Study guide

5.6 Wastewater Characteristics, Organic and Hydraulic Loading, Diurnal Flow & Septicity

Colorado Water/Wastewater Operator Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: State Laws, Regulations & CCWP Certification

1.1 CDPHE CCWP Program & Regulatory Framework (Regulation 100 / 5 CCR 1003-2) 1.2 Facility Classification & Operator in Responsible Charge (ORC) Requirements 1.3 Certification Levels, Education, Experience & Exam Eligibility (Class D-A, Grade 1-4, Class S/T) 1.4 License Renewal, Training Units (TUs) & Mandatory Regulatory Training 1.5 Colorado Primary Drinking Water Regulations (Regulation 11) & Compliance 1.6 Colorado Discharge Permit System (Regulations 61/62), DMRs & Biosolids Reporting

2 Chapter 2: Source Water & Drinking Water Treatment Processes

2.1 Raw Water Sources, High-Altitude Characteristics & Reservoir Quality 2.2 Coagulation Chemistry, Rapid Mixing & Chemical Dosing (Alum, Ferric, Polymers) 2.3 Flocculation & Sedimentation Basin Design, Operation & Settling Zones 2.4 Granular Media Filtration, Backwash Procedures & Turbidity Standards 2.5 Advanced Treatment: Membranes, Softening, GAC/PAC Adsorption & Aeration 2.6 Groundwater Sources, Well Hydraulics, Static and Pumping Levels & Specific Capacity 2.7 Source Water Characteristics, Contaminant Categories & Watershed Protection Plans 2.8 Pretreatment: Presedimentation, Aeration, Algae Control & Taste-and-Odor Management 2.9 Direct, In-Line, Pressure, Cartridge & Diatomaceous Earth Filtration 2.10 Lime-Soda Softening, Ion Exchange & Water Stabilization 2.11 Water Treatment Plant Residuals: Lagoons, Drying Beds, Land Application & Recycle

3 Chapter 3: Disinfection & Chemical Addition

3.1 Chlorine Chemistry: Hypochlorous Acid, Free/Combined Residual & Breakpoint Chlorination 3.2 Disinfection Kinetics, Baffle Factors, T10 & CT Compliance Calculations 3.3 Disinfection Byproducts (TTHMs, HAA5s) & Stage 1/2 DBP Rules 3.4 Alternative Disinfection: Chloramination, Ultraviolet (UV) Light & Chlorine Dioxide 3.5 Corrosion Control, Lead & Copper Rule Revisions (LCRR) & Fluoridation Practices

4 Chapter 4: Water Treatment Plant Equipment, Instrumentation & Maintenance

4.1 Raw Water Intakes, Screening Equipment & Raw Water Pumping 4.2 Chemical Feed Equipment: Feeders, Day Tanks, Carrier Water & Feed-Rate Calibration 4.3 Chlorination Equipment: Gas Systems, Vacuum Regulators, Hypochlorite Storage & Onsite Generation 4.4 Filter Underdrains, Support Gravel, Surface Wash, Air Scour & Filter-to-Waste 4.5 Plant Process Control, SCADA and PLC Systems, Alarm Management & Records of Operation 4.6 Preventive, Corrective and Predictive Maintenance, Work Orders & Asset Management

5 Chapter 5: Wastewater Treatment Principles & Biological Processes

5.1 Preliminary Treatment: Bar Screens, Shredders, Grit Chambers & Flow Equalization 5.2 Primary Clarification, Solids Separation & Scum Removal Mechanics 5.3 Activated Sludge Fundamentals: Aerobic Microbiology, DO Control & Biomass Growth 5.4 Return & Waste Activated Sludge Management (RAS/WAS Operations & Sludge Age) 5.5 Activated Sludge Troubleshooting: Bulking, Nocardia Foaming, Rising Sludge & Pin Floc 5.6 Wastewater Characteristics, Organic and Hydraulic Loading, Diurnal Flow & Septicity 5.7 Activated Sludge Arrangements: Conventional, Complete Mix, Step Feed, Contact Stabilization, Extended Aeration, Oxidation Ditch, SBR & MBR 5.8 Aeration Systems: Blowers, Diffusers, Surface Aerators, Oxygen Transfer & Altitude Effects

