4.2 Ampacity Sizing, Temperature Correction & Bundling Derating

Connecticut E-2 Unlimited Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Electrical Fundamentals, NEC Navigation & Connecticut Licensing

1.1 Electrical Theory, Units & Basic Formulas 1.2 NEC Layout, Article 90, Definitions & General Requirements 1.3 Connecticut Electrical Licensing, CGS Chapter 393 & DCP Regulations

2 Chapter 2: Services, Feeders & Branch Circuits

2.1 Service Conductors, Service Equipment & Disconnecting Means 2.2 Feeders, Feeder Sizing & Calculations 2.3 Branch Circuit Ratings, Receptacle Outlets & Spacing 2.4 GFCI and AFCI Protection Requirements

3 Chapter 3: Grounding and Bonding (NEC Article 250)

3.1 Grounding Electrode System & Grounding Electrode Conductors 3.2 System Grounding, Main & System Bonding Jumpers 3.3 Equipment Grounding Conductors & Enclosure/Raceway Bonding

4 Chapter 4: Conductors, Ampacity & Cables

4.1 Conductor Materials, Insulation Types & Terminal Ratings 4.2 Ampacity Sizing, Temperature Correction & Bundling Derating 4.3 Cable Assemblies: NM, NMC, MC, AC, TC & UF

5 Chapter 5: Raceways, Boxes & Conduit Fill

5.1 Conduit and Tubing Types & Installation Rules 5.2 Conduit Fill Calculations & Tables 5.3 Outlet, Device & Pull Box Sizing

6 Chapter 6: Overcurrent Protection & Tap Rules

6.1 Overcurrent Protection Devices, Fuses & Circuit Breakers 6.2 Overcurrent Protection Location & Feeder Tap Rules

7 Chapter 7: Electrical Load Calculations (Article 220)

7.1 Residential Dwelling Unit Load Calculations 7.2 Appliance, Cooking & Heating/Cooling Demands 7.3 Commercial & Multifamily Load Calculations

8 Chapter 8: Motors, Motor Circuits & Controllers (Article 430)

8.1 Motor Full-Load Current (FLC) & Conductor Sizing 8.2 Motor Overload Protection & Branch-Circuit Short-Circuit/Ground-Fault Protection 8.3 Motor Controllers, Disconnecting Means & Control Circuits

9 Chapter 9: Transformers, Power Distribution & Standby Systems

9.1 Transformer Principles, Single-Phase/Three-Phase & Sizing 9.2 Transformer Overcurrent Protection & Grounding 9.3 Generators, Transfer Switches & Standby Power

10 Chapter 10: Special Occupancies & Hazardous Locations

10.1 Hazardous (Classified) Locations 10.2 Health Care Facilities (Article 517) 10.3 Swimming Pools, Spas, Fountains & Hot Tubs (Article 680)

11 Chapter 11: Lighting, Signs & HVAC Equipment

11.1 Luminaires, Lampholders & Clothes Closet Clearances 11.2 Electric Signs & Outline Lighting (Article 600) 11.3 Air Conditioning & Refrigerating Equipment (Article 440)

12 Chapter 12: Low Voltage, Fire Alarm & Communications Systems

12.1 Class 1, Class 2, and Class 3 Remote-Control & Signaling Circuits 12.2 Fire Alarm Systems (NEC Article 760) 12.3 Communications Circuits & Optical Fiber Cables

13 Chapter 13: Solar Photovoltaics, Renewable Energy & Energy Storage

13.1 Solar Photovoltaic (PV) Systems Fundamentals & Sizing 13.2 PV Disconnects, Rapid Shutdown & Overcurrent Protection 13.3 Energy Storage Systems (ESS) & Interconnected Power Production

14 Chapter 14: Electrical Safety, High Voltage & Exam Strategy

14.1 Electrical Safety, OSHA Regulations & NFPA 70E 14.2 Medium and High Voltage Systems Over 1,000 Volts 14.3 PSI CT E-2 Exam Strategy, Codebook Navigation & Speed Tactics

4.2 Ampacity Sizing, Temperature Correction & Bundling Derating

Key Takeaways Explain This Topic AI

NEC Table 310.16 establishes baseline allowable conductor ampacities based on an ambient temperature of 30°C (86°F) and not more than three current-carrying conductors in a raceway, cable, or earth.

