14.7 Psychrometrics: Relative Humidity, Wet-Bulb Temperature, and the Psychrometric Chart
FE Other Disciplines Fundamentals of Engineering
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Strategy
About the FE Other Disciplines Exam How to Use This Study Guide
2 Chapter 1: Mathematics
1.1 Analytic Geometry, Trigonometry, and Vector Operations 1.2 Differential and Integral Calculus 1.3 Ordinary Differential Equations and Laplace Transforms 1.4 Linear Algebra, Matrices, and Systems of Equations 1.5 Numerical Methods, Root-Finding, and Numerical Integration
3 Chapter 2: Probability and Statistics
2.1 Probability Distributions, PMFs, and PDFs 2.2 Expected Value, Mean, Variance, and Descriptive Statistics 2.3 Estimation, Confidence Intervals, and Sample Sizes 2.4 Hypothesis Testing, Goodness of Fit, and Linear Regression
4 Chapter 3: Chemistry
3.1 Stoichiometry, Chemical Reactions, and Solutions 3.2 Chemical Equilibrium, Acids/Bases, and Ideal Gas Laws 3.3 Oxidation-Reduction, Electrochemistry, and Corrosion Basics
5 Chapter 4: Instrumentation and Controls
4.1 Sensors, Transducers, and Signal Conditioning 4.2 Data Sampling, Accuracy/Precision, and A/D Conversion 4.3 Logic Diagrams, Boolean Algebra, and Control Logic
6 Chapter 5: Engineering Ethics and Societal Impacts
5.1 NCEES Model Rules of Professional Conduct and Codes of Ethics 5.2 Public Protection, Licensure Boards, and Professional Liability 5.3 Societal Impacts: Sustainability, Life-Cycle Analysis, and Public Safety
7 Chapter 6: Safety, Health, and Environment
6.1 OSHA Regulations, Industrial Hygiene, and PPE 6.2 Hazard Assessment, Risk Management, and Environmental Rules 6.3 Gas Detection and Monitoring 6.4 Electrical Safety 6.5 Confined Space Entry and Ventilation Rates
8 Chapter 7: Engineering Economics
7.1 Time Value of Money, Interest Formulas, and Cash Flow Diagrams 7.2 Capital Budgeting: Present Worth, Annual Worth, IRR, and B/C Ratio 7.3 Depreciation Methods, Income Taxes, and Breakeven Analysis 7.4 Cost Analysis, Uncertainty, Expected Value, and Decision Trees
9 Chapter 8: Statics
8.1 Statics Equilibrium, Free-Body Diagrams, and Force Systems 8.2 Distributed Loads, Resultants, and Equivalent Force-Couple Systems 8.3 Internal Forces in Rigid Bodies: Trusses, Frames, Machines, and Friction 8.4 Three-Dimensional Equilibrium, Cables, and Pulley Systems 8.5 Area Properties: Centroids, Moments of Inertia, and Radius of Gyration 8.6 Weight, Mass, and Force Units: slug, lbm, lbf, and g_c
10 Chapter 9: Dynamics
9.1 Kinematics of Particles and Rigid Bodies 9.2 Newton's Second Law for Particles and Rigid Bodies 9.3 Angular Motion, Torque, and Mass Moment of Inertia 9.4 Work-Energy Principle, Power, and Efficiency 9.5 Impulse-Momentum, Impact, and Coefficient of Restitution 9.6 Dynamic Friction and Vibrations: Natural Frequency and Damping
11 Chapter 10: Strength of Materials
10.1 Stress Types, Axial Stress-Strain, and Thermal Deformation 10.2 Torsion of Circular Shafts, Polar Moment, and Angle of Twist 10.3 Shear and Moment Diagrams 10.4 Flexural Bending Stress and Transverse Shear Stress 10.5 Stress Transformations, Principal Stresses, and Mohr's Circle 10.6 Beam Deflections and Combined Axial/Bending Loading 10.7 Column Buckling (Euler Formula) and Yield/Failure Criteria
12 Chapter 11: Materials
11.1 Crystal Structure, Phase Diagrams, and Material Processing 11.2 Mechanical Properties, Fatigue, Fracture, and Corrosion 11.3 Thermal Properties of Materials 11.4 Electrical and Chemical Properties of Materials 11.5 Material Selection for Engineering Design