6 Chapter 6: Advanced Wastewater Treatment & Solids Management

6.1 Biological Nutrient Removal: Nitrification, Denitrification & Anoxic Zones 6.2 Biological & Chemical Phosphorus Removal (EBPR & Coagulant Precipitation) 6.3 Sludge Thickening, Aerobic & Anaerobic Digestion (Mesophilic/Thermophilic) 6.4 Dewatering Equipment (Centrifuges, Belt Filter Presses) & Biosolids Standards (Reg 64) 6.5 Pond & Lagoon Operations, Trickling Filters & Rotating Biological Contactors (RBCs) 6.6 Secondary Clarification: Overflow and Solids Loading Rates, RAS Rate Setting & Clarifier Diagnostics 6.7 Tertiary Filtration, Effluent Polishing & Wastewater Disinfection with Chlorine, Dechlorination and UV 6.8 Effluent Disposal, Rapid Infiltration Basins, Colorado Water Reuse Law & Regulation 84

7 Chapter 7: Water Distribution Systems

7.1 Distribution Hydraulics, Pressure Zones, Static Head & Friction Headloss 7.2 Finished Water Storage Tanks, Standpipes, Mixing & Water Age Control 7.3 Distribution Piping, Valves (Gate, Butterfly, PRV), Hydrants & Main Flushing 7.4 Cross-Connection Control, Hazard Assessment & Backflow Preventers (RPZ, DCVA, PVB, Air Gap) 7.5 Water Main Installation, Trenching, Repair, Pressure Testing & Disinfection (AWWA C651) 7.6 Network Layout, Pressure Zones, Demand Patterns, Fire Flow & the Hydraulic Grade Line 7.7 Fire Hydrants, Dry Barrel Operation, Fire Flow Testing & Unidirectional Flushing 7.8 Booster Pump Stations, Hydropneumatic Systems, Controls & Surge Protection 7.9 Customer and Master Metering, Meter Sizing, Accuracy Testing, AMR & AMI 7.10 System Mapping, GIS, As-Builts, Operational Analysis & the AWWA Water Audit 7.11 Service Line Installation, Wet Tapping, Curb Stops & the Lead Service Line Inventory 7.12 Leak Detection, District Metered Areas, Minimum Night Flow & Pressure Management 7.13 Storage Facility Inspection, Sanitary Defects, Water Age Control, Cleaning & AWWA C652 Disinfection 7.14 Utility Locating, Colorado 811 Damage Prevention, the APWA Color Code & New Construction Inspection 7.15 Well and Wellhead Maintenance, Sanitary Condition, Rehabilitation & AWWA C654 Disinfection 7.16 Booster Chlorination, Remote Chemical Feed, Chemical Storage, Security & Supply Management 7.17 Distribution Sampling Technique, Chlorine Residual Monitoring & Nitrification Control in Chloraminated Systems

8 Chapter 8: Wastewater Collection Systems

8.1 Gravity Collection Systems: Flow Velocities, Slopes, Pipe Materials & Manholes 8.2 Wastewater Lift Stations: Wet Wells, Submersible Pumps, Level Controls & Force Mains 8.3 Inflow and Infiltration (I&I) Sources, Flow Monitoring, Smoke Testing & CCTV Inspection 8.4 Collection Maintenance: Hydraulic Jetting, Mechanical Rodding & FOG/Root Mitigation 8.5 Sanitary Sewer Overflows (SSOs): Root Causes, Containment, Reporting & Mitigation 8.6 Lift Station Electrical Devices, Level Detection, Telemetry, Gas Detection & Capacity Adjustment 8.7 Lift Station Configurations, Preventive Maintenance, Wet Well Cleaning, Troubleshooting & Emergency Bypass Pumping 8.8 Collection System Rehabilitation: CIPP, Pipe Bursting, Sliplining, Grouting, Manhole Repair & Tap Defects 8.9 Excavation, Hydro Excavation, Bedding and Haunching, Grade Control & Sewer Acceptance Testing 8.10 Collection System Flow Monitoring, Area-Velocity Metering, Weirs and Flumes & Capacity Assessment

