Study guide
13.3 Magnetic Fields, Induction, Transformers, and Motor Efficiency
FE Other Disciplines Fundamentals of Engineering
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Strategy
About the FE Other Disciplines Exam How to Use This Study Guide
2 Chapter 1: Mathematics
1.1 Analytic Geometry, Trigonometry, and Vector Operations 1.2 Differential and Integral Calculus 1.3 Ordinary Differential Equations and Laplace Transforms 1.4 Linear Algebra, Matrices, and Systems of Equations 1.5 Numerical Methods, Root-Finding, and Numerical Integration
3 Chapter 2: Probability and Statistics
2.1 Probability Distributions, PMFs, and PDFs 2.2 Expected Value, Mean, Variance, and Descriptive Statistics 2.3 Estimation, Confidence Intervals, and Sample Sizes 2.4 Hypothesis Testing, Goodness of Fit, and Linear Regression
4 Chapter 3: Chemistry
3.1 Stoichiometry, Chemical Reactions, and Solutions 3.2 Chemical Equilibrium, Acids/Bases, and Ideal Gas Laws 3.3 Oxidation-Reduction, Electrochemistry, and Corrosion Basics
5 Chapter 4: Instrumentation and Controls
4.1 Sensors, Transducers, and Signal Conditioning 4.2 Data Sampling, Accuracy/Precision, and A/D Conversion 4.3 Logic Diagrams, Boolean Algebra, and Control Logic
6 Chapter 5: Engineering Ethics and Societal Impacts
5.1 NCEES Model Rules of Professional Conduct and Codes of Ethics 5.2 Public Protection, Licensure Boards, and Professional Liability 5.3 Societal Impacts: Sustainability, Life-Cycle Analysis, and Public Safety
7 Chapter 6: Safety, Health, and Environment
6.1 OSHA Regulations, Industrial Hygiene, and PPE 6.2 Hazard Assessment, Risk Management, and Environmental Rules 6.3 Gas Detection and Monitoring 6.4 Electrical Safety 6.5 Confined Space Entry and Ventilation Rates
8 Chapter 7: Engineering Economics
7.1 Time Value of Money, Interest Formulas, and Cash Flow Diagrams 7.2 Capital Budgeting: Present Worth, Annual Worth, IRR, and B/C Ratio 7.3 Depreciation Methods, Income Taxes, and Breakeven Analysis 7.4 Cost Analysis, Uncertainty, Expected Value, and Decision Trees
9 Chapter 8: Statics
8.1 Statics Equilibrium, Free-Body Diagrams, and Force Systems 8.2 Distributed Loads, Resultants, and Equivalent Force-Couple Systems 8.3 Internal Forces in Rigid Bodies: Trusses, Frames, Machines, and Friction 8.4 Three-Dimensional Equilibrium, Cables, and Pulley Systems 8.5 Area Properties: Centroids, Moments of Inertia, and Radius of Gyration 8.6 Weight, Mass, and Force Units: slug, lbm, lbf, and g_c
10 Chapter 9: Dynamics
9.1 Kinematics of Particles and Rigid Bodies 9.2 Newton's Second Law for Particles and Rigid Bodies 9.3 Angular Motion, Torque, and Mass Moment of Inertia 9.4 Work-Energy Principle, Power, and Efficiency 9.5 Impulse-Momentum, Impact, and Coefficient of Restitution 9.6 Dynamic Friction and Vibrations: Natural Frequency and Damping
11 Chapter 10: Strength of Materials
10.1 Stress Types, Axial Stress-Strain, and Thermal Deformation 10.2 Torsion of Circular Shafts, Polar Moment, and Angle of Twist 10.3 Shear and Moment Diagrams 10.4 Flexural Bending Stress and Transverse Shear Stress 10.5 Stress Transformations, Principal Stresses, and Mohr's Circle 10.6 Beam Deflections and Combined Axial/Bending Loading 10.7 Column Buckling (Euler Formula) and Yield/Failure Criteria
12 Chapter 11: Materials
11.1 Crystal Structure, Phase Diagrams, and Material Processing 11.2 Mechanical Properties, Fatigue, Fracture, and Corrosion 11.3 Thermal Properties of Materials 11.4 Electrical and Chemical Properties of Materials 11.5 Material Selection for Engineering Design
