5.2 Type I Recovery Requirements

EPA Section 608 Universal Refrigerant Certification Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 EPA 608 Universal Exam Facts 1.2 How the Universal Exam Works & How to Study 1.3 Title VI, the Clean Air Act & Why Certification Exists

2 Core: Ozone Science & Regulatory Foundations

2.1 Stratospheric Ozone Depletion & Refrigerant Chemistry 2.2 The Clean Air Act, Montreal Protocol & Venting Prohibition 2.3 Section 608 Regulatory Framework 2.4 Substitute Refrigerants, Blends & Lubricant Compatibility

3 Core: Recovery, Reclamation & Recordkeeping

3.1 The Three R's & Recovery Technique Fundamentals 3.2 Recovery Equipment Certification & the Sales Restriction 3.3 Recordkeeping & Leak Repair Requirements 3.4 Refrigeration Cycle, Gauges & Evacuation Fundamentals

4 Core: Safety, Cylinders & Leak Detection

4.1 Refrigerant Exposure Hazards & PPE 4.2 Recovery Cylinders, Fill Limits & Shipping 4.3 Leak Detection Methods & Nitrogen Use

5 Type I: Small Appliances

5.1 Small Appliance Classification & the 1993 Dividing Line 5.2 Type I Recovery Requirements 5.3 Recovery Techniques, Access Valves & Passive Devices 5.4 Refrigerant Identification, Leak Detection & Safety

6 Type II: Classification, Evacuation & Recovery

6.1 High-Pressure & Very-High-Pressure Classification 6.2 Type II Evacuation Requirements by Charge Size 6.3 Type II Recovery Techniques & Efficiency

7 Type II: Leak Management & Safety

7.1 Leak-Rate Thresholds & Repair Duty 7.2 Type II Leak Detection Methods & Test Pressure 7.3 Type II Safety Requirements

8 Type III: Classification, Evacuation & Recovery

8.1 Low-Pressure Classification & Purge Units 8.2 Type III Evacuation Requirements 8.3 Type III Recovery Techniques

9 Type III: Recharging, Leak Testing & Safety

9.1 Type III Recharging Techniques 9.2 Leak Testing, Pressurization & Purge Operation 9.3 Type III Safety Requirements

10 Exam Strategy & Final Review

10.1 Cross-Section Comparison & Common Traps 10.2 Test-Day Logistics & Retake Policy 10.3 Final Review Checklist & Study Plan

5.2 Type I Recovery Requirements

Key Takeaways Explain This Topic AI

With recovery equipment manufactured on or after November 15, 1993, a small appliance must have 90% of its refrigerant recovered if the compressor is operating, or 80% if it is not, or be evacuated to 4 inches of Hg vacuum.

System-dependent (passive) recovery relies on the appliance's compressor or internal pressure; when the compressor works, it must be run during recovery.

With an inoperative compressor, passive recovery still works with help — access valves on both the high and low sides, heating and sharply striking the compressor, or a vacuum pump with a non-pressurized recovery container — and self-contained equipment is another option.

Recovery equipment manufactured before November 15, 1993 must recover 80% whether or not the compressor works, or reach 4 in. Hg.

Compressor condition drives two decisions at once: the required recovery percentage and the recovery technique.

Last updated: October 2026

Type I Recovery Requirements

Once a technician has classified an appliance as a Type I small appliance and checked whether the recovery equipment was made before or on/after November 15, 1993 , the next question is: how much refrigerant must actually be recovered before the sealed system can be opened, disposed of, or sent for disposal? EPA Section 608 answers that question with a standard built around one variable — whether the compressor is operating or not .

The 90% / 80% / 4-in.-Hg Standard

When the recovery equipment was manufactured on or after November 15, 1993, a technician must do ONE of the following before the appliance can be serviced further or discarded:

  • Compressor condition Minimum requirement
  • Operating (functional) Recover 90% of the refrigerant charge
  • Not operating (inoperative) Recover 80% of the refrigerant charge
  • Either condition (alternative method) Evacuate the system to 4 inches of mercury (in. Hg) vacuum

The distinction between an operating and a non-operating compressor exists because compressor condition directly affects how completely refrigerant can be pulled from the sealed system. A functioning compressor can help move refrigerant toward a recovery device, supporting a higher 90% target. Once the compressor stops functioning, recovery becomes fully dependent on external equipment (passive migration or a self-contained pump), which is why the rule accepts a somewhat lower 80% target — or the 4 in. Hg vacuum alternative — for that scenario.

Notice that the standard gives a technician two ways to satisfy the requirement: hit the applicable percentage using an appropriate recovery method, or pull the system down to 4 in. Hg vacuum, whichever is achievable and verifiable with the equipment on hand. The 4 in. Hg vacuum alternative exists because, on some small appliances, verifying an exact recovered percentage is harder than simply confirming the vacuum level on a gauge.

Recovery equipment manufactured before November 15, 1993 must recover 80% of the refrigerant whether or not the compressor works, or reach 4 in. Hg — so check the recovery machine's date, not the appliance's.

What "Operative" Actually Means

An operative compressor is one that runs and is capable of pumping refrigerant through the system — it does not have to be running perfectly or efficiently, only capable of moving refrigerant. A compressor that hums but is mechanically seized, or one that has no electrical continuity and will not start at all, is inoperative for the purposes of this rule. A technician who is unsure whether a compressor qualifies as operative should attempt to start it under normal conditions before deciding which recovery percentage applies and which category of recovery equipment can legally be used. Guessing in either direction carries real consequences: assuming a marginal compressor is operative when it truly is not can leave refrigerant trapped in the oil if the technician skips the access-valve, heat-and-strike, or vacuum-pump steps, while assuming an operative compressor is inoperative can lead to needlessly settling for the lower 80% recovery figure when 90% was achievable and required.

Confirming Recovery in the Field

In practice, technicians confirm they have met the recovery standard in one of two ways: by tracking the weight of refrigerant pulled into the recovery cylinder against the appliance's nameplate charge (to estimate the recovered percentage), or by watching the system gauge fall to the 4 in. Hg vacuum alternative and holding there once the recovery machine is isolated. Whichever method is used, the goal is the same — leave as little refrigerant as legally and practically possible inside the sealed system before it is opened, repaired, or scrapped.

Type I Minimum Recovery Efficiency by Compressor Condition (Recovery Equipment Made On or After Nov 15, 1993, %)