30.3 Using Amprobes, Velometers, Pitot Tubes, Manometers & Gauges

Florida HVAC Contractor License Class A/B

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 Current Exam Facts & License Classes 1.2 Exam Format, Open-Book Rules & Pearson VUE 1.3 Eligibility, Experience Paths & Financial Responsibility

2 Establishing the Contracting Business

2.1 Business Organizational Structure 2.2 Business Plan, Marketplace & License Scope 2.3 Professionals, Fixed Assets & Bonding

3 Insurance for Florida HVAC Contractors

3.1 Obtaining Insurance (GL, Workers' Compensation & Bonds) 3.2 Coverages, Limits & Policy Language 3.3 Maintaining Insurance & CILB Certificate-Holder Rules

4 Overhead, Staffing & Markets

4.1 Developing the Business, Staffing & Markets 4.2 Determining Business Overhead (FICA, FUTA, SUTA, Workers' Comp, Rent & Utilities) 4.3 Determining Outsourced Services

5 Bids, Proposals & Estimating

5.1 Preparing Bids and Proposals 5.2 AIA Documents, Offers & Contract Components 5.3 Labor Productivity, Overhead & Project Costing

6 Purchasing, Invoices, Draws & Safety Programs

6.1 Purchasing Materials, UCC & Inventory (FIFO) 6.2 Invoices, Draw Requests & Percentage of Completion 6.3 Developing a Safety Program (OSHA, SDS & Drug Testing)

7 Managing Contracts

7.1 Contract Law, Scope & Completion Schedules 7.2 Florida Lien Law Inside Contracting 7.3 Mediation, Arbitration, Tort Law & Risk

8 Managing Trade Operations

8.1 Scheduling Trade Operations (CPM, RFI & Submittals) 8.2 OSHA Records, Document Retainage & Penalties 8.3 Takeoffs, Equipment Lease vs Purchase & Inventory

9 Accounting I: Receivables, Payables & Cash

9.1 Managing Accounts Receivable 9.2 Managing Accounts Payable & Discounts 9.3 Cash Flow, Banking & Financial Ratios

10 Accounting II: Taxes, Job Cost & Payroll

10.1 Filing Tax Forms & Returns 10.2 Tracking Job Costs 10.3 Payroll, Employment Taxes & Garnishments

11 Managing Human Resources

11.1 Hiring, I-9, Background Checks & Discrimination 11.2 HR Policies, OSHA & Drug-Test Chain of Custody 11.3 Evaluating Employees

12 Florida Contractor Law: Chapter 489 & 61G4

12.1 Chapter 489: Certified vs Registered & Qualifying Agents 12.2 61G4 Board Rules, Advertising & Discipline 12.3 Qualifying Agent Duties, Supervision & Additional Entities

13 Florida Construction Lien Law (Chapter 713)

13.1 Construction Lien Overview & Claimants 13.2 Notices to Owner, Time Limits & Perfecting Liens 13.3 Payment Bonds, Waivers & Claims of Lien

14 Financial Responsibility, CE & Federal Rules

14.1 Financial Responsibility & the 660 FICO Rule 14.2 Continuing Education & Biennial Renewal 14.3 Federal Employment, Immigration, OSHA & Environmental Rules

15 Plans, Specs & Equipment Selection

15.1 Reading Plans, Specifications, Symbols & Scales 15.2 Recommending Plan Changes & Equipment Types 15.3 EER, SEER, ARI Listings & Cost Effectiveness

16 Energy Codes, Loads & Thermal Resistance

16.1 Florida Energy Codes, R-Values & U-Factors 16.2 Determining HVAC Heating & Cooling Loads 16.3 Applying Energy Conservation, Fan Curves & Pump Curves

17 HVAC System & Duct Design

17.1 Designing HVAC Systems (Psychrometrics, Enthalpy & Airflow) 17.2 Designing Duct Systems & Insulation 17.3 Selecting Equipment, Location & Codes

