Study guide
7.1 Residential Dwelling Unit Load Calculations
Connecticut E-2 Unlimited Journeyman Electrician Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Electrical Fundamentals, NEC Navigation & Connecticut Licensing
1.1 Electrical Theory, Units & Basic Formulas 1.2 NEC Layout, Article 90, Definitions & General Requirements 1.3 Connecticut Electrical Licensing, CGS Chapter 393 & DCP Regulations
2 Chapter 2: Services, Feeders & Branch Circuits
2.1 Service Conductors, Service Equipment & Disconnecting Means 2.2 Feeders, Feeder Sizing & Calculations 2.3 Branch Circuit Ratings, Receptacle Outlets & Spacing 2.4 GFCI and AFCI Protection Requirements
3 Chapter 3: Grounding and Bonding (NEC Article 250)
3.1 Grounding Electrode System & Grounding Electrode Conductors 3.2 System Grounding, Main & System Bonding Jumpers 3.3 Equipment Grounding Conductors & Enclosure/Raceway Bonding
4 Chapter 4: Conductors, Ampacity & Cables
4.1 Conductor Materials, Insulation Types & Terminal Ratings 4.2 Ampacity Sizing, Temperature Correction & Bundling Derating 4.3 Cable Assemblies: NM, NMC, MC, AC, TC & UF
5 Chapter 5: Raceways, Boxes & Conduit Fill
5.1 Conduit and Tubing Types & Installation Rules 5.2 Conduit Fill Calculations & Tables 5.3 Outlet, Device & Pull Box Sizing
6 Chapter 6: Overcurrent Protection & Tap Rules
6.1 Overcurrent Protection Devices, Fuses & Circuit Breakers 6.2 Overcurrent Protection Location & Feeder Tap Rules
7 Chapter 7: Electrical Load Calculations (Article 220)
7.1 Residential Dwelling Unit Load Calculations 7.2 Appliance, Cooking & Heating/Cooling Demands 7.3 Commercial & Multifamily Load Calculations
8 Chapter 8: Motors, Motor Circuits & Controllers (Article 430)
8.1 Motor Full-Load Current (FLC) & Conductor Sizing 8.2 Motor Overload Protection & Branch-Circuit Short-Circuit/Ground-Fault Protection 8.3 Motor Controllers, Disconnecting Means & Control Circuits
9 Chapter 9: Transformers, Power Distribution & Standby Systems
9.1 Transformer Principles, Single-Phase/Three-Phase & Sizing 9.2 Transformer Overcurrent Protection & Grounding 9.3 Generators, Transfer Switches & Standby Power
10 Chapter 10: Special Occupancies & Hazardous Locations
10.1 Hazardous (Classified) Locations 10.2 Health Care Facilities (Article 517) 10.3 Swimming Pools, Spas, Fountains & Hot Tubs (Article 680)
11 Chapter 11: Lighting, Signs & HVAC Equipment
11.1 Luminaires, Lampholders & Clothes Closet Clearances 11.2 Electric Signs & Outline Lighting (Article 600) 11.3 Air Conditioning & Refrigerating Equipment (Article 440)
12 Chapter 12: Low Voltage, Fire Alarm & Communications Systems
12.1 Class 1, Class 2, and Class 3 Remote-Control & Signaling Circuits 12.2 Fire Alarm Systems (NEC Article 760) 12.3 Communications Circuits & Optical Fiber Cables
13 Chapter 13: Solar Photovoltaics, Renewable Energy & Energy Storage
13.1 Solar Photovoltaic (PV) Systems Fundamentals & Sizing 13.2 PV Disconnects, Rapid Shutdown & Overcurrent Protection 13.3 Energy Storage Systems (ESS) & Interconnected Power Production
14 Chapter 14: Electrical Safety, High Voltage & Exam Strategy
14.1 Electrical Safety, OSHA Regulations & NFPA 70E 14.2 Medium and High Voltage Systems Over 1,000 Volts 14.3 PSI CT E-2 Exam Strategy, Codebook Navigation & Speed Tactics
7.1 Residential Dwelling Unit Load Calculations
Key Takeaways Explain This Topic AI
NEC Article 220 Part III governs the Standard Calculation Method, requiring a baseline general lighting unit load of 3 VA per square foot based on outside building dimensions, excluding open porches, garages, and unfinished spaces not adaptable for future use.
