15.3 EER, SEER, ARI Listings & Cost Effectiveness

Florida HVAC Contractor License Class A/B

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 Current Exam Facts & License Classes 1.2 Exam Format, Open-Book Rules & Pearson VUE 1.3 Eligibility, Experience Paths & Financial Responsibility

2 Establishing the Contracting Business

2.1 Business Organizational Structure 2.2 Business Plan, Marketplace & License Scope 2.3 Professionals, Fixed Assets & Bonding

3 Insurance for Florida HVAC Contractors

3.1 Obtaining Insurance (GL, Workers' Compensation & Bonds) 3.2 Coverages, Limits & Policy Language 3.3 Maintaining Insurance & CILB Certificate-Holder Rules

4 Overhead, Staffing & Markets

4.1 Developing the Business, Staffing & Markets 4.2 Determining Business Overhead (FICA, FUTA, SUTA, Workers' Comp, Rent & Utilities) 4.3 Determining Outsourced Services

5 Bids, Proposals & Estimating

5.1 Preparing Bids and Proposals 5.2 AIA Documents, Offers & Contract Components 5.3 Labor Productivity, Overhead & Project Costing

6 Purchasing, Invoices, Draws & Safety Programs

6.1 Purchasing Materials, UCC & Inventory (FIFO) 6.2 Invoices, Draw Requests & Percentage of Completion 6.3 Developing a Safety Program (OSHA, SDS & Drug Testing)

7 Managing Contracts

7.1 Contract Law, Scope & Completion Schedules 7.2 Florida Lien Law Inside Contracting 7.3 Mediation, Arbitration, Tort Law & Risk

8 Managing Trade Operations

8.1 Scheduling Trade Operations (CPM, RFI & Submittals) 8.2 OSHA Records, Document Retainage & Penalties 8.3 Takeoffs, Equipment Lease vs Purchase & Inventory

9 Accounting I: Receivables, Payables & Cash

9.1 Managing Accounts Receivable 9.2 Managing Accounts Payable & Discounts 9.3 Cash Flow, Banking & Financial Ratios

10 Accounting II: Taxes, Job Cost & Payroll

10.1 Filing Tax Forms & Returns 10.2 Tracking Job Costs 10.3 Payroll, Employment Taxes & Garnishments

11 Managing Human Resources

11.1 Hiring, I-9, Background Checks & Discrimination 11.2 HR Policies, OSHA & Drug-Test Chain of Custody 11.3 Evaluating Employees

12 Florida Contractor Law: Chapter 489 & 61G4

12.1 Chapter 489: Certified vs Registered & Qualifying Agents 12.2 61G4 Board Rules, Advertising & Discipline 12.3 Qualifying Agent Duties, Supervision & Additional Entities

13 Florida Construction Lien Law (Chapter 713)

13.1 Construction Lien Overview & Claimants 13.2 Notices to Owner, Time Limits & Perfecting Liens 13.3 Payment Bonds, Waivers & Claims of Lien

14 Financial Responsibility, CE & Federal Rules

14.1 Financial Responsibility & the 660 FICO Rule 14.2 Continuing Education & Biennial Renewal 14.3 Federal Employment, Immigration, OSHA & Environmental Rules

15 Plans, Specs & Equipment Selection

15.1 Reading Plans, Specifications, Symbols & Scales 15.2 Recommending Plan Changes & Equipment Types 15.3 EER, SEER, ARI Listings & Cost Effectiveness

16 Energy Codes, Loads & Thermal Resistance

16.1 Florida Energy Codes, R-Values & U-Factors 16.2 Determining HVAC Heating & Cooling Loads 16.3 Applying Energy Conservation, Fan Curves & Pump Curves

17 HVAC System & Duct Design

17.1 Designing HVAC Systems (Psychrometrics, Enthalpy & Airflow) 17.2 Designing Duct Systems & Insulation 17.3 Selecting Equipment, Location & Codes

18 Piping, Pumps, Boilers, Controls & Rigging Design

18.1 Pipe Sizing, Valves, Fittings, Sealants & Layout 18.2 Control Requirements, Fan Motors, CFM & Compressor Capacity 18.3 Pumps, Boilers, Steam, Fuel & Pipe Insulation 18.4 Grease Ducts, Live Loads, Rigging & Mechanical Equipment

