29.3 Leak Detection & Refrigeration Test Instruments
Florida HVAC Contractor License Class A/B
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 Current Exam Facts & License Classes 1.2 Exam Format, Open-Book Rules & Pearson VUE 1.3 Eligibility, Experience Paths & Financial Responsibility
2 Establishing the Contracting Business
2.1 Business Organizational Structure 2.2 Business Plan, Marketplace & License Scope 2.3 Professionals, Fixed Assets & Bonding
3 Insurance for Florida HVAC Contractors
3.1 Obtaining Insurance (GL, Workers' Compensation & Bonds) 3.2 Coverages, Limits & Policy Language 3.3 Maintaining Insurance & CILB Certificate-Holder Rules
4 Overhead, Staffing & Markets
4.1 Developing the Business, Staffing & Markets 4.2 Determining Business Overhead (FICA, FUTA, SUTA, Workers' Comp, Rent & Utilities) 4.3 Determining Outsourced Services
5 Bids, Proposals & Estimating
5.1 Preparing Bids and Proposals 5.2 AIA Documents, Offers & Contract Components 5.3 Labor Productivity, Overhead & Project Costing
6 Purchasing, Invoices, Draws & Safety Programs
6.1 Purchasing Materials, UCC & Inventory (FIFO) 6.2 Invoices, Draw Requests & Percentage of Completion 6.3 Developing a Safety Program (OSHA, SDS & Drug Testing)
7 Managing Contracts
7.1 Contract Law, Scope & Completion Schedules 7.2 Florida Lien Law Inside Contracting 7.3 Mediation, Arbitration, Tort Law & Risk
8 Managing Trade Operations
8.1 Scheduling Trade Operations (CPM, RFI & Submittals) 8.2 OSHA Records, Document Retainage & Penalties 8.3 Takeoffs, Equipment Lease vs Purchase & Inventory
9 Accounting I: Receivables, Payables & Cash
9.1 Managing Accounts Receivable 9.2 Managing Accounts Payable & Discounts 9.3 Cash Flow, Banking & Financial Ratios
10 Accounting II: Taxes, Job Cost & Payroll
10.1 Filing Tax Forms & Returns 10.2 Tracking Job Costs 10.3 Payroll, Employment Taxes & Garnishments
11 Managing Human Resources
11.1 Hiring, I-9, Background Checks & Discrimination 11.2 HR Policies, OSHA & Drug-Test Chain of Custody 11.3 Evaluating Employees
12 Florida Contractor Law: Chapter 489 & 61G4
12.1 Chapter 489: Certified vs Registered & Qualifying Agents 12.2 61G4 Board Rules, Advertising & Discipline 12.3 Qualifying Agent Duties, Supervision & Additional Entities
13 Florida Construction Lien Law (Chapter 713)
13.1 Construction Lien Overview & Claimants 13.2 Notices to Owner, Time Limits & Perfecting Liens 13.3 Payment Bonds, Waivers & Claims of Lien
14 Financial Responsibility, CE & Federal Rules
14.1 Financial Responsibility & the 660 FICO Rule 14.2 Continuing Education & Biennial Renewal 14.3 Federal Employment, Immigration, OSHA & Environmental Rules
15 Plans, Specs & Equipment Selection
15.1 Reading Plans, Specifications, Symbols & Scales 15.2 Recommending Plan Changes & Equipment Types 15.3 EER, SEER, ARI Listings & Cost Effectiveness
16 Energy Codes, Loads & Thermal Resistance
16.1 Florida Energy Codes, R-Values & U-Factors 16.2 Determining HVAC Heating & Cooling Loads 16.3 Applying Energy Conservation, Fan Curves & Pump Curves
17 HVAC System & Duct Design
17.1 Designing HVAC Systems (Psychrometrics, Enthalpy & Airflow) 17.2 Designing Duct Systems & Insulation 17.3 Selecting Equipment, Location & Codes