13 Chapter 12: Fluid Mechanics
12.1 Fluid Properties, Hydrostatic Pressure, and Manometry 12.2 Dimensionless Numbers and Flow Regimes 12.3 Continuity Equation, Bernoulli Equation, and Energy Equation 12.4 Impulse-Momentum Equation and Forces on Control Volumes 12.5 Flow in Pipes, Friction Factors (Moody Diagram), and Head Losses 12.6 Turbomachinery: Pumps, Turbines, Fans, and Compressors 12.7 Open-Channel Flow, Manning's Equation, and Drag 12.8 Fluid Transport Systems and Flow Measurement 12.9 Ideal Gas Law, Gas Mixtures, and the Real Gas Law
14 Chapter 13: Basic Electrical Engineering
13.1 Electrical Fundamentals, Ohm's Law, and DC Circuits 13.2 AC Circuits, Phasors, Impedance, and Three-Phase Power 13.3 Magnetic Fields, Induction, Transformers, and Motor Efficiency 13.4 Electrical Measuring Devices: Voltmeter, Ammeter, and Wattmeter
15 Chapter 14: Thermodynamics and Heat Transfer
14.1 First & Second Laws of Thermodynamics and Pure Substance Properties 14.2 Thermodynamic Processes and Property Diagrams (T-s, P-h, P-v) 14.3 Heat Transfer: Conduction, Convection, and Radiation 14.4 Ideal Gas Processes and Power/Refrigeration Cycles 14.5 Mass and Energy Balances on Control Volumes 14.6 Combustion and Combustion Products 14.7 Psychrometrics: Relative Humidity, Wet-Bulb Temperature, and the Psychrometric Chart
14.7 Psychrometrics: Relative Humidity, Wet-Bulb Temperature, and the Psychrometric Chart
Key Takeaways Explain This Topic AI
NCEES names psychrometrics with relative humidity and wet bulb as a sub-topic of Thermodynamics and Heat Transfer.
Relative humidity is the ratio of the actual water-vapor partial pressure to the saturation pressure at the same temperature.
Humidity ratio is the mass of water vapor per unit mass of dry air and equals 0.622 times the vapor pressure divided by the difference between total and vapor pressure.
Dry-bulb, wet-bulb, and dew-point temperatures are all equal only at saturation, where relative humidity is 100%.
Sensible heating and cooling move horizontally on a psychrometric chart at constant humidity ratio, while dehumidification requires cooling the air below its dew point.
Last updated: August 2026
14.7 Psychrometrics: Relative Humidity, Wet-Bulb Temperature, and the Psychrometric Chart
NCEES lists "Psychrometrics (e.g., relative humidity, wet bulb)" as the final sub-topic of the Thermodynamics and Heat Transfer area. Psychrometrics treats moist air as a mixture of dry air and water vapor , and the whole subject rests on the fact that the water vapor is present at such low partial pressure that it behaves as an ideal gas.
The Three Temperatures
- Temperature Definition How measured
- Dry-bulb T d b T_{db} T d b The actual air temperature Ordinary thermometer
Wet-bulb T w b T_{wb} T w b Temperature reached by a wetted, ventilated thermometer through adiabatic evaporation Sling psychrometer, or a wetted wick in a moving airstream
Dew point T d p T_{dp} T d p Temperature at which condensation begins on cooling at constant pressure Chilled-mirror instrument, or read from a chart
The universal ordering: T d b ≥ T w b ≥ T d p T_{db} \ge T_{wb} \ge T_{dp} T d b ≥ T w b ≥ T d p
At saturation all three are equal , and the gap between them measures how dry the air is. The wet-bulb depression ( T d b − T w b ) (T_{db} - T_{wb}) ( T d b − T w b ) is therefore a direct index of drying potential — which is why a sling psychrometer determines relative humidity from two temperature readings, and why evaporative cooling works well in a desert and poorly in a swamp.