19 Sheet Metal Duct Fabrication

19.1 Fabricating Rectangular & Round Ducts 19.2 Seams, Locks, Taping, Mastics & Liners 19.3 Fittings, Outlets & Grilles 19.4 Kitchen Hoods, Exhausts & Drain Pans

20 Split, Package & Heat Pump Installation

20.1 Installing Split & Package Air Conditioners 20.2 Installing Split & Package Heat Pumps 20.3 Air-Cooled vs Water-Cooled Systems

21 Large Systems, Chillers & Towers

21.1 Installing by Tonnage & Class A vs Class B Limits 21.2 Chilled Water, Water Towers & Secondary Coolant 21.3 Centrifugal, Absorption & Ammonia Systems

22 Refrigeration, Coolers, Ventilation & Controls Install

22.1 Low, Medium & Ultra-Low Temperature Systems & EPA Rules 22.2 Walk-In & Reach-In Coolers 22.3 Ventilation, Exhaust, Makeup Air, Grease Ducts & Kitchen Exhaust 22.4 Geothermal, Pneumatic & DDC Controls, TAB & Smoke Tests

23 Condensers, Compressors & Air Handlers

23.1 Installing Air-Cooled & Water-Cooled Condensers 23.2 Hermetic, Semi-Hermetic & Centrifugal Compressors 23.3 Air Handlers, Evaporators, Heat Exchangers, Receivers & Heat Strips

24 Duct, Fans, Filters & Terminals

24.1 Installing Sheet Metal, Fiberglass & Flexible Duct 24.2 Fans, Blowers, Motors, Grilles, Registers & Fire Dampers 24.3 Filters, Flues, Warm-Air, Gas & Fuel-Oil Appliances

25 Refrigerant Piping & Joining

25.1 Refrigerant Piping, Copper Tubing & Pipe Sizing 25.2 Brazing, Welding, Flaring, Swaging & Soldering 25.3 Steel Pipe, Plastic Pipe, Threading & Oxy-Acetylene 25.4 Hangers, Supports, Horizontally Supported Piping & Pressure Testing

26 Metering Devices & Line Components

26.1 TXVs, Capillary Tubes, Reversing Valves & Metering Devices 26.2 Liquid, Suction & Heat-Pump Dryers, Filters & Oil Traps 26.3 Receivers, Heat Strips, Gas/Oil Appliances & Related Accessories

27 Controls Installation

27.1 Pressure, Temperature, Humidity & Bellows Controls 27.2 Thermostats, Humidistats, Pneumatic & Solid-State Controls 27.3 Transformers, Capacitors, Contactors, Relays & Safety Disconnects 27.4 Defrost Components, Starters, Solenoids & Limit Switches

28 Motors, Wiring & Electrical Installation

28.1 Wiring Single-Phase & Three-Phase Equipment 28.2 Motor Types, Protection, Controllers, Belts & Pulleys 28.3 Geothermal Loops, Surge Protectors, Phase Monitors & Plastic Pipe

29 Diagnostic Analysis: Refrigeration

29.1 Pressure-Enthalpy Diagrams & Operating Pressures 29.2 Air Volumes, Enthalpy, Wet-Bulb & Dry-Bulb 29.3 Leak Detection & Refrigeration Test Instruments

30 Diagnostic Analysis: Electrical & Instruments

30.1 Current Draw, Voltage, Power & Motor Terminals 30.2 Testing Relays, Capacitors, Starters, Transformers & Defrost Stats 30.3 Using Amprobes, Velometers, Pitot Tubes, Manometers & Gauges

31 Recovery, Repair & Calibration

31.1 Nitrogen & Gas Regulators, Recovery & Retrofit 31.2 Repairing Hermetic, Semi-Hermetic, Centrifugal Compressors & Blowers 31.3 Calibrating Thermostats, Pressure Switches & Pneumatic Controls 31.4 Superheat, Safety Cutouts, Defrost Clocks & Freezer Controls

32 Mechanical Service & Cleaning

32.1 Belts, Pulleys, Motor Rotation & Seized Compressors 32.2 Crankcase & Evaporator Pressure Regulators & Unloaders 32.3 Cleaning Towers, Condensers, Foreign Matter & Condensate Drains

33 Jobsite Safety & Equipment

33.1 PPE: Hearing, Head, Eye, Face & Respiratory Protection 33.2 Lockout/Tagout, Warning Signs, Toxic Materials & Ventilation 33.3 Rigging, Hoists, Cranes, Forklifts, Backhoes & Excavation 33.4 Ladders, Scaffolds, Tools & Air Compressors