Branch circuit and feeder conductors must be sized to carry 125% of continuous loads (operating 3+ hours) plus 100% of non-continuous loads before applying adjustment or correction factors per NEC 215.2(A)(1) and 210.19(A)(1).

When ambient temperature deviates from 30°C (86°F), Table 310.15(B)(1) temperature correction factors must be applied; raceways installed on or above rooftops exposed to sunlight require additional ambient temperature adders per Table 310.15(B)(2).

When more than three current-carrying conductors share a common raceway or cable for more than 24 inches, ampacity adjustment factors from Table 310.15(C)(1) apply: 4–6 conductors (80%), 7–9 conductors (70%), 10–20 conductors (50%), 21–30 conductors (45%), 31–40 conductors (40%), and 41+ conductors (35%).

Conductor counting rules under NEC 310.15(E) dictate that equipment grounding conductors and neutral conductors carrying only unbalanced current in 3-wire single-phase systems do not count; however, neutrals of 3-wire circuits derived from 4-wire 3-phase wye systems and neutrals carrying non-linear harmonic loads (such as IT and LED equipment) must be counted as current-carrying.

Last updated: September 2026

4.2 Ampacity Sizing, Temperature Correction & Bundling Derating

Quick Reference:

Table 310.16 Baseline Conditions: Ambient temperature 30 °C ( 86 °F ) 30\text{°C } (86\text{°F}) 30 °C ( 86 °F ) , maximum 3 3 3 current-carrying conductors in raceway, cable, or direct burial.

Continuous Load Sizing (NEC 210.19(A) & 215.2(A)): Minimum Ampacity = ( 1.25 × I continuous ) + ( 1.00 × I non-continuous ) = (1.25 \times I_{\text{continuous}}) + (1.00 \times I_{\text{non-continuous}}) = ( 1.25 × I continuous ​ ) + ( 1.00 × I non-continuous ​ ) .

Adjusted Ampacity Formula: I adjusted = I Table 310.16 × F temp × F bundle I_{\text{adjusted}} = I_{\text{Table 310.16}} \times F_{\text{temp}} \times F_{\text{bundle}} I adjusted ​ = I Table 310.16 ​ × F temp ​ × F bundle ​

Bundling Adjustment Factors (Table 310.15(C)(1)):

  • 4 – 6 4\text{–}6 4 – 6 Conductors: 80% (0.80)
  • 7 – 9 7\text{–}9 7 – 9 Conductors: 70% (0.70)
  • 10 – 20 10\text{–}20 10 – 20 Conductors: 50% (0.50)
  • 21 – 30 21\text{–}30 21 – 30 Conductors: 45% (0.45)
  • 31 – 40 31\text{–}40 31 – 40 Conductors: 40% (0.40)
  • 41 + 41+ 41 + Conductors: 35% (0.35)

Nipple Exception (310.15(C)(1) Ex. 3): Conductor bundling derating does not apply to raceways ≤ 24 inches ( 600 mm ) \le 24\text{ inches } (600\text{ mm}) ≤ 24 inches ( 600 mm ) in length; 60% conduit fill permitted.

Conductor Counting (NEC 310.15(E)): Equipment grounding conductors never count . Neutrals carrying only unbalanced load do not count (310.15(E)(1)). Neutrals of 3-wire circuits from 4-wire 3-phase wye systems DO count (310.15(E)(2)). Neutrals carrying non-linear/harmonic loads DO count (310.15(E)(3)).

Ampacity is defined by NEC Article 100 as the maximum current, in amperes, that a conductor can carry continuously under the conditions of use without exceeding its temperature rating. Every ampere passing through an electrical conductor generates thermal energy proportional to I 2 R I^2R I 2 R . If that heat cannot escape into the surrounding environment as fast as it is produced, conductor temperature rises until the insulation melts, ignites, or degrades. Determining allowable ampacity under real-world conditions is one of the most critical and frequently tested proficiencies on the Connecticut E-2 Unlimited Journeyperson exam.

1. Baseline Allowable Ampacities: NEC Table 310.16

Historically designated as Table 310.15(B)(16) in older code cycles, NEC Table 310.16 is the primary lookup table for building wire ampacity. It lists the allowable ampacities of insulated conductors rated up to 2000 volts under specific benchmark test conditions:

Ambient air temperature of exactly 30°C (86°F) .