13 Chapter 12: Fluid Mechanics
12.1 Fluid Properties, Hydrostatic Pressure, and Manometry 12.2 Dimensionless Numbers and Flow Regimes 12.3 Continuity Equation, Bernoulli Equation, and Energy Equation 12.4 Impulse-Momentum Equation and Forces on Control Volumes 12.5 Flow in Pipes, Friction Factors (Moody Diagram), and Head Losses 12.6 Turbomachinery: Pumps, Turbines, Fans, and Compressors 12.7 Open-Channel Flow, Manning's Equation, and Drag 12.8 Fluid Transport Systems and Flow Measurement 12.9 Ideal Gas Law, Gas Mixtures, and the Real Gas Law
14 Chapter 13: Basic Electrical Engineering
13.1 Electrical Fundamentals, Ohm's Law, and DC Circuits 13.2 AC Circuits, Phasors, Impedance, and Three-Phase Power 13.3 Magnetic Fields, Induction, Transformers, and Motor Efficiency 13.4 Electrical Measuring Devices: Voltmeter, Ammeter, and Wattmeter
15 Chapter 14: Thermodynamics and Heat Transfer
14.1 First & Second Laws of Thermodynamics and Pure Substance Properties 14.2 Thermodynamic Processes and Property Diagrams (T-s, P-h, P-v) 14.3 Heat Transfer: Conduction, Convection, and Radiation 14.4 Ideal Gas Processes and Power/Refrigeration Cycles 14.5 Mass and Energy Balances on Control Volumes 14.6 Combustion and Combustion Products 14.7 Psychrometrics: Relative Humidity, Wet-Bulb Temperature, and the Psychrometric Chart
13.3 Magnetic Fields, Induction, Transformers, and Motor Efficiency
Key Takeaways Explain This Topic AI
Ampere's Law (oint B dot dl = mu_0 I_enc) and the Biot-Savart Law relate electric currents to magnetic flux density B, governing fields in solenoids (B = mu_0 n I) and long conductors.
Faraday's Law of Electromagnetic Induction dictates that a time-varying magnetic flux produces an induced electromotive force e = -N (dPhi/dt), where Lenz's Law dictates that induced current opposes the changing flux.
Ideal transformers transform AC voltages and currents according to turns ratio a = N_1 / N_2, preserving apparent power (V_1 / V_2 = N_1 / N_2 = I_2 / I_1 = a).
Impedance transformation across an ideal transformer scales load impedance by the square of the turns ratio: Z_1 = a^2 Z_2 = (N_1 / N_2)^2 Z_2.
Real transformers experience core iron losses (hysteresis and eddy currents) and winding copper losses (I^2 R), with operating efficiency given by eta = P_out / (P_out + P_core + P_copper).
Last updated: August 2026
13.3 Magnetic Fields, Induction, Transformers, and Motor Efficiency
Core FE Exam Principle: Time-varying magnetic fields induce electric fields (Faraday's Law), forming the operational basis for electrical inductors, generators, and transformers. Ideal transformers transform AC voltage linearly while transforming impedance quadratically by a 2 = ( N 1 / N 2 ) 2 a^2 = (N_1/N_2)^2 a 2 = ( N 1 / N 2 ) 2 .
Magnetic Fields, Biot-Savart Law, and Ampere's Law
Magnetic fields are created by moving electric charges or current-carrying conductors. The magnetic field is characterized by:
Magnetic Flux Density ( B \mathbf{B} B ): Vector field measured in Teslas (T) or Weber/ m 2 \text{m}^2 m 2 ( Wb/m 2 \text{Wb/m}^2 Wb/m 2 ).
Magnetic Field Strength ( H \mathbf{H} H ): Measured in Amperes per meter (A/m).
Constitutive Relation: B = μ H = μ 0 μ r H \mathbf{B} = \mu \mathbf{H} = \mu_0 \mu_r \mathbf{H} B = μ H = μ 0 μ r H where μ 0 = 4 π × 10 − 7 H/m \mu_0 = 4\pi \times 10^{-7} \\ \text{H/m} μ 0 = 4 π × 1 0 − 7 H/m is the magnetic permeability of free space and μ r \mu_r μ r is relative permeability.