34 Energy Management

34.1 Envelope, Duct Pressure & Blower-Door Testing 34.2 Efficient Equipment, Zoning, ERVs, Wi-Fi Thermostats & Green Buildings 34.3 Energy Forms, R/U Factors, Window Heat Gain & Florida Load Calcs

35 Indoor Air Quality

35.1 Ventilation, Filtration, Humidity, UV & Air Cleaners 35.2 Contaminants, Source Control, TAB & Human Health Effects

15.3 EER, SEER, ARI Listings & Cost Effectiveness

Key Takeaways Explain This Topic AI

EER is cooling Btu/h divided by watts at a single rating point (AHRI AFull, 95°F outdoor); a 36,000 Btu/h unit drawing 3,000 W has an EER of 12.0 Btu/Wh.

SEER (and SEER2) is seasonal total cooling Btu divided by seasonal watt-hours; SEER2/EER2/HSPF2 come from DOE Appendix M1 / AHRI 210/240 with about 0.5 in. w.g. external static versus about 0.1 in. w.g. on the old test, so the new numbers are lower for the same hardware.

Florida is in DOE's Southeast region: split-system air conditioners under 45,000 Btu/h must be at least 14.3 SEER2; splits 45,000 Btu/h and up must be at least 13.8 SEER2; single-package air conditioners are 13.4 SEER2; split heat pumps are 14.3 SEER2 and 7.5 HSPF2.

AHRI (historically ARI) certified ratings apply only to the listed indoor/outdoor match; FBC Energy R403.7.1.1 says the published AHRI total capacity is nominal and shall not be used for equipment sizing.

The Florida Building Energy-Efficiency Rating Act (F.S. 553.990–553.998) and FBC Energy R401.3's Energy Performance Level display card are how owners see whole-building efficiency; HVAC SEER2 is an input to EnergyGauge-type tools, not a substitute for the rating.

Last updated: August 2026

15.3 EER, SEER, ARI Listings & Cost Effectiveness

Trade Area A also tests whether you can discuss EER and SEER with owners and architects : the calculations, Florida energy codes, the Florida Building Energy Rating System, ARI listings, and cost analysis. The exam references still say ARI because the CILB outline is older than the 2008 merger that created AHRI (Air-Conditioning, Heating, and Refrigeration Institute). On a 2026 job you will pull an AHRI Certificate of Product Ratings from the Directory of Certified Product Performance. The physics did not change; the test procedure and the name did.

Quick Answer: EER (and EER2 ) = cooling Btu/h ÷ watts at 95°F outdoor. SEER (and SEER2 ) = seasonal cooling Btu ÷ seasonal watt-hours. Florida split air conditioners below 45,000 Btu/h must meet 14.3 SEER2 ; 45,000–65,000 Btu/h splits meet 13.8 SEER2 . Ratings count only on the AHRI-matched indoor and outdoor pair.

EER versus SEER — the calculations

Energy Efficiency Ratio (EER) is a steady-state full-load snapshot:

EER = net cooling capacity (Btu/h) total power input (watts) \text{EER} = \dfrac{\text{net cooling capacity (Btu/h)}}{\text{total power input (watts)}} EER = total power input (watts) net cooling capacity (Btu/h) ​

AHRI 210/240 publishes that snapshot at AFull conditions: 95°F outdoor dry-bulb, indoor air about 80°F dry-bulb / 67°F wet-bulb (50 percent relative humidity at that dry-bulb). EER2 is the same ratio under the newer Appendix M1 test (higher external static). EER is the number that matters at 2 p.m. in July in Tampa, when the machine is sitting on the 95°F point for hours. Window units and many commercial full-load tables are still discussed in EER; Florida owners in hot-humid climates should hear both EER2 and SEER2, not SEER2 alone.

Worked EER: expanded or test data show 36,000 Btu/h net cooling at 95°F while the unit draws 3,000 watts (compressor + condenser fan + indoor blower as the test includes them).

36,000 / 3,000 = 12.0 EER 36{,}000 / 3{,}000 = 12.0 \text{ EER} 36 , 000/3 , 000 = 12.0 EER

Because 1 watt is 3.412 Btu/h , that EER of 12 is a COP of 12 / 3.412 ≈ 3.52 12 / 3.412 \approx 3.52 12/3.412 ≈ 3.52 .