18 Piping, Pumps, Boilers, Controls & Rigging Design

18.1 Pipe Sizing, Valves, Fittings, Sealants & Layout 18.2 Control Requirements, Fan Motors, CFM & Compressor Capacity 18.3 Pumps, Boilers, Steam, Fuel & Pipe Insulation 18.4 Grease Ducts, Live Loads, Rigging & Mechanical Equipment

19 Sheet Metal Duct Fabrication

19.1 Fabricating Rectangular & Round Ducts 19.2 Seams, Locks, Taping, Mastics & Liners 19.3 Fittings, Outlets & Grilles 19.4 Kitchen Hoods, Exhausts & Drain Pans

20 Split, Package & Heat Pump Installation

20.1 Installing Split & Package Air Conditioners 20.2 Installing Split & Package Heat Pumps 20.3 Air-Cooled vs Water-Cooled Systems

21 Large Systems, Chillers & Towers

21.1 Installing by Tonnage & Class A vs Class B Limits 21.2 Chilled Water, Water Towers & Secondary Coolant 21.3 Centrifugal, Absorption & Ammonia Systems

22 Refrigeration, Coolers, Ventilation & Controls Install

22.1 Low, Medium & Ultra-Low Temperature Systems & EPA Rules 22.2 Walk-In & Reach-In Coolers 22.3 Ventilation, Exhaust, Makeup Air, Grease Ducts & Kitchen Exhaust 22.4 Geothermal, Pneumatic & DDC Controls, TAB & Smoke Tests

23 Condensers, Compressors & Air Handlers

23.1 Installing Air-Cooled & Water-Cooled Condensers 23.2 Hermetic, Semi-Hermetic & Centrifugal Compressors 23.3 Air Handlers, Evaporators, Heat Exchangers, Receivers & Heat Strips

24 Duct, Fans, Filters & Terminals

24.1 Installing Sheet Metal, Fiberglass & Flexible Duct 24.2 Fans, Blowers, Motors, Grilles, Registers & Fire Dampers 24.3 Filters, Flues, Warm-Air, Gas & Fuel-Oil Appliances

25 Refrigerant Piping & Joining

25.1 Refrigerant Piping, Copper Tubing & Pipe Sizing 25.2 Brazing, Welding, Flaring, Swaging & Soldering 25.3 Steel Pipe, Plastic Pipe, Threading & Oxy-Acetylene 25.4 Hangers, Supports, Horizontally Supported Piping & Pressure Testing

26 Metering Devices & Line Components

26.1 TXVs, Capillary Tubes, Reversing Valves & Metering Devices 26.2 Liquid, Suction & Heat-Pump Dryers, Filters & Oil Traps 26.3 Receivers, Heat Strips, Gas/Oil Appliances & Related Accessories

27 Controls Installation

27.1 Pressure, Temperature, Humidity & Bellows Controls 27.2 Thermostats, Humidistats, Pneumatic & Solid-State Controls 27.3 Transformers, Capacitors, Contactors, Relays & Safety Disconnects 27.4 Defrost Components, Starters, Solenoids & Limit Switches

28 Motors, Wiring & Electrical Installation

28.1 Wiring Single-Phase & Three-Phase Equipment 28.2 Motor Types, Protection, Controllers, Belts & Pulleys 28.3 Geothermal Loops, Surge Protectors, Phase Monitors & Plastic Pipe

29 Diagnostic Analysis: Refrigeration

29.1 Pressure-Enthalpy Diagrams & Operating Pressures 29.2 Air Volumes, Enthalpy, Wet-Bulb & Dry-Bulb 29.3 Leak Detection & Refrigeration Test Instruments

30 Diagnostic Analysis: Electrical & Instruments

30.1 Current Draw, Voltage, Power & Motor Terminals 30.2 Testing Relays, Capacitors, Starters, Transformers & Defrost Stats 30.3 Using Amprobes, Velometers, Pitot Tubes, Manometers & Gauges

31 Recovery, Repair & Calibration

31.1 Nitrogen & Gas Regulators, Recovery & Retrofit 31.2 Repairing Hermetic, Semi-Hermetic, Centrifugal Compressors & Blowers 31.3 Calibrating Thermostats, Pressure Switches & Pneumatic Controls 31.4 Superheat, Safety Cutouts, Defrost Clocks & Freezer Controls