18 Piping, Pumps, Boilers, Controls & Rigging Design
18.1 Pipe Sizing, Valves, Fittings, Sealants & Layout 18.2 Control Requirements, Fan Motors, CFM & Compressor Capacity 18.3 Pumps, Boilers, Steam, Fuel & Pipe Insulation 18.4 Grease Ducts, Live Loads, Rigging & Mechanical Equipment
19 Sheet Metal Duct Fabrication
19.1 Fabricating Rectangular & Round Ducts 19.2 Seams, Locks, Taping, Mastics & Liners 19.3 Fittings, Outlets & Grilles 19.4 Kitchen Hoods, Exhausts & Drain Pans
20 Split, Package & Heat Pump Installation
20.1 Installing Split & Package Air Conditioners 20.2 Installing Split & Package Heat Pumps 20.3 Air-Cooled vs Water-Cooled Systems
21 Large Systems, Chillers & Towers
21.1 Installing by Tonnage & Class A vs Class B Limits 21.2 Chilled Water, Water Towers & Secondary Coolant 21.3 Centrifugal, Absorption & Ammonia Systems
22 Refrigeration, Coolers, Ventilation & Controls Install
22.1 Low, Medium & Ultra-Low Temperature Systems & EPA Rules 22.2 Walk-In & Reach-In Coolers 22.3 Ventilation, Exhaust, Makeup Air, Grease Ducts & Kitchen Exhaust 22.4 Geothermal, Pneumatic & DDC Controls, TAB & Smoke Tests
23 Condensers, Compressors & Air Handlers
23.1 Installing Air-Cooled & Water-Cooled Condensers 23.2 Hermetic, Semi-Hermetic & Centrifugal Compressors 23.3 Air Handlers, Evaporators, Heat Exchangers, Receivers & Heat Strips
24 Duct, Fans, Filters & Terminals
24.1 Installing Sheet Metal, Fiberglass & Flexible Duct 24.2 Fans, Blowers, Motors, Grilles, Registers & Fire Dampers 24.3 Filters, Flues, Warm-Air, Gas & Fuel-Oil Appliances
25 Refrigerant Piping & Joining
25.1 Refrigerant Piping, Copper Tubing & Pipe Sizing 25.2 Brazing, Welding, Flaring, Swaging & Soldering 25.3 Steel Pipe, Plastic Pipe, Threading & Oxy-Acetylene 25.4 Hangers, Supports, Horizontally Supported Piping & Pressure Testing
26 Metering Devices & Line Components
26.1 TXVs, Capillary Tubes, Reversing Valves & Metering Devices 26.2 Liquid, Suction & Heat-Pump Dryers, Filters & Oil Traps 26.3 Receivers, Heat Strips, Gas/Oil Appliances & Related Accessories
27 Controls Installation
27.1 Pressure, Temperature, Humidity & Bellows Controls 27.2 Thermostats, Humidistats, Pneumatic & Solid-State Controls 27.3 Transformers, Capacitors, Contactors, Relays & Safety Disconnects 27.4 Defrost Components, Starters, Solenoids & Limit Switches
28 Motors, Wiring & Electrical Installation
28.1 Wiring Single-Phase & Three-Phase Equipment 28.2 Motor Types, Protection, Controllers, Belts & Pulleys 28.3 Geothermal Loops, Surge Protectors, Phase Monitors & Plastic Pipe
29 Diagnostic Analysis: Refrigeration
29.1 Pressure-Enthalpy Diagrams & Operating Pressures 29.2 Air Volumes, Enthalpy, Wet-Bulb & Dry-Bulb 29.3 Leak Detection & Refrigeration Test Instruments
30 Diagnostic Analysis: Electrical & Instruments
30.1 Current Draw, Voltage, Power & Motor Terminals 30.2 Testing Relays, Capacitors, Starters, Transformers & Defrost Stats 30.3 Using Amprobes, Velometers, Pitot Tubes, Manometers & Gauges
31 Recovery, Repair & Calibration
