Study guide
22.1 Low, Medium & Ultra-Low Temperature Systems & EPA Rules
Florida HVAC Contractor License Class A/B
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 Current Exam Facts & License Classes 1.2 Exam Format, Open-Book Rules & Pearson VUE 1.3 Eligibility, Experience Paths & Financial Responsibility
2 Establishing the Contracting Business
2.1 Business Organizational Structure 2.2 Business Plan, Marketplace & License Scope 2.3 Professionals, Fixed Assets & Bonding
3 Insurance for Florida HVAC Contractors
3.1 Obtaining Insurance (GL, Workers' Compensation & Bonds) 3.2 Coverages, Limits & Policy Language 3.3 Maintaining Insurance & CILB Certificate-Holder Rules
4 Overhead, Staffing & Markets
4.1 Developing the Business, Staffing & Markets 4.2 Determining Business Overhead (FICA, FUTA, SUTA, Workers' Comp, Rent & Utilities) 4.3 Determining Outsourced Services
5 Bids, Proposals & Estimating
5.1 Preparing Bids and Proposals 5.2 AIA Documents, Offers & Contract Components 5.3 Labor Productivity, Overhead & Project Costing
6 Purchasing, Invoices, Draws & Safety Programs
6.1 Purchasing Materials, UCC & Inventory (FIFO) 6.2 Invoices, Draw Requests & Percentage of Completion 6.3 Developing a Safety Program (OSHA, SDS & Drug Testing)
7 Managing Contracts
7.1 Contract Law, Scope & Completion Schedules 7.2 Florida Lien Law Inside Contracting 7.3 Mediation, Arbitration, Tort Law & Risk
8 Managing Trade Operations
8.1 Scheduling Trade Operations (CPM, RFI & Submittals) 8.2 OSHA Records, Document Retainage & Penalties 8.3 Takeoffs, Equipment Lease vs Purchase & Inventory
9 Accounting I: Receivables, Payables & Cash
9.1 Managing Accounts Receivable 9.2 Managing Accounts Payable & Discounts 9.3 Cash Flow, Banking & Financial Ratios
10 Accounting II: Taxes, Job Cost & Payroll
10.1 Filing Tax Forms & Returns 10.2 Tracking Job Costs 10.3 Payroll, Employment Taxes & Garnishments
11 Managing Human Resources
11.1 Hiring, I-9, Background Checks & Discrimination 11.2 HR Policies, OSHA & Drug-Test Chain of Custody 11.3 Evaluating Employees
12 Florida Contractor Law: Chapter 489 & 61G4
12.1 Chapter 489: Certified vs Registered & Qualifying Agents 12.2 61G4 Board Rules, Advertising & Discipline 12.3 Qualifying Agent Duties, Supervision & Additional Entities
13 Florida Construction Lien Law (Chapter 713)
13.1 Construction Lien Overview & Claimants 13.2 Notices to Owner, Time Limits & Perfecting Liens 13.3 Payment Bonds, Waivers & Claims of Lien
14 Financial Responsibility, CE & Federal Rules
14.1 Financial Responsibility & the 660 FICO Rule 14.2 Continuing Education & Biennial Renewal 14.3 Federal Employment, Immigration, OSHA & Environmental Rules
15 Plans, Specs & Equipment Selection
15.1 Reading Plans, Specifications, Symbols & Scales 15.2 Recommending Plan Changes & Equipment Types 15.3 EER, SEER, ARI Listings & Cost Effectiveness
16 Energy Codes, Loads & Thermal Resistance
16.1 Florida Energy Codes, R-Values & U-Factors 16.2 Determining HVAC Heating & Cooling Loads 16.3 Applying Energy Conservation, Fan Curves & Pump Curves
17 HVAC System & Duct Design
17.1 Designing HVAC Systems (Psychrometrics, Enthalpy & Airflow) 17.2 Designing Duct Systems & Insulation 17.3 Selecting Equipment, Location & Codes
18 Piping, Pumps, Boilers, Controls & Rigging Design