Not more than three current-carrying conductors in the raceway, cable assembly, or earth (direct burial).

Allowable Ampacities of Insulated Copper & Aluminum Conductors (NEC Table 310.16 Extract)

Conductor Size Copper 60°C (TW, UF) Copper 75°C (THWN, XHHW) Copper 90°C (THHN, XHHW-2) Aluminum 60°C (TW, UF) Aluminum 75°C (THWN, XHHW) Aluminum 90°C (THHN, XHHW-2)

  • 14 AWG 15 A* 20 A 25 A — — —
  • 12 AWG 20 A* 25 A 30 A 15 A* 20 A 25 A
  • 10 AWG 30 A* 35 A 40 A 25 A* 30 A 35 A
  • 8 AWG 40 A 50 A 55 A 35 A 40 A 45 A
  • 6 AWG 55 A 65 A 75 A 40 A 50 A 60 A
  • 4 AWG 70 A 85 A 95 A 55 A 65 A 75 A
  • 3 AWG 85 A 100 A 115 A 65 A 75 A 85 A
  • 2 AWG 95 A 115 A 130 A 75 A 90 A 100 A
  • 1 AWG 110 A 130 A 145 A 85 A 100 A 115 A
  • 1/0 AWG 125 A 150 A 170 A 100 A 120 A 135 A
  • 2/0 AWG 145 A 175 A 195 A 115 A 135 A 150 A
  • 3/0 AWG 165 A 200 A 225 A 130 A 155 A 175 A
  • 4/0 AWG 195 A 230 A 260 A 150 A 180 A 205 A
  • 250 kcmil 215 A 255 A 290 A 170 A 205 A 230 A
  • 350 kcmil 260 A 310 A 350 A 210 A 250 A 280 A
  • 500 kcmil 320 A 380 A 430 A 260 A 310 A 350 A
  • Small Conductor Overcurrent Protection Rules (NEC 240.4(D))

Notice the asterisks (*) on #14, #12, and #10 AWG conductors in the table above. Table 310.16 shows raw thermal ampacity (e.g., #14 THHN copper is rated 25 amperes). However, NEC 240.4(D) imposes statutory maximum overcurrent protection limits for small conductors to prevent thermal damage under short-circuit and ground-fault conditions:

  • 14 AWG Copper: Maximum overcurrent protection = 15 Amperes (raw 90°C ampacity = 25A)
  • 12 AWG Copper: Maximum overcurrent protection = 20 Amperes (raw 90°C ampacity = 30A)
  • 10 AWG Copper: Maximum overcurrent protection = 30 Amperes (raw 90°C ampacity = 40A)
  • 12 AWG Aluminum: Maximum overcurrent protection = 15 Amperes
  • 10 AWG Aluminum: Maximum overcurrent protection = 25 Amperes

Exam Key: While you cannot protect #12 AWG copper with a 30A breaker for general branch circuits, you are permitted to begin derating calculations at 30 amperes (its 90°C Table 310.16 value). If derating factors reduce the adjusted ampacity to 24 amperes, the conductor remains fully compliant for a 20A circuit breaker!

2. Step-by-Step Conductor Sizing Procedure

Every professional conductor calculation requires a systematic, three-phase engineering evaluation: PHASE 1: Continuous Load Sizing

  • [ I_min = (1.25 x I_continuous) + (1.00 x I_non-continuous) ]
  • |
  • v
  • PHASE 2: Terminal Temperature Check (NEC 110.14(C))
  • [ Verify Conductor Ampacity in 75°C Column ≥ I_min ]
  • |
  • v
  • PHASE 3: Conditions of Use Derating (NEC 310.15)
  • [ I_adjusted = Table 310.16 (90°C) x Temp_Factor x Bundle_Factor ]
  • |
  • v

FINAL VERIFICATION:

  • [ I_adjusted ≥ Actual Circuit Load (Continuous + Non-continuous) ]
  • [ Overcurrent Protection ≤ I_adjusted (or next higher standard size per 240.4(B)) ]
  • Phase 1: Accounting for Continuous Loads (NEC 210.19(A) & 215.2(A))

Continuous Load Definition (NEC Article 100): A load where the maximum current is expected to continue for 3 hours or more (commercial lighting, office computers, water heaters, HVAC compressors).

Non-Continuous Load: Loads that cycle on and off or operate for less than 3 hours (residential receptacles, garbage disposals, hand dryers).