32 Mechanical Service & Cleaning

32.1 Belts, Pulleys, Motor Rotation & Seized Compressors 32.2 Crankcase & Evaporator Pressure Regulators & Unloaders 32.3 Cleaning Towers, Condensers, Foreign Matter & Condensate Drains

33 Jobsite Safety & Equipment

33.1 PPE: Hearing, Head, Eye, Face & Respiratory Protection 33.2 Lockout/Tagout, Warning Signs, Toxic Materials & Ventilation 33.3 Rigging, Hoists, Cranes, Forklifts, Backhoes & Excavation 33.4 Ladders, Scaffolds, Tools & Air Compressors

34 Energy Management

34.1 Envelope, Duct Pressure & Blower-Door Testing 34.2 Efficient Equipment, Zoning, ERVs, Wi-Fi Thermostats & Green Buildings 34.3 Energy Forms, R/U Factors, Window Heat Gain & Florida Load Calcs

35 Indoor Air Quality

35.1 Ventilation, Filtration, Humidity, UV & Air Cleaners 35.2 Contaminants, Source Control, TAB & Human Health Effects

30.3 Using Amprobes, Velometers, Pitot Tubes, Manometers & Gauges

Key Takeaways Explain This Topic AI

Trade E item 21 is using test equipment: clamp-on ammeters (Amprobe), velometers, pitot tubes, manometers, and gauges. Chapter 22.4 installed TAB; this section is choosing the instrument and reading it without mixing units.

A clamp-on ammeter measures current from the magnetic field around ONE conductor. Clamping the whole cable (hot and neutral, or all three phases in one jaw) reads near zero because the fields cancel. Compare the reading to RLA/FLA, not to LRA.

A velometer reads face velocity in fpm at a grille or coil. A pitot tube plus manometer reads velocity pressure in a duct. For standard air, V (fpm) ≈ 4005 × √VP (inches of water). Do not use 4005 × VP.

Duct static, velocity pressure, and total pressure are inches of water (in. w.c.), not psig. Total pressure = static + velocity pressure. 1 psi ≈ 27.7 in. w.c. — a 0.5 in. w.c. blower ESP is about 0.018 psi, not 'half a pound.'

Ohm and microfarad tests are LOTO. Clamp-on current and voltage tests are live measurements with a CAT-rated meter. Refrigerant gauges belong to Chapter 29; this cluster is electrical current and air/water pressure instruments.

Last updated: August 2026

30.3 Using Amprobes, Velometers, Pitot Tubes, Manometers & Gauges

Trade E’s instrument bullet is using test equipment : the Amprobe (clamp-on ammeter), velometer , pitot tube , manometer , and gauges . Chapter 22.4 already used pitot math in a TAB install. Chapter 29.3 used refrigerant leak detectors and refrigeration gauges. This section is the diagnostic use of the same kit on a Florida service call: current without breaking the circuit, air velocity at a face versus velocity pressure in a duct, and inches of water for static. The CBT books are Refrigeration & Air Conditioning Technology , 9th Edition (2021), the Troubleshooting Handbook , 2nd Edition (2003), and the Trane Ductulator when you translate velocity into cfm. OSHA 1926 still splits the work: LOTO before internals; rated live meters for clamp-on and voltage.

Quick Answer: Clamp-on (Amprobe): one conductor, compare to RLA/FLA . Velometer: face fpm at a grille or coil. Pitot + manometer: duct VP in inches of water , V ≈ 4005 VP V \approx 4005 \sqrt{\text{VP}} V ≈ 4005 VP ​ for standard air. Static is also in. w.c. , not psig. TP = SP + VP .

Amprobe / clamp-on ammeter — current without a break

Amprobe is the brand that became the field word for a clamp-on AC ammeter . The jaw reads current from the magnetic field around a single conductor . That is how you get the 19.8 A versus 14.1 RLA comparison in 30.1 without opening the circuit.

