Study guide
26.3 Receivers, Heat Strips, Gas/Oil Appliances & Related Accessories
Florida HVAC Contractor License Class A/B
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 Current Exam Facts & License Classes 1.2 Exam Format, Open-Book Rules & Pearson VUE 1.3 Eligibility, Experience Paths & Financial Responsibility
2 Establishing the Contracting Business
2.1 Business Organizational Structure 2.2 Business Plan, Marketplace & License Scope 2.3 Professionals, Fixed Assets & Bonding
3 Insurance for Florida HVAC Contractors
3.1 Obtaining Insurance (GL, Workers' Compensation & Bonds) 3.2 Coverages, Limits & Policy Language 3.3 Maintaining Insurance & CILB Certificate-Holder Rules
4 Overhead, Staffing & Markets
4.1 Developing the Business, Staffing & Markets 4.2 Determining Business Overhead (FICA, FUTA, SUTA, Workers' Comp, Rent & Utilities) 4.3 Determining Outsourced Services
5 Bids, Proposals & Estimating
5.1 Preparing Bids and Proposals 5.2 AIA Documents, Offers & Contract Components 5.3 Labor Productivity, Overhead & Project Costing
6 Purchasing, Invoices, Draws & Safety Programs
6.1 Purchasing Materials, UCC & Inventory (FIFO) 6.2 Invoices, Draw Requests & Percentage of Completion 6.3 Developing a Safety Program (OSHA, SDS & Drug Testing)
7 Managing Contracts
7.1 Contract Law, Scope & Completion Schedules 7.2 Florida Lien Law Inside Contracting 7.3 Mediation, Arbitration, Tort Law & Risk
8 Managing Trade Operations
8.1 Scheduling Trade Operations (CPM, RFI & Submittals) 8.2 OSHA Records, Document Retainage & Penalties 8.3 Takeoffs, Equipment Lease vs Purchase & Inventory
9 Accounting I: Receivables, Payables & Cash
9.1 Managing Accounts Receivable 9.2 Managing Accounts Payable & Discounts 9.3 Cash Flow, Banking & Financial Ratios
10 Accounting II: Taxes, Job Cost & Payroll
10.1 Filing Tax Forms & Returns 10.2 Tracking Job Costs 10.3 Payroll, Employment Taxes & Garnishments
11 Managing Human Resources
11.1 Hiring, I-9, Background Checks & Discrimination 11.2 HR Policies, OSHA & Drug-Test Chain of Custody 11.3 Evaluating Employees
12 Florida Contractor Law: Chapter 489 & 61G4
12.1 Chapter 489: Certified vs Registered & Qualifying Agents 12.2 61G4 Board Rules, Advertising & Discipline 12.3 Qualifying Agent Duties, Supervision & Additional Entities
13 Florida Construction Lien Law (Chapter 713)
13.1 Construction Lien Overview & Claimants 13.2 Notices to Owner, Time Limits & Perfecting Liens 13.3 Payment Bonds, Waivers & Claims of Lien
14 Financial Responsibility, CE & Federal Rules
14.1 Financial Responsibility & the 660 FICO Rule 14.2 Continuing Education & Biennial Renewal 14.3 Federal Employment, Immigration, OSHA & Environmental Rules
15 Plans, Specs & Equipment Selection
15.1 Reading Plans, Specifications, Symbols & Scales 15.2 Recommending Plan Changes & Equipment Types 15.3 EER, SEER, ARI Listings & Cost Effectiveness
16 Energy Codes, Loads & Thermal Resistance
16.1 Florida Energy Codes, R-Values & U-Factors 16.2 Determining HVAC Heating & Cooling Loads 16.3 Applying Energy Conservation, Fan Curves & Pump Curves
17 HVAC System & Duct Design
17.1 Designing HVAC Systems (Psychrometrics, Enthalpy & Airflow) 17.2 Designing Duct Systems & Insulation 17.3 Selecting Equipment, Location & Codes
18 Piping, Pumps, Boilers, Controls & Rigging Design
18.1 Pipe Sizing, Valves, Fittings, Sealants & Layout 18.2 Control Requirements, Fan Motors, CFM & Compressor Capacity 18.3 Pumps, Boilers, Steam, Fuel & Pipe Insulation 18.4 Grease Ducts, Live Loads, Rigging & Mechanical Equipment
19 Sheet Metal Duct Fabrication
19.1 Fabricating Rectangular & Round Ducts 19.2 Seams, Locks, Taping, Mastics & Liners 19.3 Fittings, Outlets & Grilles 19.4 Kitchen Hoods, Exhausts & Drain Pans
20 Split, Package & Heat Pump Installation
20.1 Installing Split & Package Air Conditioners 20.2 Installing Split & Package Heat Pumps 20.3 Air-Cooled vs Water-Cooled Systems