Mandatory Rule: Conductors must have an allowable ampacity not less than 125% of the continuous load plus 100% of the non-continuous load : I minimum ampacity = ( 1.25 × I continuous ) + ( 1.00 × I non-continuous ) \mathbf{I_{\text{minimum ampacity}} = (1.25 \times I_{\text{continuous}}) + (1.00 \times I_{\text{non-continuous}})} I minimum ampacity ​ = ( 1.25 × I continuous ​ ) + ( 1.00 × I non-continuous ​ )

Phase 2: Terminal Temperature Verification (NEC 110.14(C))

Before applying any environmental derating, verify that the unadjusted conductor ampacity from the 75°C column (or 60°C column if terminals are not marked 75°C) is greater than or equal to I minimum ampacity I_{\text{minimum ampacity}} I minimum ampacity ​ . Equipment terminals are calibrated assuming conductor heat will sink into the cable; undersizing the wire at the terminal overheats breaker internal bimetallic strips, causing nuisance tripping.

Phase 3: Conditions of Use Derating

When conditions on the job site deviate from the Table 310.16 baseline ( 30 °C 30\text{°C} 30 °C , max 3 3 3 conductors), derating multipliers must be applied. The derated ampacity must be capable of carrying the actual connected load ( 1.00 × I continuous + 1.00 × I non-continuous 1.00 \times I_{\text{continuous}} + 1.00 \times I_{\text{non-continuous}} 1.00 × I continuous ​ + 1.00 × I non-continuous ​ ).

3. Ambient Temperature Correction Factors (NEC Table 310.15(B)(1) & Table 310.15(B)(2))

When conductors operate in ambient temperatures higher than 30°C (86°F)—such as unconditioned industrial attics, commercial kitchens, boiler rooms, or outdoor conduits—the temperature differential between the conductor core and the ambient air decreases. Less heat can dissipate, requiring conductor current to be throttled back.

Table 310.15(B)(1) Ambient Temperature Correction Multipliers (Based on 30°C)

Ambient Temperature (°C) Ambient Temperature (°F) 60°C Rating (TW, UF) 75°C Rating (THWN, XHHW) 90°C Rating (THHN, XHHW-2)

  • 10°C or less 50°F or less 1.29 1.20 1.15
  • 11 – 15°C 51 – 59°F 1.22 1.15 1.12
  • 16 – 20°C 60 – 68°F 1.15 1.11 1.08
  • 21 – 25°C 69 – 77°F 1.08 1.05 1.04
  • 26 – 30°C 78 – 86°F 1.00 1.00 1.00
  • 31 – 35°C 87 – 95°F 0.91 0.94 0.96
  • 36 – 40°C 96 – 104°F 0.82 0.88 0.91
  • 41 – 45°C 105 – 113°F 0.71 0.82 0.87
  • 46 – 50°C 114 – 122°F 0.58 0.75 0.82
  • 51 – 55°C 123 – 131°F 0.41 0.67 0.76
  • 56 – 60°C 132 – 140°F — 0.58 0.71
  • 61 – 70°C 141 – 158°F — 0.35 0.58
  • 71 – 80°C 159 – 176°F — — 0.41
  • Rooftop Ambient Temperature Adders (NEC Table 310.15(B)(2))

Raceways installed outdoors on or above building roofs absorb intense solar radiation. The air inside the conduit heats well above ambient weather temperatures. Under the 2020 NEC adopted in Connecticut:

Raceways less than 7/8 inch (22 mm) above the roof: Where raceways are installed in direct contact or less than 7/8 in above the roof surface, a temperature adder of 33°C (60°F) must be added to the outdoor design ambient temperature before entering Table 310.15(B)(1).

Raceways 7/8 inch (22 mm) or more above the roof: Where conduit is elevated on approved rooftop support blocks at least 7/8 in above the roof surface, no solar temperature adder is required .

4. Conductor Bundling Adjustment Factors (NEC Table 310.15(C)(1))

When multiple current-carrying conductors are routed through the same raceway or bundled in a cable for long distances, their individual thermal dissipation plumes overlap, trapping heat inside the enclosure. Table 310.15(C)(1) mandates percentage reductions based on the number of current-carrying conductors.