Biot-Savart Law
The Biot-Savart Law computes the differential magnetic flux density d B d\mathbf{B} d B generated by a current element I d l I d\mathbf{l} I d l at distance (r): d B = μ 0 I 4 π d l × r ^ r 2 d\mathbf{B} = \frac{\mu_0 I}{4\pi} \frac{d\mathbf{l} \times \hat{\mathbf{r}}}{r^2} d B = 4 π μ 0 I r 2 d l × r ^
For a long, straight, infinitely extended conductor carrying current (I), the magnetic flux density at radial distance (r) simplifies to: B = μ 0 I 2 π r B = \frac{\mu_0 I}{2\pi r} B = 2 π r μ 0 I
Ampere's Circuital Law
Ampere's Law states that the line integral of magnetic field density B \mathbf{B} B around any closed path equals μ 0 \mu_0 μ 0 times the total enclosed current I enc I_{\text{enc}} I enc : ∮ B ⋅ d l = μ 0 I enc \oint \mathbf{B} \cdot d\mathbf{l} = \mu_0 I_{\text{enc}} ∮ B ⋅ d l = μ 0 I enc
Long Air-Core Solenoid: For a solenoid with (N) turns over length (L) (turn density (n = N/L)): B = μ 0 n I = μ 0 ( N L ) I B = \mu_0 n I = \mu_0 \left(\frac{N}{L}\right) I B = μ 0 n I = μ 0 ( L N ) I
Toroid: For a toroidal coil of mean radius (r): B = μ 0 N I 2 π r B = \frac{\mu_0 N I}{2\pi r} B = 2 π r μ 0 N I
Magnetic Forces on Charges and Conductors
Lorentz Force on Moving Charge: F = q ( E + v × B ) \mathbf{F} = q \left( \mathbf{E} + \mathbf{v} \times \mathbf{B} \right) F = q ( E + v × B )
Force on Current-Carrying Wire: F = I ( L × B ) ⟹ F = I L B sin θ \mathbf{F} = I \left( \mathbf{L} \times \mathbf{B} \right) \implies F = I L B \sin\theta F = I ( L × B ) ⟹ F = I L B sin θ
- Electromagnetic Induction, Faraday's Law, and Lenz's Law
- Magnetic Flux ( Φ \Phi Φ )
Magnetic flux Φ \Phi Φ measures the total magnetic field passing normally through a surface area (A): Φ = ∬ B ⋅ d A = B A cos θ [ Webers, Wb = T ⋅ m 2 ] \Phi = \iint \mathbf{B} \cdot d\mathbf{A} = B A \cos\theta \quad [\text{Webers, Wb} = \text{T}\cdot\text{m}^2] Φ = ∬ B ⋅ d A = B A cos θ [ Webers, Wb = T ⋅ m 2 ]
Faraday's Law of Induction
Faraday's Law states that any change in magnetic flux linkage through a conducting loop induces an electromotive force (EMF, (e)) proportional to the time rate of flux change: ≠ = − N d Φ d t [ Volts, V ] \ne = -N \frac{d\Phi}{dt} \quad [\text{Volts, V}] = = − N d t d Φ [ Volts, V ]
where (N) is the number of turns in the coil. The negative sign represents Lenz's Law .
Lenz's Law: The direction of an induced voltage or current always creates a magnetic field that opposes the original change in magnetic flux that produced it.
Motional EMF
When a straight conductor of length (L) moves at velocity (v) perpendicular to a uniform magnetic field (B), an EMF is induced across its terminals: ≠ = B L v sin θ [ Volts, V ] \ne = B L v \sin\theta \quad [\text{Volts, V}] = = B Lv sin θ [ Volts, V ]
Ideal Transformers and Impedance Transformation
An ideal transformer consists of two high-permeability coupled windings around a common magnetic core, assuming zero winding resistance, zero core losses ( P core = 0 P_{\text{core}} = 0 P core = 0 ), and zero magnetic flux leakage. Ideal Transformer Schematic
- N1 : N2 (Turns Ratio a = N1/N2)
- +-------+ || +-------+
- | )| || |( |
- + I1 | Primary) || |(Secondary I2 +
- V1 ---> | Coil )| || |( Coil <--- V2 Load Z_L
- | )| || |( | -
- +-------+ || +-------+
- Primary-to-Secondary Transformation Equations
Let N 1 N_1 N 1 be primary turns, N 2 N_2 N 2 secondary turns, and a = N 1 N 2 a = \frac{N_1}{N_2} a = N 2 N 1 the turns ratio.
