshooting: Bulking, Nocardia Foaming, Rising Sludge & Pin Floc 5.6 Wastewater Characteristics, Organic and Hydraulic Loading, Diurnal Flow & Septicity 5.7 Activated Sludge Arrangements: Conventional, Complete Mix, Step Feed, Contact Stabilization, Extended Aeration, Oxidation Ditch, SBR & MBR 5.8 Aeration Systems: Blowers, Diffusers, Surface Aerators, Oxygen Transfer & Altitude Effects

6 Chapter 6: Advanced Wastewater Treatment & Solids Management

6.1 Biological Nutrient Removal: Nitrification, Denitrification & Anoxic Zones 6.2 Biological & Chemical Phosphorus Removal (EBPR & Coagulant Precipitation) 6.3 Sludge Thickening, Aerobic & Anaerobic Digestion (Mesophilic/Thermophilic) 6.4 Dewatering Equipment (Centrifuges, Belt Filter Presses) & Biosolids Standards (Reg 64) 6.5 Pond & Lagoon Operations, Trickling Filters & Rotating Biological Contactors (RBCs) 6.6 Secondary Clarification: Overflow and Solids Loading Rates, RAS Rate Setting & Clarifier Diagnostics 6.7 Tertiary Filtration, Effluent Polishing & Wastewater Disinfection with Chlorine, Dechlorination and UV 6.8 Effluent Disposal, Rapid Infiltration Basins, Colorado Water Reuse Law & Regulation 84

7 Chapter 7: Water Distribution Systems

7.1 Distribution Hydraulics, Pressure Zones, Static Head & Friction Headloss 7.2 Finished Water Storage Tanks, Standpipes, Mixing & Water Age Control 7.3 Distribution Piping, Valves (Gate, Butterfly, PRV), Hydrants & Main Flushing 7.4 Cross-Connection Control, Hazard Assessment & Backflow Preventers (RPZ, DCVA, PVB, Air Gap) 7.5 Water Main Installation, Trenching, Repair, Pressure Testing & Disinfection (AWWA C651) 7.6 Network Layout, Pressure Zones, Demand Patterns, Fire Flow & the Hydraulic Grade Line 7.7 Fire Hydrants, Dry Barrel Operation, Fire Flow Testing & Unidirectional Flushing 7.8 Booster Pump Stations, Hydropneumatic Systems, Controls & Surge Protection 7.9 Customer and Master Metering, Meter Sizing, Accuracy Testing, AMR & AMI 7.10 System Mapping, GIS, As-Builts, Operational Analysis & the AWWA Water Audit 7.11 Service Line Installation, Wet Tapping, Curb Stops & the Lead Service Line Inventory 7.12 Leak Detection, District Metered Areas, Minimum Night Flow & Pressure Management 7.13 Storage Facility Inspection, Sanitary Defects, Water Age Control, Cleaning & AWWA C652 Disinfection 7.14 Utility Locating, Colorado 811 Damage Prevention, the APWA Color Code & New Construction Inspection 7.15 Well and Wellhead Maintenance, Sanitary Condition, Rehabilitation & AWWA C654 Disinfection 7.16 Booster Chlorination, Remote Chemical Feed, Chemical Storage, Security & Supply Management 7.17 Distribution Sampling Technique, Chlorine Residual Monitoring & Nitrification Control in Chloraminated Systems

8 Chapter 8: Wastewater Collection Systems

8.1 Gravity Collection Systems: Flow Velocities, Slopes, Pipe Materials & Manholes 8.2 Wastewater Lift Stations: Wet Wells, Submersible Pumps, Level Controls & Force Mains 8.3 Inflow and Infiltration (I&I) Sources, Flow Monitoring, Smoke Testing & CCTV Inspection 8.4 Collection Maintenance: Hydraulic Jetting, Mechanical Rodding & FOG/Root Mitigation 8.5 Sanitary Sewer Overflows (SSOs): Root Causes, Containment, Reporting & Mitigation 8.6 Lift Station Electrical Devices, Level Detection, Telemetry, Gas Detection & Capacity Adjustment 8.7 Lift Station Configurations, Preventive Maintenance, Wet Well Cleaning, Troubleshooting & Emergency Bypass Pumping 8.8 Collection System Rehabilitation: CIPP, Pipe Bursting, Sliplining, Grouting, Manhole Repair & Tap Defects 8.9 Excavation, Hydro Excavation, Bedding and Haunching, Grade Control & Sewer Acceptance Testing 8.10 Collection System Flow Monitoring, Area-Velocity Metering, Weirs and Flumes & Capacity Assessment