Table 310.15(C)(1) Adjustment Factors

Number of Current-Carrying Conductors Percent of Table 310.16 Values Decimal Multiplier ( F bundle F_{\text{bundle}} F bundle ​ )

  • 1 through 3 100% 1.00
  • 4 through 6 80% 0.80
  • 7 through 9 70% 0.70
  • 10 through 20 50% 0.50
  • 21 through 30 45% 0.45
  • 31 through 40 40% 0.40
  • 41 and above 35% 0.35
  • The 24-Inch Nipple Exception (NEC 310.15(C)(1) Exception No. 3)

Bundling derating applies only where conductors are bundled or installed in a raceway exceeding 24 inches (600 mm) in continuous length. Where conductors pass through a conduit nipple not exceeding 24 inches (600 mm) installed between panels, switchboards, or wireways:

Zero derating applies: Bundling adjustment factors from Table 310.15(C)(1) are not required .

Conduit fill relaxes: Allowable conduit fill increases from the standard 40% up to 60% (Chapter 9, Note 4 to tables).

5. Conductor Counting Rules (NEC 310.15(E))

To apply Table 310.15(C)(1), an electrician must accurately count which conductors generate heat. Miscounting conductors leads to either dangerously overheated raceways or drastically oversized, costly conduits.

Equipment Grounding Conductors (NEC 310.15(E))

Equipment grounding conductors (EGCs), bonding jumpers, and grounding electrode conductors (GECs) carry current only during momentary ground faults . Under normal operating conditions, they carry zero current. Grounding conductors are never counted as current-carrying conductors.

Neutral Conductors: Three Critical Rules (NEC 310.15(E)(1)–(3))

Whether a neutral conductor counts depends strictly on the circuit geometry and load characteristics: NEUTRAL CONDUCTOR COUNTING RULES

  • |
  • +-----------------------------------+-----------------------------------+
  • | | |
  • v v v
  • [ NEC 310.15(E)(1) ] [ NEC 310.15(E)(2) ] [ NEC 310.15(E)(3) ]
  • Single-Phase 120/240V 3-Wire from 4-Wire 3-Phase Non-Linear / Harmonic
  • Balanced/Unbalanced Wye System (208Y/120V) Loads (LEDs, Computers)
  • Neutral carries only net Neutral carries vector sum Triplen harmonics add;

unbalanced current. approximately equal to phase. Neutral carries heavy current.

==> DOES NOT COUNT ==> MUST BE COUNTED ==> MUST BE COUNTED

Unbalanced Neutral in Single-Phase Circuits (NEC 310.15(E)(1)): In a standard 120/240V single-phase 3-wire multiwire branch circuit, the neutral carries only the unbalanced current ( I N = ∣ I A − I B ∣ I_N = |I_A - I_B| I N ​ = ∣ I A ​ − I B ​ ∣ ). If Phase A carries 16A and Phase B carries 12A, the neutral carries only 4A. The heat generated across all three wires never exceeds the heat of two fully loaded conductors. Therefore, the neutral does not count . A 3-wire 120/240V circuit counts as two current-carrying conductors.

3-Wire Circuits Derived from 4-Wire, 3-Phase Wye Systems (NEC 310.15(E)(2)): When two phase legs and a neutral are tapped from a 208Y/120V or 480Y/277V 4-wire, 3-phase wye system to supply single-phase loads, the currents are 120° out of phase. The neutral current is given by: I N = I A 2 + I B 2 − ( I A I B ) I_N = \sqrt{I_A^2 + I_B^2 - (I_A I_B)} I N ​ = I A 2 ​ + I B 2 ​ − ( I A ​ I B ​ ) ​ Even if both phase legs carry balanced loads of 20A, the neutral carries approximately 20A . Because all three conductors simultaneously carry full load current, the neutral must be counted . The circuit counts as three current-carrying conductors.

Nonlinear and Harmonic Loads (NEC 310.15(E)(3)): In a 4-wire, 3-phase wye circuit supplying equipment with nonlinear switching power supplies (personal computers, data servers, LED electronic drivers, variable frequency drives), odd triplen harmonics (3rd, 9th, 15th harmonic frequencies) are zero-sequence currents that do not cancel in the neutral. Instead, they add together arithmetically in the neutral. Neutral current frequently exceeds phase conductor current ( I N > I phase I_N > I_{\text{phase}} I N ​ > I phase ​ ). Where the major portion of the load consists of nonlinear loads, the neutral must be counted . The 4-wire circuit counts as four current-carrying conductors.