21 Large Systems, Chillers & Towers
21.1 Installing by Tonnage & Class A vs Class B Limits 21.2 Chilled Water, Water Towers & Secondary Coolant 21.3 Centrifugal, Absorption & Ammonia Systems
22 Refrigeration, Coolers, Ventilation & Controls Install
22.1 Low, Medium & Ultra-Low Temperature Systems & EPA Rules 22.2 Walk-In & Reach-In Coolers 22.3 Ventilation, Exhaust, Makeup Air, Grease Ducts & Kitchen Exhaust 22.4 Geothermal, Pneumatic & DDC Controls, TAB & Smoke Tests
23 Condensers, Compressors & Air Handlers
23.1 Installing Air-Cooled & Water-Cooled Condensers 23.2 Hermetic, Semi-Hermetic & Centrifugal Compressors 23.3 Air Handlers, Evaporators, Heat Exchangers, Receivers & Heat Strips
24 Duct, Fans, Filters & Terminals
24.1 Installing Sheet Metal, Fiberglass & Flexible Duct 24.2 Fans, Blowers, Motors, Grilles, Registers & Fire Dampers 24.3 Filters, Flues, Warm-Air, Gas & Fuel-Oil Appliances
25 Refrigerant Piping & Joining
25.1 Refrigerant Piping, Copper Tubing & Pipe Sizing 25.2 Brazing, Welding, Flaring, Swaging & Soldering 25.3 Steel Pipe, Plastic Pipe, Threading & Oxy-Acetylene 25.4 Hangers, Supports, Horizontally Supported Piping & Pressure Testing
26 Metering Devices & Line Components
26.1 TXVs, Capillary Tubes, Reversing Valves & Metering Devices 26.2 Liquid, Suction & Heat-Pump Dryers, Filters & Oil Traps 26.3 Receivers, Heat Strips, Gas/Oil Appliances & Related Accessories
27 Controls Installation
27.1 Pressure, Temperature, Humidity & Bellows Controls 27.2 Thermostats, Humidistats, Pneumatic & Solid-State Controls 27.3 Transformers, Capacitors, Contactors, Relays & Safety Disconnects 27.4 Defrost Components, Starters, Solenoids & Limit Switches
28 Motors, Wiring & Electrical Installation
28.1 Wiring Single-Phase & Three-Phase Equipment 28.2 Motor Types, Protection, Controllers, Belts & Pulleys 28.3 Geothermal Loops, Surge Protectors, Phase Monitors & Plastic Pipe
29 Diagnostic Analysis: Refrigeration
29.1 Pressure-Enthalpy Diagrams & Operating Pressures 29.2 Air Volumes, Enthalpy, Wet-Bulb & Dry-Bulb 29.3 Leak Detection & Refrigeration Test Instruments
30 Diagnostic Analysis: Electrical & Instruments
30.1 Current Draw, Voltage, Power & Motor Terminals 30.2 Testing Relays, Capacitors, Starters, Transformers & Defrost Stats 30.3 Using Amprobes, Velometers, Pitot Tubes, Manometers & Gauges
31 Recovery, Repair & Calibration
31.1 Nitrogen & Gas Regulators, Recovery & Retrofit 31.2 Repairing Hermetic, Semi-Hermetic, Centrifugal Compressors & Blowers 31.3 Calibrating Thermostats, Pressure Switches & Pneumatic Controls 31.4 Superheat, Safety Cutouts, Defrost Clocks & Freezer Controls
32 Mechanical Service & Cleaning
32.1 Belts, Pulleys, Motor Rotation & Seized Compressors 32.2 Crankcase & Evaporator Pressure Regulators & Unloaders 32.3 Cleaning Towers, Condensers, Foreign Matter & Condensate Drains
33 Jobsite Safety & Equipment
33.1 PPE: Hearing, Head, Eye, Face & Respiratory Protection 33.2 Lockout/Tagout, Warning Signs, Toxic Materials & Ventilation 33.3 Rigging, Hoists, Cranes, Forklifts, Backhoes & Excavation 33.4 Ladders, Scaffolds, Tools & Air Compressors
34 Energy Management
34.1 Envelope, Duct Pressure & Blower-Door Testing 34.2 Efficient Equipment, Zoning, ERVs, Wi-Fi Thermostats & Green Buildings 34.3 Energy Forms, R/U Factors, Window Heat Gain & Florida Load Calcs
35 Indoor Air Quality
35.1 Ventilation, Filtration, Humidity, UV & Air Cleaners 35.2 Contaminants, Source Control, TAB & Human Health Effects
26.3 Receivers, Heat Strips, Gas/Oil Appliances & Related Accessories
Key Takeaways Explain This Topic AI
A liquid receiver sits on the high side after the condenser, stores charge for pump-down, and is commonly kept from filling beyond about 80 percent liquid so vapor space remains. It is not a suction accumulator. Critically charged cap-tube and many residential splits omit the receiver.