Every dwelling unit mandates a minimum of two 20-ampere small appliance branch circuits calculated at 1,500 VA each (3,000 VA total, NEC 220.52(A)) and at least one 20-ampere laundry branch circuit calculated at 1,500 VA (NEC 220.52(B)).
General lighting, small appliance, and laundry loads are combined before applying Table 220.42 demand factors: the first 3,000 VA is evaluated at 100%, the portion from 3,001 VA to 120,000 VA is evaluated at 35%, and any excess over 120,000 VA is evaluated at 25%.
Dwelling unit convenience receptacles in living rooms, bedrooms, and hallways are included in the 3 VA per square foot general lighting calculation per NEC 220.14(J); electricians must never add an individual 180 VA allowance for residential general-use receptacles.
The minimum number of general lighting branch circuits is derived by dividing total un-derated general lighting volt-amperes by branch circuit volt-ampere capacity (1,800 VA for 15A or 2,400 VA for 20A), rounding any fractional remainder up to the next whole integer.
Last updated: September 2026
7.1 Residential Dwelling Unit Load Calculations
Quick Reference:
Standard Method (Part III) vs. Optional Method (Part IV / 220.82): Part III applies to any dwelling regardless of size; Part IV requires a single-family dwelling or individual dwelling unit with an ampacity rating of 100A or greater.
Dwelling General Lighting Unit Load (NEC Table 220.12): 3 VA per square foot based on outside building dimensions.
Floor Area Exclusions (NEC 220.12 & 220.14(J)): Open porches, garages, and unused or unfinished spaces not adaptable for future use.
Small Appliance Branch Circuits (NEC 210.11(C)(1) & 220.52(A)): Minimum 2 circuits @ 1,500 VA each = 3,000 VA minimum.
Laundry Branch Circuit (NEC 210.11(C)(2) & 220.52(B)): Minimum 1 circuit @ 1,500 VA.
Table 220.42 Lighting & Appliance Demand Factors:
- First 3,000 VA: 100% (3,000 VA maximum)
- 3,001 to 120,000 VA: 35%
- Remainder over 120,000 VA: 25%
General Receptacles in Dwellings (NEC 220.14(J)): Included in the 3 VA/sq ft lighting allowance; do NOT add 180 VA per outlet.
Nominal Voltage Base: Residential single-phase calculations use 120/240 volts (NEC 220.5).
Every electrical contractor, master electrician, and journeyperson installing residential services in Connecticut must master the feeder and service calculation standards established in NEC Article 220 . Sizing a service entrance panel, meter socket, and service entrance conductors is not a matter of guesswork or rule of thumb—it is an exacting legal calculation mandated by the National Electrical Code to ensure conductors operate safely below insulation thermal limits while avoiding excessive voltage drop and nuisance tripping. On the Connecticut E-2 Unlimited Journeyperson licensing examination, residential load calculations represent one of the most heavily tested subject areas.
1. Statutory Framework: Article 220 Methodologies
NEC Article 220 is organized into distinct logical parts that govern branch-circuit, feeder, and service load calculations:
Part I: General (220.1–220.5): Defines calculation voltages (120V, 120/240V, 208Y/120V, 480Y/277V) and rounding rules (fractions under 0.5 amperes are dropped, 0.5A and greater round up).
Part II: Branch-Circuit Load Calculations (220.10–220.18): Establishes minimum unit loads per square foot and individual outlet minimums.
Part III: Feeder and Service Load Calculations — Standard Method (220.40–220.61): The universal baseline calculation method. It evaluates connected loads individually and applies empirical demand factors based on electrical diversity.
Part IV: Optional Feeder and Service Load Calculations (220.80–220.88): Streamlined calculation methods, primarily NEC 220.82 for single-family dwellings and NEC 220.84 for multifamily buildings.