Relative Humidity ϕ = P v P sat ( T d b ) × 100 % \phi = \frac{P_v}{P_{\text{sat}}(T_{db})}\times100\% ϕ = P sat ( T d b ) P v × 100%
where P v P_v P v is the actual partial pressure of water vapor and P sat P_{\text{sat}} P sat is the saturation pressure at the dry-bulb temperature .
The critical implication: because P sat P_{\text{sat}} P sat rises steeply with temperature, heating air without adding moisture lowers its relative humidity even though the absolute moisture content is unchanged. Air at 10 °C and 80% RH heated to 25 °C falls to about 30% RH — the reason winter indoor air feels dry and requires humidification. Conversely, cooling raises RH until saturation is reached, at which point condensation begins.
- T T T (°C) P sat P_{\text{sat}} P sat (kPa)
- 0 0.611
- 5 0.872
- 10 1.228
- 15 1.706
- 20 2.339
- 25 3.169
- 30 4.246
- 35 5.628
- 40 7.384
Humidity Ratio (Specific Humidity) ω = m v m a = 0.622 P v P − P v [ kg water/kg dry air ] \omega = \frac{m_v}{m_a} = 0.622\,\frac{P_v}{P - P_v} \qquad [\text{kg water/kg dry air}] ω = m a m v = 0.622 P − P v P v [ kg water/kg dry air ]
The 0.622 is the molar-mass ratio M v / M a = 18.02 / 28.97 M_v/M_a = 18.02/28.97 M v / M a = 18.02/28.97 .
Why everything is per kilogram of dry air: during humidification, dehumidification, and mixing, the mass of water changes but the mass of dry air is conserved . Using dry air as the basis makes it the invariant reference, so ω \omega ω changes only when moisture is actually added or removed.
Enthalpy of Moist Air h = 1.006 T + ω ( 2,501 + 1.86 T ) [ kJ/kg dry air, T in ° C ] h = 1.006\,T + \omega(2{,}501 + 1.86\,T) \qquad [\text{kJ/kg dry air, } T \text{ in }°\text{C}] h = 1.006 T + ω ( 2 , 501 + 1.86 T ) [ kJ/kg dry air, T in ° C ]
- Term Meaning
- 1.006 T 1.006\,T 1.006 T Sensible heat of the dry air
- 2,501 ω 2{,}501\,\omega 2 , 501 ω Latent heat of vaporization carried by the moisture
- 1.86 ω T 1.86\,\omega T 1.86 ω T Sensible heat of the vapor
Latent heat dominates. At ω = 0.010 \omega = 0.010 ω = 0.010 the latent term is 25.0 25.0 25.0 kJ/kg against a sensible term of about 20 20 20 kJ/kg at 20 °C. This is why removing moisture is thermodynamically expensive and why air-conditioning loads are reported as separate sensible and latent components.
Processes on the Psychrometric Chart
The chart plots ω \omega ω (vertical) against T d b T_{db} T d b (horizontal), with the saturation curve ( ϕ = 100 % \phi = 100\% ϕ = 100% ) as the upper-left boundary. Lines of constant RH, wet-bulb, and enthalpy overlay it.
- Process Direction on the chart ω \omega ω Notes
- Sensible heating Horizontal, right Constant RH falls
- Sensible cooling Horizontal, left Constant RH rises , until saturation
Cooling + dehumidification Left to saturation, then down along the curve Decreases The only way to remove moisture by cooling
Humidification (steam) Nearly vertical, up Increases Little temperature change
Evaporative cooling Up and to the left along a constant wet-bulb line Increases Adiabatic ; sensible heat converts to latent
Adiabatic mixing Along the straight line joining the two states Between the two Position set by the mass-flow ratio
Worked Example 1: Full State Determination
Air at 30 °C dry-bulb and 50% relative humidity, at 101.3 kPa. Find P v P_v P v , ω \omega ω , h h h , and the dew point.