9 Chapter 9: Pumps, Motors & Utility Mechanics

9.1 Centrifugal Pumps: Volutes, Impellers, Packing Seals & Mechanical Seals 9.2 Positive Displacement Pumps (Peristaltic, Diaphragm, Progressive Cavity) & Dosing Systems 9.3 Pump Performance Curves, System Head Curves, Cavitation & NPSH Calculations 9.4 Electric Motors (Single/Three Phase), Controls, Variable Frequency Drives (VFDs) & Power 9.5 Flow Meters (Venturi, Magnetic, Ultrasonic), Online Analyzers, PLCs & SCADA Telemetry 9.6 Air Compressors, Conveyors, Hoists and Cranes, Service Piping & Standby Power Generation 9.7 Valve Types and Duties, Air Release and Air-Vacuum Valves, Water Hammer & Surge Control

10 Chapter 10: Laboratory Analysis & Water Quality Monitoring

10.1 Regulatory Sampling Procedures, Chain of Custody, Holding Times & Preservation Techniques 10.2 Physical & Chemical Drinking Water Testing: Turbidity, pH, Alkalinity, Hardness & Chlorine (DPD) 10.3 Wastewater Laboratory Analysis: BOD5, COD, Total Suspended Solids (TSS) & Settleometry 10.4 Microbiological Testing: Total Coliform, E. coli (Colilert, Membrane Filtration) & QA/QC 10.5 Bench-Scale Jar Testing, Coagulant Optimization & Streaming Current Monitoring 10.6 Laboratory Equipment, Calibration and Verification, QA/QC Program & Certified Laboratory Requirements 10.7 Nutrient Series, Metals Sampling, Whole Effluent Toxicity & Electrode Measurements (DO, pH, ORP, H2S)

11 Chapter 11: Operator Mathematics & Applied Calculations

11.1 Core Conversions, Geometric Area, Pipe Volume & Continuous Flow Rate (MGD, GPM, cfs) 11.2 Chemical Dosage, The Standard "Pounds Formula", Active Chemical & Solution Purity 11.3 Hydraulic Retention Time (HRT), Surface Overflow Rate (SOR) & Weir Overflow Rates 11.4 Process Control Calculations: F/M Ratio, MCRT/Solids Retention Time (SRT) & Sludge Volume Index (SVI) 11.5 Distribution Pressure, Static vs Dynamic Head, Water Horsepower & Wire-to-Water Efficiency 11.6 CT Calculations: Baffling Factors, T10, Temperature and pH Corrections & Multi-Segment Compliance

12 Chapter 12: Safety, Emergency Operations & Compliance

12.1 Permit-Required Confined Space (PRCS) Entry, Atmospheric Testing (O2/LEL/H2S/CO) & Rescue 12.2 Control of Hazardous Energy: Lockout/Tagout (LOTO), Arc Flash & Electrical Safety 12.3 Chemical Safety: Chlorine Gas Handling, Ton Cylinders, Sulfur Dioxide, Ammonia & SDS/GHS 12.4 Trenching & Excavation: Soil Classification, Sloping, Shoring, Shielding & Competent Person Rules 12.5 Emergency Action Plans, Security Vulnerability, Spill Containment & CDPHE Tier 1/2/3 Public Notice 12.6 Work Zone Traffic Control, PPE, Fall Protection, Fire Extinguishers, First Aid & Bloodborne Pathogens 12.7 Standard Operating Procedures, Operating Records, Regulatory Reporting, Customer Complaints & Supervisory Duties

5.6 Wastewater Characteristics, Organic and Hydraulic Loading, Diurnal Flow & Septicity

Key Takeaways Explain This Topic AI

Load rather than concentration governs plant capacity, and load in pounds per day equals flow in MGD times concentration in mg/L times 8.34.