Standard Method (Part III) vs. Optional Method (Part IV / 220.82)
Calculation Feature Standard Method (Part III) Optional Method (Part IV / 220.82)
Applicability Any residential dwelling unit, regardless of service size Single-family dwellings with ≥ 100 A \ge 100\text{A} ≥ 100 A service conductors
General Lighting & Receptacles 3 VA/sq ft (Table 220.12) 3 VA/sq ft (NEC 220.82(B)(1))
Small Appliance & Laundry Sized at 1,500 VA each; added to lighting before Table 220.42 demand Sized at 1,500 VA each; added to general loads before 40% demand
Lighting Demand Tiers First 3,000 VA @ 100%; 3,001–120,000 VA @ 35%; excess @ 25% First 10,000 VA @ 100%; remainder of all general loads @ 40%
Cooking Equipment Sized via Table 220.55 (Column C: 8 kW baseline + Note 1) Nameplate rating included in general loads at 40% (after first 10 kVA)
Clothes Dryer Table 220.54 (minimum 5,000 VA or nameplate @ 100%) Nameplate rating included in general loads at 40% (after first 10 kVA)
Fastened-in-Place Appliances 75% demand factor if 4 or more appliances (NEC 220.53) Nameplate rating included in general loads at 40% (after first 10 kVA)
Heating vs. Cooling (HVAC) Omit smaller load per NEC 220.60; calculate larger at 100% 100% of A/C vs. 100% of heat pump vs. 65% of central electric heat
Exam Strategy: The Connecticut E-2 exam tests both methods. Unless the examination question specifically states "Using the Optional Calculation Method" or references "NEC 220.82," you must use the Standard Method under Part III .
2. General Lighting Load Determinations (NEC 220.12 & 220.14(J))
Under NEC 220.12 , the general lighting load for dwelling units is calculated at 3 VA per square foot of usable living space. This unit load is an empirical metric developed by the NFPA that accounts for interior illumination throughout the home.
How Floor Area Is Measured
NEC 220.12 mandates that the floor area for each floor must be computed from the outside dimensions of the building, dwelling unit, or other areas involved . DWELLING UNIT FLOOR AREA BOUNDARIES
- +-------------------------------------------------------------------------+
- | |
- | [ HABITABLE LIVING SPACES ] |
- | - Bedrooms, Living Rooms, Kitchen, Dining Areas |
- | - Bathrooms, Hallways, Closets, Pantries |
- | - Finished Basements & Habitable Attics |
- | |
- | =======> INCLUDED AT 3 VA PER SQ FT (OUTSIDE DIMENSIONS) <======= |
- | |
- +-------------------------------------------------------------------------+
- | | |
- | [ ATTACHED GARAGE ] | [ OPEN UNENCLOSED PORCH ] |
- | - Storage, vehicle parking | - Exterior decks, unheated patios |
- | - Unfinished storage attics | - Crawl spaces |
- | | |
- | =======> EXCLUDED PER NEC 220.12 (DO NOT COUNT SQUARE FEET!) <======= |
- +-------------------------------------------------------------------------+
- Spaces Included vs. Excluded
Mandatory Inclusions: All finished, habitable living areas on all floor levels (first floor, second floor, finished attic, and finished basement).
Mandatory Exclusions (NEC 220.12):
- Open porches and exterior decks;
- Attached or detached automobile garages;
Unused or unfinished spaces not adaptable for future use (such as low-clearance crawl spaces or unfinished truss attics).
Dwelling Unit Receptacles Included (NEC 220.14(J))
In commercial buildings, every single convenience receptacle yoke is calculated separately at 180 VA per strap. However, in dwelling units, NEC 220.14(J) specifically dictates that all general-use receptacle outlets of 20 amperes or less (such as convenience outlets in living rooms, bedrooms, dens, and hallways) are considered part of the 3 VA per square foot general lighting load .
Electricians must never count general wall receptacles in a house and add 180 VA for each. Doing so is a major examination error that results in severely over-sizing service conductors.
3. Small Appliance and Laundry Branch Circuits (NEC 220.52)
In addition to general illumination, the NEC recognizes that modern households utilize portable heating and motor-driven appliances that impose heavy, localized electrical demands in kitchens and laundry areas. To prevent branch-circuit overloads, Article 210 mandates dedicated 20-ampere circuits, while Article 220 dictates their minimum volt-ampere calculations.
Small Appliance Branch Circuits (NEC 210.11(C)(1) & 220.52(A))
Circuit Requirement: A dwelling unit must have a minimum of two 20-ampere small appliance branch circuits supplying all receptacle outlets in the kitchen, pantry, breakfast room, and dining room (NEC 210.52(B)).
Calculation Value: Under NEC 220.52(A), each small appliance branch circuit must be calculated at not less than 1,500 volt-amperes .
Combined Minimum: 2 × 1 , 500 VA = 3 , 000 VA 2 \times 1,500\text{ VA} = \mathbf{3,000\text{ VA}} 2 × 1 , 500 VA = 3 , 000 VA .