6. Comprehensive Multi-Step Worked Calculation

To demonstrate the complete synthesis of conductor sizing, let us work through an advanced exam-level scenario.

The Problem Scenario

An industrial maintenance facility in Connecticut requires a new feeder installed in an unconditioned mechanical boiler room with an ambient temperature of 45°C (113°F) . The feeder consists of eight (8) #8 AWG THHN copper current-carrying conductors routed together in a continuous 60-foot run of Electrical Metallic Tubing (EMT). The feeder terminates on a distribution panelboard with terminal lugs marked 75°C .

Required: Calculate the maximum allowable adjusted ampacity of each #8 AWG conductor under these specific conditions of use, and determine the maximum standard circuit breaker rating permitted to protect these conductors.

  • Step-by-Step Calculation Procedure
  • Step 1: Establish Table 310.16 Baseline Ampacity
  • Conductor: #8 AWG Copper
  • Insulation: THHN (rated 90°C)

From NEC Table 310.16, in the Copper 90°C column: I base (90°C) = 55 Amperes \mathbf{I_{\text{base (90°C)}} = 55\text{ Amperes}} I base (90°C) ​ = 55 Amperes

  • Step 2: Determine Ambient Temperature Correction Factor ( F temp F_{\text{temp}} F temp ​ )
  • Ambient temperature in boiler room = 45°C (113°F)
  • Locate 41–45°C row in NEC Table 310.15(B)(1)
  • Look across to the 90°C rating column : F temp = 0.87 \mathbf{F_{\text{temp}} = 0.87} F temp ​ = 0.87
  • Step 3: Determine Conductor Bundling Adjustment Factor ( F bundle F_{\text{bundle}} F bundle ​ )
  • Total current-carrying conductors in EMT = 8 conductors
  • Conduit run length = 60 feet (exceeds 24 inches, so nipple exception does not apply)

Locate 7 to 9 conductors row in NEC Table 310.15(C)(1): F bundle = 70 % = 0.70 \mathbf{F_{\text{bundle}} = 70\% = 0.70} F bundle ​ = 70% = 0.70

Step 4: Calculate Adjusted Ampacity

Multiply baseline 90°C ampacity by both derating factors: I adjusted = I base (90°C) × F temp × F bundle I_{\text{adjusted}} = I_{\text{base (90°C)}} \times F_{\text{temp}} \times F_{\text{bundle}} I adjusted ​ = I base (90°C) ​ × F temp ​ × F bundle ​ I adjusted = 55 A × 0.87 × 0.70 = 55 A × 0.609 = 33.50 Amperes I_{\text{adjusted}} = 55\text{ A} \times 0.87 \times 0.70 = 55\text{ A} \times 0.609 = \mathbf{33.50\text{ Amperes}} I adjusted ​ = 55 A × 0.87 × 0.70 = 55 A × 0.609 = 33.50 Amperes

Step 5: Verify Equipment Terminal Limitation (NEC 110.14(C))

Equipment terminal lugs are rated for 75°C.

Look up #8 AWG Copper in the 75°C column of Table 310.16: I terminal max (75°C) = 50 Amperes \mathbf{I_{\text{terminal max (75°C)}} = 50\text{ Amperes}} I terminal max (75°C) ​ = 50 Amperes

Verification check: I adjusted = 33.50 A ≤ 50 A I_{\text{adjusted}} = 33.50\text{ A} \le 50\text{ A} I adjusted ​ = 33.50 A ≤ 50 A .

Because the adjusted ampacity (33.50A) is lower than the terminal limit (50A), the adjusted value of 33.50 Amperes governs the installation.

Step 6: Overcurrent Protection Selection (NEC 240.4(B))

Allowable continuous load: 33.50 A 1.25 = 26.80 Amperes \frac{33.50\text{ A}}{1.25} = 26.80\text{ Amperes} 1.25 33.50 A ​ = 26.80 Amperes .

Maximum overcurrent protective device: Under NEC 240.4(B) (the next higher standard rating rule, applicable for circuits 800A or less where conductor ampacity does not correspond to a standard fuse or breaker size), the next standard rating above 33.50A per NEC 240.6(A) is 35 Amperes (provided the circuit does not supply multi-outlet receptacles).

Loading diagram... Comprehensive Conductor Ampacity Sizing and Derating Workflow