One conductor. If you clamp the entire SO cord — hot and neutral — the fields cancel and the meter reads near zero on a healthy circuit. On three-phase, clamp one leg at a time ; do not swallow all three. A ground conductor in the jaw with the hot will also lie. Many techs still use a line-splitter or a plug adapter that separates the conductors at a receptacle for fractional-horsepower indoor units.

Range and inrush. Set a range above FLA , not above LRA, for running load. Use an inrush (peak/hold) function if you actually need LRA; a slow analog needle will not catch it. A compressor that starts at ~70 A and runs at 14 A is doing what LRA and RLA said. A compressor that runs at 22 A on a 14 A RLA is the 30.1 overload story.

True RMS meters belong on VFD and SCR loads; an averaging meter can mis-read electronic fan speeds. CAT rating and insulated jaws still matter on a 480-volt RTU. Clamp-on is a live test: covers as listed, PPE as Chapter 33, no ohm probes on those same terminals while they are hot. Some clamp-ons also read volts and watts ; watts on a motor still want the PF discussion from 30.1 — a clamp that multiplies E × I without PF is reporting VA .

Worked clamp-on. Indoor blower nameplate FLA 6.8 A , 230 V, 1φ. You read 9.4 A , supply static +0.55 in. w.c. , return −0.40 in. w.c. External static is 0.95 in. w.c. against a 0.50 in. w.c. nameplate ESP. High static, high amps, low airflow — dirty filter, crushed flex, wet coil, closed dampers — not a failed blower motor until the air path is proven. That is how the Amprobe and the manometer talk to each other.

Velometer versus pitot tube — two different velocities

A velometer (the classic Alnor swinging-vane instrument, or a rotating-vane / hot-wire anemometer doing the same job) reads air speed at a plane in feet per minute . Hold it in the plane of the grille , the coil face, or an outdoor-air hood. Average a grid. Cfm ≈ V × Ak , where Ak is the effective (not geometric) area of the grille — the manufacturer’s Ak, not the painted opening you measured with a tape. A rotating vane laid on a filter rack reads face velocity ; a 24×24 filter (4 ft²) at 300 fpm is about 1,200 cfm through that filter if the velocity is representative.

A pitot tube is a dual-port probe: the tip faces the flow and sees total pressure ; the side taps see static pressure . A manometer between those ports reads velocity pressure (VP) . You use a pitot inside a duct , not at a grille face. Traverse (ASHRAE / AABC / NEBB grid), average √VP (average the velocities, not the raw VP if the item is picky), then

V ≈ 4005 × VP V \approx 4005 \times \sqrt{\text{VP}} V ≈ 4005 × VP ​

for standard air (0.075 lb/ft³), with V in fpm and VP in inches of water . Cfm = V × inside area (ft²). Hot, wet, or high-altitude air changes density and the constant; Florida comfort ducts are treated as standard air unless the item says otherwise.

Worked pitot (same arithmetic as 22.4, diagnostic use). VP = 0.16 in. w.c.

V = 4005 × 0.16 = 4005 × 0.40 = 1,602 fpm V = 4005 \times \sqrt{0.16} = 4005 \times 0.40 = 1{,}602\ \text{fpm} V = 4005 × 0.16 ​ = 4005 × 0.40 = 1 , 602 fpm

A 24×12 duct (2.0 ft² inside) is about 3,200 cfm . If the schedule was 2,400 cfm, you are high . If you wrongly compute 4005 × 0.16 = 641 4005 \times 0.16 = 641 4005 × 0.16 = 641 fpm, you will starve every other branch trying to “fix” a number that was never low.

When to grab which. Velometer: grilles, coils, OA intakes, hood faces — places a pitot cannot sit in developed duct flow. Pitot: duct traverses , fan inlet/outlet where you need VP, SP, and TP . A flow hood (balometer) is a velometer family instrument that integrates face velocity into cfm at a diffuser. None of these replace a tachometer if the fan rpm is wrong, and none of them replace the Amprobe if the motor is over FLA.