Voltage Transformation Ratio: V 1 V 2 = N 1 N 2 = a ⟹ V 1 = a V 2 \frac{V_1}{V_2} = \frac{N_1}{N_2} = a \implies V_1 = a V_2 V 2 V 1 = N 2 N 1 = a ⟹ V 1 = a V 2
Current Transformation Ratio: I 1 I 2 = N 2 N 1 = 1 a ⟹ I 1 = I 2 a \frac{I_1}{I_2} = \frac{N_2}{N_1} = \frac{1}{a} \implies I_1 = \frac{I_2}{a} I 2 I 1 = N 1 N 2 = a 1 ⟹ I 1 = a I 2
Apparent Power Conservation: S 1 = V 1 I 1 = ( a V 2 ) ( I 2 a ) = V 2 I 2 = S 2 S_1 = V_1 I_1 = (a V_2) \left(\frac{I_2}{a}\right) = V_2 I_2 = S_2 S 1 = V 1 I 1 = ( a V 2 ) ( a I 2 ) = V 2 I 2 = S 2
Impedance Transformation (Reflected Load Impedance)
When a load impedance Z L = Z 2 \mathbf{Z}_L = \mathbf{Z}_2 Z L = Z 2 is connected across the secondary terminals, the equivalent impedance Z 1 ′ \mathbf{Z}_1' Z 1 ′ reflected to (seen from) the primary side is: Z 1 ′ = V 1 I 1 = a V 2 ( I 2 a ) = a 2 ( V 2 I 2 ) = a 2 Z 2 = ( N 1 N 2 ) 2 Z L \mathbf{Z}_1' = \frac{\mathbf{V}_1}{\mathbf{I}_1} = \frac{a \mathbf{V}_2}{\left(\frac{\mathbf{I}_2}{a}\right)} = a^2 \left(\frac{\mathbf{V}_2}{\mathbf{I}_2}\right) = a^2 \mathbf{Z}_2 = \left(\frac{N_1}{N_2}\right)^2 \mathbf{Z}_L Z 1 ′ = I 1 V 1 = ( a I 2 ) a V 2 = a 2 ( I 2 V 2 ) = a 2 Z 2 = ( N 2 N 1 ) 2 Z L
Exam Tip: Impedance transforms with the square of the turns ratio a 2 a^2 a 2 . Stepping up voltage ((a < 1)) decreases reflected impedance, while stepping down voltage ((a > 1)) increases reflected impedance.
Practical Transformer Characteristics and Efficiency
Real transformers deviate from ideal behavior due to physical loss mechanisms:
Winding Copper Losses ( P copper P_{\text{copper}} P copper ): I 2 R I^2 R I 2 R heating losses in primary and secondary conductor windings: P copper = I 1 2 R 1 + I 2 2 R 2 P_{\text{copper}} = I_1^2 R_1 + I_2^2 R_2 P copper = I 1 2 R 1 + I 2 2 R 2
Core Iron Losses ( P core P_{\text{core}} P core ):
Hysteresis Loss: Energy required to continually reorient magnetic domains in the AC iron core.
Eddy Current Loss: Circular induced currents in the conductive core (mitigated by thin laminated steel sheets).
Transformer Efficiency ( η \eta η ): η = P out P in × 100 % = P out P out + P core + P copper × 100 % \eta = \frac{P_{\text{out}}}{P_{\text{in}}} \times 100\% = \frac{P_{\text{out}}}{P_{\text{out}} + P_{\text{core}} + P_{\text{copper}}} \times 100\% η = P in P out × 100% = P out + P core + P copper P out × 100% where P out = V 2 I 2 cos θ L P_{\text{out}} = V_2 I_2 \cos\theta_L P out = V 2 I 2 cos θ L .
- Comprehensive Worked Engineering Example
- Problem Statement
A step-down distribution transformer supplies power to an industrial manufacturing load. The transformer details and load parameters are:
Primary winding turns N 1 = 2400 N_1 = 2400 N 1 = 2400 , secondary turns N 2 = 120 N_2 = 120 N 2 = 120 .