31.1 Nitrogen & Gas Regulators, Recovery & Retrofit 31.2 Repairing Hermetic, Semi-Hermetic, Centrifugal Compressors & Blowers 31.3 Calibrating Thermostats, Pressure Switches & Pneumatic Controls 31.4 Superheat, Safety Cutouts, Defrost Clocks & Freezer Controls
32 Mechanical Service & Cleaning
32.1 Belts, Pulleys, Motor Rotation & Seized Compressors 32.2 Crankcase & Evaporator Pressure Regulators & Unloaders 32.3 Cleaning Towers, Condensers, Foreign Matter & Condensate Drains
33 Jobsite Safety & Equipment
33.1 PPE: Hearing, Head, Eye, Face & Respiratory Protection 33.2 Lockout/Tagout, Warning Signs, Toxic Materials & Ventilation 33.3 Rigging, Hoists, Cranes, Forklifts, Backhoes & Excavation 33.4 Ladders, Scaffolds, Tools & Air Compressors
34 Energy Management
34.1 Envelope, Duct Pressure & Blower-Door Testing 34.2 Efficient Equipment, Zoning, ERVs, Wi-Fi Thermostats & Green Buildings 34.3 Energy Forms, R/U Factors, Window Heat Gain & Florida Load Calcs
35 Indoor Air Quality
35.1 Ventilation, Filtration, Humidity, UV & Air Cleaners 35.2 Contaminants, Source Control, TAB & Human Health Effects
29.3 Leak Detection & Refrigeration Test Instruments
Key Takeaways Explain This Topic AI
FBC Mechanical 1110.3: leak/strength-test with oxygen-free nitrogen, helium, or argon — never oxygen, air, or combustible gas. Oxygen plus oil is an explosion hazard.
Soap bubbles find leaks on a pressurized circuit. Electronic (heated-diode or infrared) detectors are the usual choice on HFC systems such as R-410A. Halide (chloride/halogen) torches respond to chlorine in CFC/HCFC refrigerants (R-12, R-22), not to R-410A.
UV dye plus a lamp is a supplement after the manufacturer allows it — not a license to keep topping off a leaker, and not a substitute for EPA Section 608 recovery and repair rules.
A micron vacuum gauge on the system (not the pump-mounted analog in-Hg compound gauge) is what proves FBC 1110.5: 500 microns, then an isolated hold at or below 1,500 microns for at least 10 minutes.
Velometer, clamp-on ammeter (Amprobe), and VOM are Trade E test instruments: air velocity, current draw versus RLA, and volts/ohms on controls. They do not replace a micron gauge or a leak detector.
Last updated: August 2026
29.3 Leak Detection & Refrigeration Test Instruments
Trade E still has to find the hole and prove the instruments . The outline’s remaining cluster in this chapter is chlorine/halogen leak detectors , the testing equipment used on a refrigeration call ( velometer, Amprobe, VOM, vacuum gauges ), and the standing rule that you already met in Section 25.4: never use oxygen as a pressure-test gas . Refrigeration & Air Conditioning Technology , 9th Edition (2021) is the detector-and-meter book. FBC Mechanical 2023 Section 1110 is the test-gas and vacuum sentence. EPA Section 608 (federal, not a substitute for the CILB card) still forbids venting. Class B still diagnoses through 25 tons / 500,000 Btu per system .
Quick Answer: Pressurize with oxygen-free nitrogen (never oxygen ). Find leaks with soap bubbles and/or an electronic detector on R-410A . A halide torch is a chlorine tool ( R-22 / R-12 ), not a 410A tool. Prove vacuum with a micron gauge ( 500 / 1,500 / 10 min ). Amprobe = amps; VOM = volts/ohms; velometer = air fpm.