Pump-down: close the liquid-line solenoid (or king valve), let the compressor pull refrigerant into the receiver/condenser, and stop on low-pressure control. Do not pump into a completely liquid-full vessel.
1 kW ≈ 3,413 Btu/h, so a 10 kW heat kit is about 34,130 Btu/h. In Climate Zone 2, FBC Energy R403.7.2 forbids electric resistance as primary heat; R403.1.3 limits supplementary strips to compressor shortfall, defrost, or compressor/thermostat failure. Sequencers stage the kW; firestats and airflow proving stay in the circuit.
F.S. 489.105: Class A/B may disconnect and reconnect LP or natural-gas appliance changeouts inside buildings but shall not install gas fuel lines within buildings. Combination gas valves, thermocouples, and listed LP conversion kits are appliance accessories on a legal reconnect — new CSST is not.
Fuel-oil furnace accessories include the nozzle (gph), pump, cad cell, oil filter, and barometric draft regulator on Type L vent. Oil piping/tanks are not an HVAC fuel-line grant the way refrigerant pipe is. Class B heating still caps at 500,000 Btu in any one system.
Last updated: August 2026
26.3 Receivers, Heat Strips, Gas/Oil Appliances & Related Accessories
Chapter 23.3 named receivers versus accumulators and hung heat strips on the air handler. Chapter 24.3 hung air filters, flues, and the F.S. 489.105 gas fence . This section is the remaining Trade D accessory install so those clusters do not leave a gap: how you pipe a receiver for pump-down , the line accessories that travel with it, heat-strip kits as staged electrical accessories , and the gas and oil controls that belong on a legal disconnect/reconnect . Refrigeration & Air Conditioning Technology , 9th Edition (2021), FBC Mechanical 2023 Chapter 11 , FBC Energy Conservation 2023 R403.1.3 / R403.7.2 , NFPA 90B 2024 , and F.S. 489.105 are the spine. Class B still stops at 25 tons / 500,000 Btu in any one system .
Quick Answer: A receiver is high-side liquid storage for pump-down — leave about 20 percent vapor space (do not fill past about 80 percent liquid ). An accumulator is low-side slug protection. Heat strips are supplemental in Climate Zone 2 , staged by a sequencer , about 3,413 Btu/h per kW . HVAC may reconnect a gas or oil appliance , not run new fuel lines inside the building.
Receivers, pump-down, and the line accessories that travel with them
A liquid receiver sits on the high side after the condenser . It stores liquid so the condenser can drain, the charge can grow and shrink with ambient and load, and the system can pump down : a liquid-line solenoid (or the king valve on the receiver outlet) closes, the compressor pulls remaining refrigerant into the receiver and condenser, and the low-pressure control stops the compressor. That is how you change a drier core or a TXV without recovering the whole charge into a cylinder — you still recover if you will open a part that cannot be isolated (EPA 608, Chapter 22.1).
Fill. Leave vapor space . A common exam figure is not more than about 80 percent liquid at the worst high ambient so hydrostatic pressure cannot crush the vessel. Receivers are pressure vessels : relief pipes outdoors per Chapter 11, not into a return plenum. A king valve on the liquid outlet, a sight glass on the receiver or in the liquid line after the drier, and sometimes a level probe are the accessories. Size a pump-down receiver to hold the full charge without backing liquid into the condenser at that 80 percent limit.
Critically charged cap-tube and many residential TXV splits omit the receiver. Adding one without redesigning the charge is how you flood the condenser or starve the TXV. Heat pumps usually run a critical charge plus a suction accumulator , not a receiver — reversing flow would fight a one-way liquid drum.
Section 23.3’s identity table still holds: receiver = high-side liquid storage ; accumulator = low-side suction vessel with a U-tube and oil-return orifice. Swap them and you either slug the compressor or lose pump-down.
Related refrigerant line accessories on this outline:
Accessory Where it goes Job
Liquid-line solenoid Liquid line, often just before the TXV Closes for pump-down ; also used as a refrigerant shutoff on some multi-evaporator racks
Sight glass / moisture indicator Liquid line after the drier Full liquid when running as designed; color says wet or dry
Vibration eliminator Suction and discharge, close to the compressor , in the plane of crankshaft motion Flex so the compressor does not work-harden the copper
- Discharge muffler Hot-gas line Cuts pulsation; not a check valve
- Service / king valves Compressor stubs, receiver outlet Front-seat / back-seat; mid-seat for gauges
Install vibration eliminators parallel to the compressor crankshaft (so they bend with the throw), as close to the stubs as the listing allows, and support the piping beyond them — the hose is not a hanger. Do not use the reversing-valve body or the receiver as a junction to hang a 20-foot riser.