Code Restrictions: These circuits are dedicated exclusively to small appliances. They are prohibited from supplying general lighting outlets, exhaust fans, garbage disposals, or dishwasher receptacles.
Laundry Branch Circuit (NEC 210.11(C)(2) & 220.52(B))
Circuit Requirement: A dwelling unit must have a minimum of at least one 20-ampere laundry branch circuit supplying receptacle outlets for laundry equipment (washing machine, iron, steamer).
Calculation Value: Under NEC 220.52(B), the laundry branch circuit load must be calculated at not less than 1,500 volt-amperes .
Code Restrictions: This circuit cannot have any outlets outside the laundry area and cannot supply lighting fixtures.
Exception: A laundry circuit is not required in dwelling units located in multifamily buildings where central laundry facilities are provided on the premises.
Consolidated Lighting & Appliance Subtotal
In the Standard Calculation Method, the general lighting load, the small appliance circuits, and the laundry circuit are summed together into a single baseline figure before applying demand factors: Baseline Subtotal = General Lighting VA + Small Appliance VA ( ≥ 3 , 000 ) + Laundry VA ( ≥ 1 , 500 ) \mathbf{\text{Baseline Subtotal} = \text{General Lighting VA} + \text{Small Appliance VA (}\ge 3,000\text{)} + \text{Laundry VA (}\ge 1,500\text{)}} Baseline Subtotal = General Lighting VA + Small Appliance VA ( ≥ 3 , 000 ) + Laundry VA ( ≥ 1 , 500 ) Minimum Allowance for Small Appliance + Laundry = 3 , 000 VA + 1 , 500 VA = 4 , 500 VA \mathbf{\text{Minimum Allowance for Small Appliance + Laundry} = 3,000\text{ VA} + 1,500\text{ VA} = 4,500\text{ VA}} Minimum Allowance for Small Appliance + Laundry = 3 , 000 VA + 1 , 500 VA = 4 , 500 VA
4. Applying Lighting & Appliance Demand Factors (NEC Table 220.42)
Because it is mathematically impossible for every light fixture, television, kitchen mixer, toaster, and clothes washer in a residence to operate simultaneously at full rated capacity, NEC Table 220.42 provides statutory demand factors to reflect actual diversity of electrical use.
NEC Table 220.42 Demand Factors for Dwelling Units
- Portion of General Lighting & Appliance Load Demand Factor (Percent) Calculation Method
- First 3,000 VA or less 100% Multiplied by 1.00 (Maximum = 3,000 VA)
- From 3,001 VA to 120,000 VA 35% Multiplied by 0.35
- Remainder over 120,000 VA 25% Multiplied by 0.25 TABLE 220.42 DEMAND TIER STRUCTURE
- 0 VA ----------------- 3,000 VA ------------------------- 120,000 VA ----------> Excess
- | TIER 1 | TIER 2 | TIER 3 |
- | 100% Rate | 35% Rate | 25% Rate |
- | (Max = 3,000 VA) | [(Subtotal - 3,000) x 0.35] | [Excess x |
- | | | 0.25] |
- Step-by-Step Demand Factor Calculation Logic
Calculate gross living area square footage from exterior dimensions.
Multiply square footage by 3 VA/sq ft to determine General Lighting Load.
Add 3,000 VA for two small appliance branch circuits (or N × 1 , 500 VA N \times 1,500\text{ VA} N × 1 , 500 VA if more than two are installed).
Add 1,500 VA for one laundry branch circuit (or N × 1 , 500 VA N \times 1,500\text{ VA} N × 1 , 500 VA if more than one is installed).
Sum the values to find the Total Connected Lighting and Appliance Load.
Subtract the first 3,000 VA and take it at 100% ( 3 , 000 × 1.00 = 3 , 000 VA 3,000 \times 1.00 = 3,000\text{ VA} 3 , 000 × 1.00 = 3 , 000 VA ).
Take the remaining portion (up to 120,000 VA) and multiply by 35% (0.35).
Add the two results together to establish the Net Calculated General Lighting and Appliance Demand Load .
5. Determining General Lighting Branch Circuit Counts
Beyond calculating total service ampacity, an electrician must determine the statutory minimum number of branch circuits required to feed the general illumination of the dwelling per NEC 210.11(A) .