9 Chapter 9: Pumps, Motors & Utility Mechanics

9.1 Centrifugal Pumps: Volutes, Impellers, Packing Seals & Mechanical Seals 9.2 Positive Displacement Pumps (Peristaltic, Diaphragm, Progressive Cavity) & Dosing Systems 9.3 Pump Performance Curves, System Head Curves, Cavitation & NPSH Calculations 9.4 Electric Motors (Single/Three Phase), Controls, Variable Frequency Drives (VFDs) & Power 9.5 Flow Meters (Venturi, Magnetic, Ultrasonic), Online Analyzers, PLCs & SCADA Telemetry 9.6 Air Compressors, Conveyors, Hoists and Cranes, Service Piping & Standby Power Generation 9.7 Valve Types and Duties, Air Release and Air-Vacuum Valves, Water Hammer & Surge Control

10 Chapter 10: Laboratory Analysis & Water Quality Monitoring

10.1 Regulatory Sampling Procedures, Chain of Custody, Holding Times & Preservation Techniques 10.2 Physical & Chemical Drinking Water Testing: Turbidity, pH, Alkalinity, Hardness & Chlorine (DPD) 10.3 Wastewater Laboratory Analysis: BOD5, COD, Total Suspended Solids (TSS) & Settleometry 10.4 Microbiological Testing: Total Coliform, E. coli (Colilert, Membrane Filtration) & QA/QC 10.5 Bench-Scale Jar Testing, Coagulant Optimization & Streaming Current Monitoring 10.6 Laboratory Equipment, Calibration and Verification, QA/QC Program & Certified Laboratory Requirements 10.7 Nutrient Series, Metals Sampling, Whole Effluent Toxicity & Electrode Measurements (DO, pH, ORP, H2S)

11 Chapter 11: Operator Mathematics & Applied Calculations

11.1 Core Conversions, Geometric Area, Pipe Volume & Continuous Flow Rate (MGD, GPM, cfs) 11.2 Chemical Dosage, The Standard "Pounds Formula", Active Chemical & Solution Purity 11.3 Hydraulic Retention Time (HRT), Surface Overflow Rate (SOR) & Weir Overflow Rates 11.4 Process Control Calculations: F/M Ratio, MCRT/Solids Retention Time (SRT) & Sludge Volume Index (SVI) 11.5 Distribution Pressure, Static vs Dynamic Head, Water Horsepower & Wire-to-Water Efficiency 11.6 CT Calculations: Baffling Factors, T10, Temperature and pH Corrections & Multi-Segment Compliance

12 Chapter 12: Safety, Emergency Operations & Compliance

12.1 Permit-Required Confined Space (PRCS) Entry, Atmospheric Testing (O2/LEL/H2S/CO) & Rescue 12.2 Control of Hazardous Energy: Lockout/Tagout (LOTO), Arc Flash & Electrical Safety 12.3 Chemical Safety: Chlorine Gas Handling, Ton Cylinders, Sulfur Dioxide, Ammonia & SDS/GHS 12.4 Trenching & Excavation: Soil Classification, Sloping, Shoring, Shielding & Competent Person Rules 12.5 Emergency Action Plans, Security Vulnerability, Spill Containment & CDPHE Tier 1/2/3 Public Notice 12.6 Work Zone Traffic Control, PPE, Fall Protection, Fire Extinguishers, First Aid & Bloodborne Pathogens 12.7 Standard Operating Procedures, Operating Records, Regulatory Reporting, Customer Complaints & Supervisory Duties

9.7 Valve Types and Duties, Air Release and Air-Vacuum Valves, Water Hammer & Surge Control

Key Takeaways Explain This Topic AI

A gate valve is an isolation device only, because holding it partly open wire-draws the seat until the valve will no longer seal.

Air release valves vent small accumulations under pressure while air-vacuum valves exhaust air during filling and admit air during draining, and most high points need a combination valve.

Air accumulating at unvented high points progressively reduces effective flow area and is a classic cause of a force main gradually losing capacity.

The Joukowsky equation gives surge head as wave speed times velocity change divided by 32.2, so a 4 ft/s change at 3,600 ft/s wave speed produces about 447 feet of head.

Check valve slam on reverse flow often produces a larger transient than the pump stop itself, which is why non-slam, spring-assisted, or dual-disc checks are used on high-head lines.

Last updated: August 2026

Valves do more than open and close

WPI lists valves (backflow, control valve, isolating, throttling, pressure regulation) among water treatment equipment, mains and related equipment including pressure regulating valves and air relief valves among distribution components, and pressure relief valves, air relief, and valves among collection lift station devices. Choosing the wrong valve for a duty, or operating the right valve badly, causes most of the surge damage in a water system.