COD is measured in about two hours and is always higher than BOD5; a plant-specific COD to BOD ratio of roughly 1.5 to 2.5 makes COD a practical same-day surrogate.

Falling influent concentration with rising flow is the signature of infiltration and inflow, because the mass load stays nearly constant while the water volume grows.

Volatile suspended solids are about 70 to 80 percent of total suspended solids in domestic wastewater, and a falling MLVSS to MLSS ratio indicates inert material accumulating in the inventory.

Septicity in long force mains and full-flowing sewers generates hydrogen sulfide, causing odor complaints, sulfuric acid crown corrosion, and added oxygen demand at the headworks.

Last updated: August 2026

Knowing your influent before you treat it

Every process control decision in a wastewater plant starts from the same question: how much of what is arriving, and when. WPI's Treatment Process Evaluation and Adjustment content area is 38 percent of the Wastewater Treatment Class I exam, and its calculations are all built on influent characterization.

Composition of typical domestic wastewater

Raw domestic wastewater is roughly 99.9 percent water . Everything that matters is in the remaining 0.1 percent.

  • Parameter Weak Medium Strong
  • BOD5, mg/L 110 190 350
  • COD, mg/L 250 430 800
  • Total suspended solids, mg/L 120 210 400
  • Total nitrogen as N, mg/L 20 40 70
  • Ammonia as N, mg/L 12 25 45
  • Total phosphorus as P, mg/L 4 7 12
  • Alkalinity as CaCO3, mg/L 50 100 200

A commonly used planning figure is roughly 0.17 to 0.20 pounds of BOD5 per person per day and a similar mass of suspended solids, with 60 to 100 gallons per capita per day of flow.

The oxygen demand family

BOD5 is the oxygen consumed by microorganisms degrading organic matter over five days at 20 degrees Celsius. It measures the biodegradable fraction and takes five days to report — its central operating limitation.

CBOD5 excludes nitrogenous demand by adding a nitrification inhibitor, so it isolates carbonaceous demand. Many Colorado permits are written on CBOD5 for exactly this reason.

COD oxidizes chemically with dichromate in about two hours and captures both biodegradable and non-biodegradable organics. It is always higher than BOD.

The COD to BOD ratio is a useful fingerprint. Domestic wastewater typically runs about 1.5 to 2.5 . A ratio well above 3 signals a large non-biodegradable or industrial fraction. Once the ratio is established for a specific plant, same-day COD becomes a practical surrogate for the five-day BOD result.

Total organic carbon (TOC) is faster still and correlates well once calibrated.

Solids

Total solids equals total suspended solids (TSS) plus total dissolved solids .

TSS splits into volatile suspended solids (VSS) , burned off at 550 degrees Celsius and representing the organic and biological fraction, and fixed suspended solids , the mineral ash.

Settleable solids , measured in an Imhoff cone in mL/L after one hour, indicate what primary clarification will remove.

In domestic wastewater, VSS is normally about 70 to 80 percent of TSS. In mixed liquor the MLVSS to MLSS ratio is a proxy for how much of the sludge inventory is active biomass, and it typically runs 0.70 to 0.85 — it falls when grit or industrial inerts accumulate.