Vapor pressure , with P sat ( 30 ° C ) = 4.246 P_{\text{sat}}(30°\text{C}) = 4.246 P sat ( 30° C ) = 4.246 kPa: P v = ϕ P sat = 0.50 ( 4.246 ) = 2.123 kPa P_v = \phi P_{\text{sat}} = 0.50(4.246) = 2.123\ \text{kPa} P v = ϕ P sat = 0.50 ( 4.246 ) = 2.123 kPa
Humidity ratio: ω = 0.622 2.123 101.3 − 2.123 = 0.622 2.123 99.18 = 0.622 ( 0.02141 ) = 0.01332 kg/kg dry air \omega = 0.622\frac{2.123}{101.3 - 2.123} = 0.622\frac{2.123}{99.18} = 0.622(0.02141) = 0.01332\ \text{kg/kg dry air} ω = 0.622 101.3 − 2.123 2.123 = 0.622 99.18 2.123 = 0.622 ( 0.02141 ) = 0.01332 kg/kg dry air
Enthalpy: h = 1.006 ( 30 ) + 0.01332 [ 2,501 + 1.86 ( 30 ) ] = 30.18 + 0.01332 ( 2,556.8 ) = 30.18 + 34.06 = 64.2 kJ/kg dry air h = 1.006(30) + 0.01332[2{,}501 + 1.86(30)] = 30.18 + 0.01332(2{,}556.8) = 30.18 + 34.06 = \boxed{64.2\ \text{kJ/kg dry air}} h = 1.006 ( 30 ) + 0.01332 [ 2 , 501 + 1.86 ( 30 )] = 30.18 + 0.01332 ( 2 , 556.8 ) = 30.18 + 34.06 = 64.2 kJ/kg dry air
Note that the moisture carries more energy (34.1 kJ/kg) than the dry air itself (30.2 kJ/kg), at only 1.3% moisture by mass.
Dew point is the saturation temperature corresponding to P v = 2.123 P_v = 2.123 P v = 2.123 kPa. From the table, 2.123 kPa lies between 15 °C (1.706) and 20 °C (2.339). Interpolating: T d p = 15 + 5 ( 2.123 − 1.706 2.339 − 1.706 ) = 15 + 5 ( 0.659 ) = 18.3 ° C T_{dp} = 15 + 5\left(\frac{2.123-1.706}{2.339-1.706}\right) = 15 + 5(0.659) = \boxed{18.3\ °\text{C}} T d p = 15 + 5 ( 2.339 − 1.706 2.123 − 1.706 ) = 15 + 5 ( 0.659 ) = 18.3 ° C
Practical consequence: any surface in this air below 18.3 °C will sweat. A chilled-water pipe at 7 °C or a single-glazed window on a cold day condenses, which is why insulation and vapor barriers are specified against the design dew point rather than the air temperature.
Worked Example 2: Cooling Coil with Sensible and Latent Loads
2.0 kg/s of dry air enters a coil at 30 °C, ω 1 = 0.0133 \omega_1 = 0.0133 ω 1 = 0.0133 (the state above), and leaves at 14 °C, 95% RH. Find the total, sensible, and latent loads.
Exit state , with P sat ( 14 ° C ) ≈ 1.598 P_{\text{sat}}(14°\text{C}) \approx 1.598 P sat ( 14° C ) ≈ 1.598 kPa: P v = 0.95 ( 1.598 ) = 1.518 kPa P_v = 0.95(1.598) = 1.518\ \text{kPa} P v = 0.95 ( 1.598 ) = 1.518 kPa ω 2 = 0.622 1.518 101.3 − 1.518 = 0.622 1.518 99.78 = 0.00946 kg/kg \omega_2 = 0.622\frac{1.518}{101.3-1.518} = 0.622\frac{1.518}{99.78} = 0.00946\ \text{kg/kg} ω 2 = 0.622 101.3 − 1.518 1.518 = 0.622 99.78 1.518 = 0.00946 kg/kg h 2 = 1.006 ( 14 ) + 0.00946 [ 2,501 + 1.86 ( 14 ) ] = 14.08 + 0.00946 ( 2,527.0 ) = 14.08 + 23.90 = 37.98 kJ/kg h_2 = 1.006(14) + 0.00946[2{,}501+1.86(14)] = 14.08 + 0.00946(2{,}527.0) = 14.08 + 23.90 = 37.98\ \text{kJ/kg} h 2 = 1.006 ( 14 ) + 0.00946 [ 2 , 501 + 1.86 ( 14 )] = 14.08 + 0.00946 ( 2 , 527.0 ) = 14.08 + 23.90 = 37.98 kJ/kg