Primary supply voltage V 1 = 4800 V V_1 = 4800 \text{ V} V 1 = 4800 V (RMS, 60 Hz).
Secondary load impedance Z L = 4.0 + j 3.0 Ω \mathbf{Z}_L = 4.0 + j 3.0 \\ \Omega Z L = 4.0 + j 3.0 Ω .
Transformer internal losses: Constant core loss P core = 150 W P_{\text{core}} = 150 \text{ W} P core = 150 W , primary winding resistance R 1 = 2.50 Ω R_1 = 2.50 \\ \Omega R 1 = 2.50 Ω , and secondary winding resistance R 2 = 0.0060 Ω R_2 = 0.0060 \\ \Omega R 2 = 0.0060 Ω .
Calculate:
The turns ratio (a), secondary voltage V 2 V_2 V 2 , secondary current magnitude I 2 I_2 I 2 , and primary current magnitude I 1 I_1 I 1 .
The equivalent load impedance Z 1 ′ \mathbf{Z}_1' Z 1 ′ reflected to the primary side.
The active output power P out P_{\text{out}} P out , total copper loss P copper P_{\text{copper}} P copper , total losses P loss P_{\text{loss}} P loss , and overall operating efficiency η \eta η .
- Step-by-Step Solution
- Step 1: Compute Turns Ratio, Voltages, and Currents
Turns ratio (a): a = N 1 N 2 = 2400 120 = 20.0 a = \frac{N_1}{N_2} = \frac{2400}{120} = 20.0 a = N 2 N 1 = 120 2400 = 20.0
Secondary terminal voltage V 2 V_2 V 2 : V 2 = V 1 a = 4800 V 20.0 = 240.0 V V_2 = \frac{V_1}{a} = \frac{4800 \text{ V}}{20.0} = 240.0 \text{ V} V 2 = a V 1 = 20.0 4800 V = 240.0 V
Magnitude of secondary load impedance ∣ Z L ∣ |\mathbf{Z}_L| ∣ Z L ∣ : ∣ Z L ∣ = 4.0 2 + 3.0 2 = 16.0 + 9.0 = 5.00 Ω |\mathbf{Z}_L| = \sqrt{4.0^2 + 3.0^2} = \sqrt{16.0 + 9.0} = 5.00 \\ \Omega ∣ Z L ∣ = 4. 0 2 + 3. 0 2 = 16.0 + 9.0 = 5.00 Ω
Secondary load power factor angle: θ L = arctan ( 3.0 / 4.0 ) = 36.87 ∘ \theta_L = \arctan(3.0 / 4.0) = 36.87^\circ θ L = arctan ( 3.0/4.0 ) = 36.8 7 ∘ , p f L = cos ( 36.87 ∘ ) = 0.800 lagging pf_L = \cos(36.87^\circ) = 0.800 \text{ lagging} p f L = cos ( 36.8 7 ∘ ) = 0.800 lagging .
Secondary current magnitude I 2 I_2 I 2 : I 2 = V 2 ∣ Z L ∣ = 240.0 V 5.00 Ω = 48.00 A I_2 = \frac{V_2}{|\mathbf{Z}_L|} = \frac{240.0 \text{ V}}{5.00 \\ \Omega} = 48.00 \text{ A} I 2 = ∣ Z L ∣ V 2 = 5.00 Ω 240.0 V = 48.00 A
Primary current magnitude I 1 I_1 I 1 : I 1 = I 2 a = 48.00 A 20.0 = 2.400 A I_1 = \frac{I_2}{a} = \frac{48.00 \text{ A}}{20.0} = 2.400 \text{ A} I 1 = a I 2 = 20.0 48.00 A = 2.400 A
Step 2: Compute Reflected Load Impedance on Primary Side
Using the impedance scaling law Z 1 ′ = a 2 Z L \mathbf{Z}_1' = a^2 \mathbf{Z}_L Z 1 ′ = a 2 Z L : Z 1 ′ = ( 20.0 ) 2 × ( 4.0 + j 3.0 Ω ) = 400 × ( 4.0 + j 3.0 ) = 1600 + j 1200 Ω \mathbf{Z}_1' = (20.0)^2 \times (4.0 + j 3.0 \\ \Omega) = 400 \times (4.0 + j 3.0) = 1600 + j 1200 \\ \Omega Z 1 ′ = ( 20.0 ) 2 × ( 4.0 + j 3.0 Ω ) = 400 × ( 4.0 + j 3.0 ) = 1600 + j 1200 Ω
Reflected impedance magnitude: ∣ Z 1 ′ ∣ = 400 × 5.00 = 2000 Ω |\mathbf{Z}_1'| = 400 \times 5.00 = 2000 \\ \Omega ∣ Z 1 ′ ∣ = 400 × 5.00 = 2000 Ω .