Loading, and why it is not concentration

Concentration alone tells you nothing about whether the plant is overloaded. Load is what matters, and it comes from the pounds formula:

lbs/day = flow (MGD) x concentration (mg/L) x 8.34

Worked example. A plant receives 1.85 MGD with an influent BOD5 of 235 mg/L.

lbs BOD5/day = 1.85 x 235 x 8.34 = 3,626 lbs/day

If the aeration basin holds 0.60 MG at 2,400 mg/L MLVSS, the biomass inventory is 0.60 x 2,400 x 8.34 = 12,010 lbs, and the F/M ratio is 3,626 divided by 12,010 = 0.30 per day . Concentration alone could not have told you that.

Organic loading rate is expressed as pounds of BOD per day per 1,000 cubic feet of basin volume, and hydraulic loading as flow per unit area or volume. Both are compared against design values to judge whether an upset is a loading problem or a process problem.

Flow patterns and what they do to the plant

Domestic influent follows a diurnal curve : a low overnight, a sharp morning peak, a midday dip, and an evening peak. Small systems see wider swings than large ones because there is less averaging.

Peaking factors of 1.5 to 3 times average daily flow are normal, and higher in small systems.

Peak hydraulic flow washes solids out of clarifiers; peak organic load starves the aeration basin of oxygen. They do not always coincide.

Infiltration and inflow superimposes wet-weather flow that is high in volume and low in strength , so the concentration falls while the mass load may barely move. A plant that suddenly sees influent BOD drop from 220 mg/L to 90 mg/L after a storm has an I&I problem, not a customer problem.

Seasonal variation matters greatly in Colorado: ski and resort communities can see populations swing by a factor of five, and cold winter influent slows biological rates precisely when the load is highest.

Industrial contributions arrive as batches. A single food processor or brewery discharge can double the organic load for a few hours. This is why pretreatment programs and significant industrial user permits exist, and why Regulation 100 raises collection system classification when three or more significant industrial users are present.

Septicity

Wastewater held too long without oxygen goes septic . Sulfate-reducing bacteria in the slime layer of a full-flowing sewer or a long force main reduce sulfate to hydrogen sulfide . The consequences run through the whole plant:

Odor complaints at the headworks, at manholes, and at the force main discharge.

Crown corrosion in gravity sewers, where H2S is oxidized biologically to sulfuric acid on moist concrete above the water line.

Blackened, foul influent that has already consumed its own oxygen, arriving with an immediate oxygen demand.

Depressed dissolved oxygen at the head of the aeration basin and a higher air requirement.

Toxicity: hydrogen sulfide has an OSHA permissible exposure limit of 20 ppm as a ceiling and is immediately dangerous to life or health at 100 ppm.

Indicators an operator watches are influent color and odor, dissolved oxygen at the headworks, sulfide concentration, and oxidation-reduction potential.

Sampling that represents the day

A grab sample is a single sample at one instant. Required for pH, temperature, dissolved oxygen, total residual chlorine, and bacteria, all of which change or degrade quickly.

A composite sample blends aliquots over 24 hours. Flow-proportional compositing, where aliquot size or frequency tracks flow, gives the truest daily average and is what permits normally require for BOD and TSS.

Time-proportional compositing takes equal aliquots at equal intervals and is acceptable only where flow is relatively constant.

Samples must be iced to 6 degrees Celsius or below during collection and transport, and holding times observed: 48 hours for BOD, 28 days for preserved COD, 7 days for TSS.

Putting it together

Characterization drives everything downstream. Influent BOD and TSS set the F/M ratio and the sludge production rate. Influent ammonia and alkalinity set the nitrification capacity and whether supplemental alkalinity is needed. Influent phosphorus sets the chemical dose or the EBPR design. Flow variability sets the need for equalization . And the difference between influent and effluent, expressed as a percentage, is the removal efficiency the permit is written against:

Percent removal = [(influent - effluent) / influent] x 100

A plant with 235 mg/L influent BOD and 12 mg/L effluent BOD achieves (235 - 12) / 235 x 100 = 94.9 percent removal , comfortably above the 85 percent secondary treatment requirement.

Loading diagram... Influent Characterization Driving Process Control