Valve types and their proper duty

Valve Construction Correct duty Do not use for

Gate Wedge or resilient seat rising across the flow Isolation — fully open or fully closed Throttling; a partly open gate wire-draws the seat

Butterfly Disc rotating in the flow stream Isolation and coarse throttling ; low headloss when open High differential throttling; the disc obstructs the bore

Globe Plug seating against a port, flow turns twice Throttling and control Applications needing low headloss

Ball Rotating bored ball Quick isolation; some throttling with a characterized ball High-cycle throttling in dirty service

  • Plug Tapered or cylindrical plug Isolation and throttling in sludge and grit service Fine control
  • Check Opens with forward flow, closes on reverse Prevent backflow Isolation; a check valve is not a shutoff
  • Pressure reducing (PRV) Pilot-controlled diaphragm Hold a constant downstream pressure Isolation

Pressure sustaining / relief Pilot-controlled diaphragm Hold a minimum upstream pressure, or relieve surge Flow control

Altitude Pilot senses tank level Stops flow when a tank is full Throttling

Air release / air-vacuum / combination Float-operated Release accumulated air, admit air on drain Anything else

A gate valve is not a throttling valve. Partially open, the flow accelerates past the wedge edge and erodes the seat, and the valve eventually will not seal. When operators need throttling in a distribution system, the answer is a control valve, a butterfly valve within its rating, or a variable frequency drive on the pump.

Air valves, and why they matter more than they look

Three distinct devices are commonly confused:

Air release valve. Small orifice, releases small accumulations of air during normal operation while the line is pressurized. Installed at high points on force mains and transmission mains.

Air-vacuum (air and vacuum) valve. Large orifice. Exhausts large volumes of air while a line fills and admits air while a line drains , preventing vacuum collapse. Closes once liquid reaches it and cannot release air under pressure.

Combination air valve. Both functions in one body. This is what most high points actually need.

Two failure consequences appear repeatedly on exams and in real damage reports. Without air release at high points, accumulated air progressively reduces the effective flow area and a force main or transmission main gradually loses capacity — the "it used to keep up" problem. Without air-vacuum capability, draining a line pulls a vacuum that can collapse a pipe or pull the gasket out of a joint , and rapid filling compresses trapped air into a violent surge.

Air valves in wastewater service foul with grease and solids and require a routine cleaning schedule; a plugged air valve on a force main is effectively no air valve.

Water hammer

Water hammer is a pressure transient created when the velocity of a moving column of water changes suddenly. The physics is worth carrying: stopping a moving mass instantly converts its momentum into pressure. The Joukowsky equation gives the pressure rise for an instantaneous stop:

ΔH = (a x ΔV) / g

where a is the pressure wave speed (roughly 3,000 to 4,500 ft/s in typical water pipe, lower in flexible plastic), ΔV is the velocity change in ft/s, and g is 32.2 ft/s².

Worked example. A pump discharge line carries water at 5 ft/s. A valve closes rapidly and the wave speed is 3,500 ft/s.

  • ΔH = (3,500 x 5) ÷ 32.2 = 17,500 ÷ 32.2 = 543 feet of head
  • In psi: 543 ÷ 2.31 = 235 psi above the operating pressure

That is why a fast-closing valve on a 100 psi system can burst a pipe rated for 200 psi. The critical time for a pipeline is 2L/a, twice the length divided by wave speed; a closure faster than that produces the full Joukowsky rise.

Causes and controls

Cause Control

Rapid valve closure (including a slammed hydrant) Close valves slowly ; operator training is the cheapest control

Pump start against an empty or partially empty line Fill slowly; use pump control valves that open and close on a timed ramp

Power failure stopping pumps instantly Surge tanks, hydropneumatic surge vessels, surge anticipator valves , flywheels, soft-stop VFDs

Column separation at high points Combination air valves properly sized and maintained

Check valve slam on reverse flow Slow-closing, spring-assisted, or damped check valves rather than swing checks on high-head lines

Rapid demand change (fire flow start or stop) Zone design, pressure control

Check valve slam deserves its own note: when a pump stops, flow reverses before a plain swing check closes, and the disc slams onto the seat against reverse velocity. The resulting transient is often larger than the one from the pump stopping. Non-slam, spring-assisted, dual-disc, or tilting-disc checks close before appreciable reverse velocity develops.

Valve exercising and records

Every valve in a distribution or collection system should be operated on a program — commonly annually for critical valves and on a multi-year cycle for the remainder. Records capture valve ID, location, size, type, direction to open, total turns, turns to close, condition, and any leakage . Two practical points:

Record the number of turns. A valve that used to take 26 turns and now closes in 18 has a broken stem or a dropped wedge.

Return the valve to its correct position and verify it. The most common cause of a mysterious low-pressure or water-quality complaint is a valve left partly or fully closed after a repair, or a zone boundary valve left open.