Step 3: Compute Output Power, Losses, and Efficiency
Active output power P out P_{\text{out}} P out : P out = V 2 I 2 cos θ L = 240.0 V × 48.00 A × 0.800 = 9216.0 W = 9.216 kW P_{\text{out}} = V_2 I_2 \cos\theta_L = 240.0 \text{ V} \times 48.00 \text{ A} \times 0.800 = 9216.0 \text{ W} = 9.216 \text{ kW} P out = V 2 I 2 cos θ L = 240.0 V × 48.00 A × 0.800 = 9216.0 W = 9.216 kW
Total winding copper loss P copper P_{\text{copper}} P copper : P copper = I 1 2 R 1 + I 2 2 R 2 = ( 2.400 A ) 2 × 2.50 Ω + ( 48.00 A ) 2 × 0.0060 Ω P_{\text{copper}} = I_1^2 R_1 + I_2^2 R_2 = (2.400 \text{ A})^2 \times 2.50 \\ \Omega + (48.00 \text{ A})^2 \times 0.0060 \\ \Omega P copper = I 1 2 R 1 + I 2 2 R 2 = ( 2.400 A ) 2 × 2.50 Ω + ( 48.00 A ) 2 × 0.0060 Ω P copper = ( 5.760 × 2.50 ) + ( 2304.0 × 0.0060 ) = 14.40 W + 13.824 W = 28.224 W P_{\text{copper}} = (5.760 \times 2.50) + (2304.0 \times 0.0060) = 14.40 \text{ W} + 13.824 \text{ W} = 28.224 \text{ W} P copper = ( 5.760 × 2.50 ) + ( 2304.0 × 0.0060 ) = 14.40 W + 13.824 W = 28.224 W
Total losses P loss P_{\text{loss}} P loss : P loss = P core + P copper = 150.0 W + 28.224 W = 178.224 W P_{\text{loss}} = P_{\text{core}} + P_{\text{copper}} = 150.0 \text{ W} + 28.224 \text{ W} = 178.224 \text{ W} P loss = P core + P copper = 150.0 W + 28.224 W = 178.224 W
Operating Efficiency η \eta η : η = P out P out + P loss × 100 % = 9216.0 W 9216.0 W + 178.224 W × 100 % \eta = \frac{P_{\text{out}}}{P_{\text{out}} + P_{\text{loss}}} \times 100\% = \frac{9216.0 \text{ W}}{9216.0 \text{ W} + 178.224 \text{ W}} \times 100\% η = P out + P loss P out × 100% = 9216.0 W + 178.224 W 9216.0 W × 100% η = 9216.0 9394.224 × 100 % = 98.10 % \eta = \frac{9216.0}{9394.224} \times 100\% = 98.10\% η = 9394.224 9216.0 × 100% = 98.10%
Final Answer: (a = 20), V 2 = 240 V V_2 = 240 \text{ V} V 2 = 240 V , I 2 = 48.0 A I_2 = 48.0 \text{ A} I 2 = 48.0 A , I 1 = 2.40 A I_1 = 2.40 \text{ A} I 1 = 2.40 A , reflected primary impedance Z 1 ′ = 1600 + j 1200 Ω \mathbf{Z}_1' = 1600 + j 1200 \\ \Omega Z 1 ′ = 1600 + j 1200 Ω , output power P out = 9.216 kW P_{\text{out}} = 9.216 \text{ kW} P out = 9.216 kW , and efficiency η = 98.10 % \eta = 98.10\% η = 98.10% .