Total load: Q ˙ total = m ˙ a ( h 1 − h 2 ) = 2.0 ( 64.2 − 37.98 ) = 2.0 ( 26.2 ) = 52.5 kW \dot{Q}_{\text{total}} = \dot{m}_a(h_1-h_2) = 2.0(64.2 - 37.98) = 2.0(26.2) = \boxed{52.5\ \text{kW}} Q ˙ total = m ˙ a ( h 1 − h 2 ) = 2.0 ( 64.2 − 37.98 ) = 2.0 ( 26.2 ) = 52.5 kW
Sensible load (temperature change at the exit humidity, using moist-air specific heat ≈ 1.02 kJ/kg·K): Q ˙ s = m ˙ a c p ( T 1 − T 2 ) = 2.0 ( 1.02 ) ( 30 − 14 ) = 32.6 kW \dot{Q}_s = \dot{m}_a c_p(T_1-T_2) = 2.0(1.02)(30-14) = 32.6\ \text{kW} Q ˙ s = m ˙ a c p ( T 1 − T 2 ) = 2.0 ( 1.02 ) ( 30 − 14 ) = 32.6 kW
Latent load (moisture removal): Q ˙ L = m ˙ a ( ω 1 − ω 2 ) ( 2,501 ) = 2.0 ( 0.0133 − 0.00946 ) ( 2,501 ) = 2.0 ( 0.00384 ) ( 2,501 ) = 19.2 kW \dot{Q}_L = \dot{m}_a(\omega_1-\omega_2)(2{,}501) = 2.0(0.0133-0.00946)(2{,}501) = 2.0(0.00384)(2{,}501) = 19.2\ \text{kW} Q ˙ L = m ˙ a ( ω 1 − ω 2 ) ( 2 , 501 ) = 2.0 ( 0.0133 − 0.00946 ) ( 2 , 501 ) = 2.0 ( 0.00384 ) ( 2 , 501 ) = 19.2 kW
Check: 32.6 + 19.2 = 51.8 32.6 + 19.2 = 51.8 32.6 + 19.2 = 51.8 kW, within rounding of 52.5 kW ✓
Sensible heat ratio: S H R = 32.6 / 52.5 = 0.62 SHR = 32.6/52.5 = 0.62 S H R = 32.6/52.5 = 0.62 — so 38% of the cooling capacity goes to removing water , not to lowering temperature. Condensate rate: 2.0 ( 0.00384 ) = 0.0077 2.0(0.00384) = 0.0077 2.0 ( 0.00384 ) = 0.0077 kg/s = 27.7 = 27.7 = 27.7 kg/h.
The design lesson: a coil sized on temperature change alone would be undersized by about 60%. And because dehumidification requires the coil surface to be below the dew point , a chilled-water system running at too high a supply temperature can meet the sensible load while removing no moisture at all — the classic cause of a space that is cool but clammy.
Worked Example 3: Evaporative Cooling
Air at 38 °C and 20% RH passes through an evaporative cooler with 85% effectiveness. The wet-bulb temperature is 22 °C. Find the exit dry-bulb temperature. T out = T d b − ε ( T d b − T w b ) = 38 − 0.85 ( 38 − 22 ) = 38 − 0.85 ( 16 ) = 38 − 13.6 = 24.4 ° C T_{\text{out}} = T_{db} - \varepsilon(T_{db}-T_{wb}) = 38 - 0.85(38-22) = 38 - 0.85(16) = 38 - 13.6 = \boxed{24.4\ °\text{C}} T out = T d b − ε ( T d b − T w b ) = 38 − 0.85 ( 38 − 22 ) = 38 − 0.85 ( 16 ) = 38 − 13.6 = 24.4 ° C
A 13.6 °C drop with no refrigeration — the process is adiabatic, converting sensible heat into latent heat as water evaporates, so it moves up along a constant wet-bulb line.
The hard limit: the exit temperature can never fall below the wet-bulb temperature , which is what makes evaporative cooling effective in dry climates (large wet-bulb depression) and nearly useless in humid ones. At 30 °C and 80% RH the wet-bulb is about 27 °C, so even a perfect cooler could drop the air only 3 °C — and it would leave the space saturated.