Seasonal Energy Efficiency Ratio (SEER) is not one afternoon:

SEER = total cooling delivered over a cooling season (Btu) total electrical energy over that season (watt-hours) \text{SEER} = \dfrac{\text{total cooling delivered over a cooling season (Btu)}}{\text{total electrical energy over that season (watt-hours)}} SEER = total electrical energy over that season (watt-hours) total cooling delivered over a cooling season (Btu) ​

AHRI 210/240 and DOE Appendix M build SEER from a set of indoor/outdoor tests and a climate-weighted bin model (part load, cycling, and for two-stage/variable units the intermediate ratings). SEER2 is that seasonal number under Appendix M1. You cannot convert a field-measured EER into a legal SEER2 with a napkin factor and stamp a permit. A rule of thumb sometimes seen in older shops (EER ≈ 0.875 × SEER) is not a compliance calculation and is not how AHRI lists equipment.

HSPF2 (Heating Seasonal Performance Factor 2) is the heat-pump heating analog of SEER2, Btu of heat per watt-hour over a heating season, reported for Region IV in the AHRI certificate.

SEER2 / EER2: what actually changed in 2023

On January 1, 2023, DOE's Appendix M1 (10 CFR 430 Subpart B) replaced Appendix M for rating residential central air conditioners and heat pumps. AHRI 210/240 was aligned to that procedure. The headline change: external static pressure used in the test rose from about 0.1 in. w.g. to about 0.5 in. w.g. (up to five times, depending on capacity), closer to real ductwork. Coil, fan, and cycling details also moved. The same hardware therefore prints a lower SEER2 than its old SEER. Nothing “got worse”; the ruler got stricter. Do not tell an owner that a 14.3 SEER2 unit is less efficient than last decade's 15 SEER — 14.3 SEER2 in the Southeast was set as the successor to a 15 SEER regional minimum.

  • Metric What it measures Typical test cue Where you use it
  • EER Full-load Btu/h per watt 95°F outdoor, ~80/67 indoor Peak-day conversation; many commercial tables

EER2 Same ratio, M1 static AHRI 210/240 AFull under Appendix M1 Current certificates; Southwest also has regional EER2 floors

  • SEER Seasonal Btu per Wh Appendix M bins, ~0.1 in. w.g. ESP Pre-2023 equipment and older literature
  • SEER2 Seasonal Btu per Wh Appendix M1, ~0.5 in. w.g. ESP Current residential <65,000 Btu/h splits and packages

IEER Integrated part-load, commercial AHRI 340/360 for ≥65,000 Btu/h Rooftops and split commercial above the SEER2 range

HSPF2 Seasonal heating Btu per Wh Appendix M1 heating bins Heat pumps

AHRI 210/240 covers factory-made unitary AC and air-source heat pumps below 65,000 Btu/h . At 65,000 Btu/h and above , you are in AHRI 340/360 (and IEER/EER language in FBC Energy commercial tables). That 65,000 Btu/h line is 5.4 tons — still inside Class B's 25-ton cap, but the rating standard has already changed.

Florida energy-code and federal minimums

FBC Energy R403.7.1: new or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed . Florida is in DOE's Southeast region (10 CFR 430.32). Effective January 1, 2023, those residential central air-conditioner installation regional standards (single-phase, <65,000 Btu/h) include:

  • Split-system air conditioners < 45,000 Btu/h: 14.3 SEER2
  • Split-system air conditioners ≥ 45,000 Btu/h: 13.8 SEER2

Single-package air conditioners: 13.4 SEER2 (national package floor; Southeast does not add a higher SEER2 package number the way it does for splits)

  • Split-system heat pumps: 14.3 SEER2 and 7.5 HSPF2 (national heat-pump standard)
  • Single-package heat pumps: 13.4 SEER2 and 6.7 HSPF2

A 3.5-ton (42,000 Btu/h) split AC and a 4-ton (48,000 Btu/h) split AC therefore sit on different SEER2 floors . That is an exam trap and a counter trap. FBC Energy 2023 commercial Table C403.2.3(1) (electrically operated unitary air conditioners) prints the same post-1/1/2023 SEER2 figures for three-phase and non-U.S. single-phase products in the <45,000 and 45,000–65,000 rows (14.3 and 13.8 SEER2 for splits; 13.4 SEER2 for single package), tested to AHRI 210/240. Larger commercial equipment in that table moves to EER/IEER under AHRI 340/360. Do not use the 9th Edition (2026) FBC Energy numbers on this exam — the 2026 Air Conditioning reference list is the 2023 Energy Conservation volume.