Mathematical Formulation Minimum Branch Circuits = Total Un-derated General Lighting Load (VA) Circuit Voltage (120V) × Circuit Ampere Rating (15A or 20A) \mathbf{\text{Minimum Branch Circuits} = \frac{\text{Total Un-derated General Lighting Load (VA)}}{\text{Circuit Voltage (120V)} \times \text{Circuit Ampere Rating (15A or 20A)}}} Minimum Branch Circuits = Circuit Voltage (120V) × Circuit Ampere Rating (15A or 20A) Total Un-derated General Lighting Load (VA) Capacity of 15A, 120V Circuit = 15 A × 120 V = 1 , 800 VA \mathbf{\text{Capacity of 15A, 120V Circuit} = 15\text{ A} \times 120\text{ V} = 1,800\text{ VA}} Capacity of 15A, 120V Circuit = 15 A × 120 V = 1 , 800 VA Capacity of 20A, 120V Circuit = 20 A × 120 V = 2 , 400 VA \mathbf{\text{Capacity of 20A, 120V Circuit} = 20\text{ A} \times 120\text{ V} = 2,400\text{ VA}} Capacity of 20A, 120V Circuit = 20 A × 120 V = 2 , 400 VA
Mandatory Code Rule: Branch circuit quantities must always be based on the full, un-derated general lighting load (before applying Table 220.42 demand factors). If the mathematical division results in any fractional remainder, the number must always be rounded up to the next higher whole integer.
6. Complete Worked Step-by-Step Calculation: 2,400 Sq Ft Dwelling
To see the Standard Method operate in practice, let us evaluate a full real-world residential example representative of questions on the Connecticut E-2 examination.
Example Problem Statement
An electrician is calculating the baseline service requirements for a single-family dwelling. The building has outside exterior dimensions of 40 feet by 60 feet. It features an attached two-car garage measuring 20 feet by 24 feet (480 sq ft) and an unfinished, unheated attic space not adaptable for future living quarters. Assuming nominal 120/240-volt single-phase service, determine:
- The gross square footage of habitable living space;
- The general lighting load;
- The minimum number of 15-ampere general lighting branch circuits;
- The total connected general lighting, small appliance, and laundry load;
The net calculated demand load after applying NEC Table 220.42.
Step 1: Calculate Habitable Floor Area
Per NEC 220.12, only habitable living areas based on outside dimensions are included:
Habitable Living Area: 40 ft × 60 ft = 2 , 400 sq ft 40\text{ ft} \times 60\text{ ft} = \mathbf{2,400\text{ sq ft}} 40 ft × 60 ft = 2 , 400 sq ft
Attached Garage: 480 sq ft 480\text{ sq ft} 480 sq ft → \rightarrow → EXCLUDED per NEC 220.12.
Unfinished Attic: EXCLUDED per NEC 220.12.
Total Usable Floor Area: 2 , 400 sq ft \mathbf{2,400\text{ sq ft}} 2 , 400 sq ft .
Step 2: Compute General Lighting Load
Using Table 220.12 (3 VA per square foot): General Lighting Load = 2 , 400 sq ft × 3 VA/sq ft = 7 , 200 VA \text{General Lighting Load} = 2,400\text{ sq ft} \times 3\text{ VA/sq ft} = \mathbf{7,200\text{ VA}} General Lighting Load = 2 , 400 sq ft × 3 VA/sq ft = 7 , 200 VA
Step 3: Determine Minimum 15-Ampere Lighting Branch Circuits
Each 15A, 120V circuit has a volt-ampere rating of 15 A × 120 V = 1 , 800 VA 15\text{ A} \times 120\text{ V} = 1,800\text{ VA} 15 A × 120 V = 1 , 800 VA : Number of Circuits = 7 , 200 VA 1 , 800 VA = 4.0 circuits \text{Number of Circuits} = \frac{7,200\text{ VA}}{1,800\text{ VA}} = 4.0\text{ circuits} Number of Circuits = 1 , 800 VA 7 , 200 VA = 4.0 circuits
Result: Exactly 4 general lighting branch circuits (15A, 120V) are required. If the dwelling were wired with 20A lighting circuits: 7 , 200 / 2 , 400 = 3 7,200 / 2,400 = 3 7 , 200/2 , 400 = 3 circuits.