Never oxygen — then pick a detector that matches the refrigerant
FBC Mechanical 1110.3: field strength/leak tests use oxygen-free nitrogen, helium, or argon . Oxygen, air, and combustible gases shall not be used. The cutting-torch oxygen hose is the classic fatal shortcut: oxygen + compressor oil is an explosion . Shop air carries moisture and the same fire problem in an oily pipe. The small-bore exception (nameplate refrigerant as the test medium on tubing not over 5/8 inch OD ) is not a license to skip nitrogen on a 7/8-inch suction, and it is not permission to spray extra 410A around a fitting “to listen for it” — that is venting under 608.
Standing-pressure decay (nitrogen, regulator, relief, 1110.4 gauge rules, 60-minute hold with no makeup gas ) tells you whether the circuit leaks. Detectors tell you where .
Method How it works Use it when Do not
Soap bubble / bubble solution Nitrogen (or listed test gas) pressure; film at joints, flares, Schrader caps, gaskets Cheap, visual, every pressurized circuit Use on a vacuum (bubbles need positive pressure); use a corrosive dish soap that eats copper if the listing wants a commercial bubble fluid
Electronic (heated diode, infrared, corona) Sensor responds to halogen refrigerant in air R-410A, R-134a, R-454B , and most HFC/HFO comfort-cooling circuits; also HCFCs Sniff a nitrogen-only test without a trace of refrigerant if the detector needs refrigerant molecules; ignore calibration and wind
Ultrasonic Microphone hears turbulent leak noise Pressurized nitrogen leaks in noisy mechanical rooms Treat it as a 608 refrigerant identifier
UV dye + lamp Dye circulates; UV shows the stain Manufacturer-approved dye, after the leak is a service reality Dump dye into a system the OEM forbids; use dye as a reason to keep topping off a leaker
Halide (chloride / halogen) torch Fuel flame over a copper element turns green/blue-green in chlorine CFC / HCFC with chlorine: R-12, R-22, R-502 R-410A, R-134a, R-404A (no chlorine — the torch will not tell the truth); machinery rooms with flammables; occupied space as a “sniffer”
Halide torch is the outline’s chlorine/halogen leak detector . It is an old, exam-favorite tool, and it is refrigerant-specific . R-22 has chlorine; the copper element forms copper chloride and the flame greens . R-410A is an HFC blend (R-32/R-125) with no chlorine — a halide torch is the wrong detector. Electronic heated-diode and IR tools are what you carry on a 410A Florida split. A helper who “always uses the green-flame torch” on 410A will pass a leaking liquid line and then add charge.
Electronic detectors still need a little refrigerant in the nitrogen if you are hunting on a repaired, empty circuit — follow the detector manual (some IR tools want a known trace; some ultrasonic tools do not). Calibrate, sniff from the bottom of a joint (refrigerant vapors are often heavier than air), and remember a 15 mph beach breeze will steal the sample. Soap bubbles remain the honest backup on a flare that the electronic wand cannot pin.
UV dye is a supplement . It does not replace 608 leak-repair thresholds on larger appliances, and it does not make a chronic leaker legal because “we can see it glow next season.” Recover, repair, nitrogen-test, evacuate, weigh in.
Worked leak call. A 3-ton R-410A change-out in Lee County loses 80 psig of nitrogen overnight on the 1110 hold. Helper A opens the oxygen hose “to get more pressure.” Stop — 1110.3 and the oil-film bomb. Helper B brings the pressure back with nitrogen , soaps the flares, and finds a wet Schrader. Helper C waves a halide torch and declares the circuit tight because the flame stayed orange — wrong detector for 410A. An electronic wand at the same Schrader screams. Replace the core, retest 60 minutes, then 500-micron vacuum.
Vacuum gauges vs the manifold compound gauge
Compound gauges on a manifold read in-Hg vacuum to some psig . They are fine for pump-down to a low-side psig or a rough “into vacuum.” They are not accurate in the micron range. 1,000 microns = 1 mm Hg ≈ 0.039 in. Hg . The last inch on a compound gauge is a barn door compared with 500 microns .