Heat strips as remaining electrical accessories
Chapter 23.3 already put airflow proving , a primary automatic-reset limit , and a manual-reset / fusible firestat in the kit. What still has to land as a Trade D accessory:
Math. 1 kW ≈ 3,413 Btu/h . A 5 kW kit is about 17,065 Btu/h . A 10 kW kit is about 34,130 Btu/h . A 15 kW kit is about 51,195 Btu/h . Those numbers sit well under Class B’s 500,000 Btu heating cap by themselves . A 20-ton package with a 600,000 Btu gas module is still Class A on the heating cap even if the 15 kW strip kit looks small. Count the system heating total.
Sequencers (or an electronic board) stage the elements and often bring the blower on first. Dumping 15 kW on one contactor without time delay is a voltage-flicker and a high-limit problem. Outdoor thermostats (or the heat-pump control) enforce FBC Energy R403.1.3 : supplementary electric heat only when the vapor-compression cycle cannot meet the setpoint, the unit is in defrost , or the compressor or thermostat malfunctions . R403.7.2 still forbids electric resistance as primary heat in Climate Zone 2 (most of Florida). Zone 1A (Miami-Dade through Palm Beach and the southwest Gulf counties listed in the energy code) is the exception on that particular primary-heat item — still do not treat a 10 kW kit as a furnace.
Wiring. Use the air-handler nameplate MCA/MOCP for the configured kit. HVAC may land low-voltage W/E/AUX, sequencers, and dedicated HVAC-circuit repairs with a breaker lock , plus single-phase disconnect reconnects under 489.105 . A new feeder from the service equipment to a new strip disconnect is an electrical contractor . Do not jumper a firestat, and do not land 40 A of strips on a 15 A lighting circuit.
Gas and oil appliance accessories on a legal reconnect
F.S. 489.105(3)(f) and (g): Class A and Class B shall not install LP or natural-gas fuel lines within buildings , except disconnecting or reconnecting changeouts of those appliances. Chapter 24.3 taught the fence, Type B versus Type L vents, and manifold pressures ( about 3.5 in. w.c. natural gas , 10–11 in. w.c. LP ). Remaining accessories on that reconnect:
Gas. The combination gas valve is regulator plus operator in one listed body. A standing pilot uses a thermocouple (about 30 mV hot; dropout commonly near 15 mV or as the valve lists) or a thermopile . Intermittent spark and hot-surface ignition (HSI) use a flame sensor (microamps) instead of a millivolt pile. LP conversion is a listed kit — orifices and regulator spring together — not a field-drilled hole. A sediment trap (drip leg) at the appliance and the appliance shutoff are part of a legal reconnect; extending CSST through the attic is not. Subcontract building fuel pipe to a mechanical or plumbing contractor.
Fuel oil. No. 2 heating oil through a nozzle stamped in gph and spray angle, a high-pressure pump (often about 100 psi at the nozzle — use the listing), a cad cell that sees flame (ohms drop when it sees light), an oil filter , and a barometric draft regulator on the Type L vent connector. HVAC reconnects the existing appliance oil connection the way it reconnects gas — it does not bury a new tank line on the HVAC permit. Type B gas vent on an oil furnace is still wrong (Chapter 24.3).
Worked Class B heat check. An 80,000 Btu/h gas furnace plus a 3-ton coil is inside 500,000 Btu and 25 tons . A 20-ton RTU with 600,000 Btu gas is over the heating cap — Class A — even if someone calls the gas section an accessory. Boilers and unfired pressure vessels remain Class A statutory scope (Chapter 18); this accessory cluster is warm-air appliances.
Florida scenario
Gulf Breeze Comfort, certified Class B in Hillsborough, has three tickets. Ticket 1 is a water-cooled 15-ton package (legal Class B) that needs a receiver , king valve , liquid-line solenoid , and pump-down to change a drier core — relief piped outdoors, receiver not filled as a solid liquid drum. Ticket 2 is a Zone 2A heat-pump AHU with a 10 kW kit: 34,130 Btu/h , sequenced , ODT / R403.1.3 lockout, firestat left in the circuit, existing dedicated single-phase disconnect. Ticket 3 is an 80,000 Btu/h natural-gas furnace changeout: reconnect the union, listed combination valve , verify 3.5 in. w.c. , keep the sediment trap , subcontract the new CSST someone wanted run from the meter. Three different accessories, one license fence. What the qualifier must not do is treat the receiver as an accumulator, run the 10 kW as primary heat all winter, or call new building gas pipe a reconnect.
Traps: (1) Receiver ↔ accumulator. (2) Filling a receiver 100 percent liquid. (3) One-way vibration eliminator used as a hanger. (4) 10 kW as primary heat in Zone 2. (5) New CSST as HVAC work. (6) Field-drilled LP orifices. (7) Type B vent on oil. (8) Class B bidding a 600,000 Btu gas module.