Step 4: Add Mandatory Small Appliance and Laundry Loads
Small Appliance Branch Circuits (NEC 220.52(A)): 2 circuits × 1 , 500 VA = 3 , 000 VA \times 1,500\text{ VA} = \mathbf{3,000\text{ VA}} × 1 , 500 VA = 3 , 000 VA
Laundry Branch Circuit (NEC 220.52(B)): 1 circuit × 1 , 500 VA = 1 , 500 VA \times 1,500\text{ VA} = \mathbf{1,500\text{ VA}} × 1 , 500 VA = 1 , 500 VA Total Connected Subtotal = 7 , 200 VA (Lighting) + 3 , 000 VA (Appliance) + 1 , 500 VA (Laundry) = 11 , 700 VA \text{Total Connected Subtotal} = 7,200\text{ VA (Lighting)} + 3,000\text{ VA (Appliance)} + 1,500\text{ VA (Laundry)} = \mathbf{11,700\text{ VA}} Total Connected Subtotal = 7 , 200 VA (Lighting) + 3 , 000 VA (Appliance) + 1 , 500 VA (Laundry) = 11 , 700 VA
Step 5: Apply NEC Table 220.42 Demand Factors
Now, apply the tiered demand factors to the 11,700 VA connected subtotal:
Tier 1 (First 3,000 VA @ 100%): 3 , 000 VA × 1.00 = 3 , 000 VA 3,000\text{ VA} \times 1.00 = \mathbf{3,000\text{ VA}} 3 , 000 VA × 1.00 = 3 , 000 VA
Tier 2 (Portion from 3,001 VA to 11,700 VA @ 35%): Remaining Load = 11 , 700 VA − 3 , 000 VA = 8 , 700 VA \text{Remaining Load} = 11,700\text{ VA} - 3,000\text{ VA} = 8,700\text{ VA} Remaining Load = 11 , 700 VA − 3 , 000 VA = 8 , 700 VA 8 , 700 VA × 0.35 = 3 , 045 VA 8,700\text{ VA} \times 0.35 = \mathbf{3,045\text{ VA}} 8 , 700 VA × 0.35 = 3 , 045 VA
Net Calculated Demand Load: Net Demand = 3 , 000 VA + 3 , 045 VA = 6 , 045 VA \text{Net Demand} = 3,000\text{ VA} + 3,045\text{ VA} = \mathbf{6,045\text{ VA}} Net Demand = 3 , 000 VA + 3 , 045 VA = 6 , 045 VA Net Amperage Contribution at 240V = 6 , 045 VA 240 V = 25.19 Amperes \mathbf{\text{Net Amperage Contribution at 240V} = \frac{6,045\text{ VA}}{240\text{ V}} = 25.19\text{ Amperes}} Net Amperage Contribution at 240V = 240 V 6 , 045 VA = 25.19 Amperes
Notice the immense impact of diversity: the connected load of 11,700 VA (48.75A at 240V) is safely and legally reduced to 6,045 VA (25.19A at 240V) for the service conductor calculation.
7. Common Exam Traps & Real-World Field Pitfalls
When sitting for the Connecticut licensing exam, candidates frequently stumble over several subtle provisions of Article 220 Part III:
The Garage Trap: Never include the square footage of an attached garage in the general lighting calculation, even if the garage has lighting outlets and convenience receptacles. The general lighting unit load in Table 220.12 explicitly covers dwelling living spaces.
The Convenience Receptacle Trap: Never add 180 VA for each duplex receptacle installed in living rooms, bedrooms, or hallways. In residential occupancies, all general-use receptacles are legally included in the 3 VA/sq ft calculation per NEC 220.14(J).
The Blanket 35% Trap: Do not calculate 11 , 700 × 0.35 = 4 , 095 VA 11,700 \times 0.35 = 4,095\text{ VA} 11 , 700 × 0.35 = 4 , 095 VA . You must always evaluate the first 3,000 VA at 100% before taking 35% of the remainder.
The Small Appliance Circuit Count Trap: If an architect specifies four small appliance circuits on the kitchen plans instead of the code-minimum two, the calculation must reflect all four: 4 × 1 , 500 VA = 6 , 000 VA 4 \times 1,500\text{ VA} = 6,000\text{ VA} 4 × 1 , 500 VA = 6 , 000 VA . The Code sets minimums, not maximums.
Branch Circuit vs. Service Demand: Never apply Table 220.42 demand factors when determining the number of branch circuits required! Branch circuits must be sized for 100% of the calculated un-derated load.