Manometers, inches of water, and gauges

A manometer measures low air (and sometimes gas) pressure. Forms: U-tube , inclined , digital , and Magnehelic (diaphragm gauge). The HVAC air unit is inches of water column (in. w.c. or in. WG) . Total pressure = static pressure + velocity pressure :

TP = SP + VP \text{TP} = \text{SP} + \text{VP} TP = SP + VP

Static pressure is the push on the duct wall. Velocity pressure is the directed energy of the moving air. A pitot’s total port minus atmosphere is TP; side port minus atmosphere is SP; total minus static is VP.

Inches of water are not pounds per square inch. 1 psi ≈ 27.7 in. w.c. A blower nameplated 0.50 in. w.c. ESP is about 0.018 psi . Calling that “half a pound of static” is how you talk yourself into a hydronic gauge on a duct. Typical comfort-duct static sits in tenths to about 2 in. w.c. Kitchen grease ducts and high-pressure VAV boxes run higher, still in inches of water , not refrigerant psig. Natural-gas manifold pressure is often 3.5 in. w.c. (inches of water again). Hydronic TAB uses psig or feet of head on a differential gauge across a circuit setter — different instrument, different unit.

Worked static. Blower nameplate 0.50 in. w.c. ESP. Return static −0.25 , supply +0.30 . Total ESP = 0.55 in. w.c. — close to nameplate, amps should be near FLA if the motor is healthy. Same blower, return −0.45 , supply +0.55 , ESP 1.00 in. w.c. : high static, high amps, low cfm. Open the air path before you replace the motor you just clamp-on tested.

Gauges on this Trade E bullet include the air gauges above and the refrigerant manifold from Chapter 29 (compound suction in psig/in. Hg, high-side psig). Do not put a 500-psig refrigerant gauge on a 1-inch Magnehelic and expect a duct reading, and do not put a Magnehelic on a R-410A liquid line. Vacuum gauges (microns) are a recovery/evacuation instrument (Chapter 31), not a velometer.

  • Instrument Reads Unit Exam trap
  • Clamp-on / Amprobe Current on one conductor Amperes vs RLA/FLA Whole-cable clamp reads ~0
  • Voltmeter E at disconnect and motor Volts Off-load panel voltage only
  • Velometer / vane / hot-wire Face velocity fpm; cfm = V × Ak Using geometric area instead of Ak
  • Pitot tube VP, SP, TP in a duct in. w.c. 4005 × VP, no square root

U-tube / Magnehelic / digital manometer SP, VP, TP, gas manifold Inches of water Calling 0.5 in. w.c. “0.5 psi”

  • Refrigerant manifold Suction / discharge psig / in. Hg Using it as a duct static gauge
  • Hydronic differential gauge Pressure drop across a setter psi or ft of head Mixing with in. w.c. duct static
  • Florida HVAC scenario

Sunrise Comfort, certified Class B in Orange County, is balancing a 5-ton changeout (well under 25 tons). The helper clamps the entire outdoor whip, reads 0.2 A , and condemns the compressor as open. Separately he holds a velometer in a 16×8 trunk, treats 800 fpm as if it were a pitot VP of 800 in. w.c., and reports the duct is “800 inches of water — the fan is in surge.” Correct kit: clamp one leg of the whip and compare to RLA ; use the pitot and manometer in that trunk (VP will be a few tenths of an inch of water); use the velometer at the supply grilles with Ak . A Magnehelic on the return shows −0.35 in. w.c. , not −0.35 psi. The owner’s 30-ton office RTU next door is Class A work; Class B still has to traverse that 30-ton supply duct with a pitot and read inches of water on the exam.

Traps: (1) Clamping hot and neutral together. (2) Comparing running amps to LRA. (3) Using a velometer as if it read VP. (4) 4005 × VP 4005 \times \text{VP} 4005 × VP without the square root. (5) Duct static quoted in psig. (6) Refrigerant gauges on ducts. (7) Ohm tests without LOTO, or live clamp-on treated as an excuse to skip LOTO on internals.

Loading diagram... Which instrument for which HVAC measurement