FBC Mechanical 1110.5 method 2: achieve 500 microns , isolate the pump, remain at or below 1,500 microns for at least 10 minutes . That number is read on a micron (vacuum) gauge piped to the system , valve-off from the pump so you are not reading the pump’s happy display through a wet hose.
Worked vacuum. Micron gauge on the suction service port: 400 microns , pump isolated. Ten minutes later 1,200 microns — pass (still ≤1,500). Same start, 2,800 microns in three minutes — leak or moisture . If the rise is fast and nitrogen standing-pressure already failed, it is a leak . If standing nitrogen held and microns climb slowly toward a plateau, it is often water in the oil/drier — keep pumping, change the drier, do not charge.
Deep vacuum is also how you boil remaining moisture. A 29-inch compound “vacuum” at a 40°F coil is not 500 microns. Buy the micron gauge.
Velometer, Amprobe, VOM — the rest of the Trade E kit
The outline lists these with refrigeration test equipment because a “no-cool” is not always a leak.
Velometer — Section 29.2. If cfm is 280 per ton, fix air before you hunt a 2-ounce leak that is not there.
Amprobe (clamp-on ammeter) — measures current without opening the circuit. Compare compressor RLA (rated load amps) on the nameplate to running amps. High amps + high head = dirty condenser, overcharge, or bad outdoor airflow (Florida grass clippings in the coil). High amps + locked rotor that never drops = seized compressor (Chapter 32). Low amps + high SH = unloaded or starved compressor, not a motor that “needs more gas.” Clamp one conductor; clamping the whole whip reads near zero because the currents cancel.
Worked Amprobe. 3-ton 410A compressor RLA 16.8 A . Running 21.5 A , liquid 480 psig on a 95°F day, condenser packed with palmetto trash. Clean the coil; amps fall to 15.9 A . That was not a leak and not a bad capacitor yet.
VOM (volt-ohm-milliammeter) — volts at the disconnect and contactor, ohms on windings and heater elements (power off, isolated), milliamps on some flame-safety and control loops. A 24-volt thermostat that is actually 19 V under load is a transformer or shorted damper, not a 410A leak. Continuity across a fused disconnect that is off is a dead meter, not a dead compressor. Chapter 30 drills electrical diagnosis; Trade E’s point here is that the VOM and Amprobe sit in the same bag as the gauges so you do not recover a full charge to “check the compressor” when L1 is dark.
Manifold gauges still must be rated for the refrigerant. R-410A high-side hoses and gauges are a different pressure class than R-22. Low-loss fittings and 608 still apply: you are not paid to vent the hose into a Naples driveway.
Florida scenario
Sunset Coast Mechanical, Class B in Lee County, has three no-cools on one 90°F afternoon. Job 1 is a 2-ton 410A that equalizes at 90 psig at 75°F indoor — far below the typical ~218 psig standing saturation (29.1). Nitrogen hold fails; soap bubbles show a cracked flare; electronic detector confirms; halide torch is left on the truck because 410A has no chlorine . Nitrogen retest, 500-micron hold, weigh-in. Job 2 is a 4-ton with a full standing charge, 4°F superheat, and 1,100 cfm on a velometer/free-area calc that wanted 1,600 — Amprobe shows low compressor amps because the coil is iced (low load), not a leak. Job 3 is a 30-ton packaged 410A on a condo roof: same leak method, same oxygen ban, same micron gauge — but 489.105 makes the contract Class A. The Class B candidate still owes the detector theory; the qualifier does not take the job.
Traps: (1) Oxygen or air as the test gas. (2) Halide torch on R-410A. (3) Certifying 500 microns on a compound gauge. (4) Clamping an Amprobe around a whole power whip. (5) Using dye or extra refrigerant as a substitute for repair and 608 recovery. (6) Hunting a leak on a coil that is actually a 280 cfm/ton air problem.