ARI / AHRI listings

Certified ratings live in the AHRI Directory of Certified Product Performance . The downloadable Certificate of Product Ratings lists the outdoor model, indoor model (coil or air handler), optional furnace as indoor section, SEER2 , EER2 (AFull) , cooling capacity at AFull, and HSPF2 for heat pumps, with an AHRI reference number. Only that combination is certified. Mixing a 3-ton condensing unit with a 4-ton indoor coil from a different family, or with a furnace that is not on the matchup sheet, voids the listed SEER2 . Energy code, ENERGY STAR, and many rebate programs want that certificate in the permit packet. FBC Energy R403.7.1.1 separately warns you: the AHRI total capacity on that certificate is still a nominal rating-test value — use expanded performance data at design temperatures for Manual S sizing.

Florida Building Energy Rating System and cost effectiveness

The Florida Building Energy-Efficiency Rating Act , F.S. 553.990–553.998 , creates a statewide uniform building energy-efficiency rating (not a second SEER sticker). Ratings must account for climate, construction practice, and building use, stay compatible with federal rating systems and the Florida Building Code, and provide a way to compare buildings at sale. F.S. 553.996 requires that a prospective purchaser be notified, at or before contract, of the option to obtain an energy-efficiency rating. FBC Energy R401.3 (mandatory) requires an Energy Performance Level (EPL) display card , certified by the builder, before final approval; F.S. 553.9085 requires that EPL card as an addendum to the sales contract for new residential buildings. Commission-approved software (historically EnergyGauge and other approved tools) produces residential performance-path and Energy Rating Index compliance; HVAC efficiency is one input among envelope, ducts, and water heating. When you talk to an architect about “the rating,” you are talking about that whole-building number, not the condensing-unit carton.

Cost analysis the exam expects is simple and honest. Seasonal kWh for a given cooling load scales inversely with SEER2 :

kWh ≈ capacity (Btu/h) × equivalent full-load hours SEER2 × 1,000 \text{kWh} \approx \dfrac{\text{capacity (Btu/h)} \times \text{equivalent full-load hours}}{\text{SEER2} \times 1{,}000} kWh ≈ SEER2 × 1 , 000 capacity (Btu/h) × equivalent full-load hours ​

Illustration only, not a utility tariff: a 36,000 Btu/h system with 2,000 equivalent full-load hours uses about 5,035 kWh at 14.3 SEER2 and about 4,500 kWh at 16.0 SEER2 — roughly 535 kWh saved. At a sample $0.14/kWh , that is about $75 per year . If the 16.0 SEER2 match costs $900 more installed, simple payback is about 12 years , before maintenance, duct leakage, or a time-of-use rate. A leaky attic duct or an unmatched coil can erase that $75. The cost-effective recommendation is often code-minimum or modestly above-minimum equipment plus a duct and envelope that EnergyGauge can see , not a 20 SEER2 outdoor unit on a 0.1-inch-static fantasy and a dirty filter.

Florida HVAC scenario

An Orlando (Climate Zone 2) owner wants to reuse a pre-2023 “14 SEER” 3-ton condensing unit from the shop loft with a new 3.5-ton indoor coil “because it will be more efficient.” Three failures: (1) Southeast installation of a split AC under 45,000 Btu/h now requires 14.3 SEER2 on a certified match , not a leftover 14 SEER carton; (2) the mixed coil is not an AHRI listed combination , so you have no SEER2 to put on the EPL card or the energy calculation; (3) even if a listed 3.5-ton match existed, R403.7.1.1 still forbids sizing from the AHRI nominal column — Manual J might be 28,000 Btu/h, and a 3.5-ton expanded-data total could blow the 1.15 cap and the latent problem. The conversation with the architect is: listed 14.3 SEER2 (or better) match, expanded-data capacity inside 1.15, ducts that make the M1 static look realistic, and an EnergyGauge/EPL package that reflects what will actually be installed.

DOE 2023 cooling minimums (SEER2) that apply in Florida