18.1 Pipe Sizing, Valves, Fittings, Sealants & Layout 18.2 Control Requirements, Fan Motors, CFM & Compressor Capacity 18.3 Pumps, Boilers, Steam, Fuel & Pipe Insulation 18.4 Grease Ducts, Live Loads, Rigging & Mechanical Equipment
19 Sheet Metal Duct Fabrication
19.1 Fabricating Rectangular & Round Ducts 19.2 Seams, Locks, Taping, Mastics & Liners 19.3 Fittings, Outlets & Grilles 19.4 Kitchen Hoods, Exhausts & Drain Pans
20 Split, Package & Heat Pump Installation
20.1 Installing Split & Package Air Conditioners 20.2 Installing Split & Package Heat Pumps 20.3 Air-Cooled vs Water-Cooled Systems
21 Large Systems, Chillers & Towers
21.1 Installing by Tonnage & Class A vs Class B Limits 21.2 Chilled Water, Water Towers & Secondary Coolant 21.3 Centrifugal, Absorption & Ammonia Systems
22 Refrigeration, Coolers, Ventilation & Controls Install
22.1 Low, Medium & Ultra-Low Temperature Systems & EPA Rules 22.2 Walk-In & Reach-In Coolers 22.3 Ventilation, Exhaust, Makeup Air, Grease Ducts & Kitchen Exhaust 22.4 Geothermal, Pneumatic & DDC Controls, TAB & Smoke Tests
23 Condensers, Compressors & Air Handlers
23.1 Installing Air-Cooled & Water-Cooled Condensers 23.2 Hermetic, Semi-Hermetic & Centrifugal Compressors 23.3 Air Handlers, Evaporators, Heat Exchangers, Receivers & Heat Strips
24 Duct, Fans, Filters & Terminals
24.1 Installing Sheet Metal, Fiberglass & Flexible Duct 24.2 Fans, Blowers, Motors, Grilles, Registers & Fire Dampers 24.3 Filters, Flues, Warm-Air, Gas & Fuel-Oil Appliances
25 Refrigerant Piping & Joining
25.1 Refrigerant Piping, Copper Tubing & Pipe Sizing 25.2 Brazing, Welding, Flaring, Swaging & Soldering 25.3 Steel Pipe, Plastic Pipe, Threading & Oxy-Acetylene 25.4 Hangers, Supports, Horizontally Supported Piping & Pressure Testing
26 Metering Devices & Line Components
26.1 TXVs, Capillary Tubes, Reversing Valves & Metering Devices 26.2 Liquid, Suction & Heat-Pump Dryers, Filters & Oil Traps 26.3 Receivers, Heat Strips, Gas/Oil Appliances & Related Accessories
27 Controls Installation
27.1 Pressure, Temperature, Humidity & Bellows Controls 27.2 Thermostats, Humidistats, Pneumatic & Solid-State Controls 27.3 Transformers, Capacitors, Contactors, Relays & Safety Disconnects 27.4 Defrost Components, Starters, Solenoids & Limit Switches
28 Motors, Wiring & Electrical Installation
28.1 Wiring Single-Phase & Three-Phase Equipment 28.2 Motor Types, Protection, Controllers, Belts & Pulleys 28.3 Geothermal Loops, Surge Protectors, Phase Monitors & Plastic Pipe
29 Diagnostic Analysis: Refrigeration
29.1 Pressure-Enthalpy Diagrams & Operating Pressures 29.2 Air Volumes, Enthalpy, Wet-Bulb & Dry-Bulb 29.3 Leak Detection & Refrigeration Test Instruments
30 Diagnostic Analysis: Electrical & Instruments
30.1 Current Draw, Voltage, Power & Motor Terminals 30.2 Testing Relays, Capacitors, Starters, Transformers & Defrost Stats 30.3 Using Amprobes, Velometers, Pitot Tubes, Manometers & Gauges
31 Recovery, Repair & Calibration
31.1 Nitrogen & Gas Regulators, Recovery & Retrofit 31.2 Repairing Hermetic, Semi-Hermetic, Centrifugal Compressors & Blowers 31.3 Calibrating Thermostats, Pressure Switches & Pneumatic Controls 31.4 Superheat, Safety Cutouts, Defrost Clocks & Freezer Controls
32 Mechanical Service & Cleaning
32.1 Belts, Pulleys, Motor Rotation & Seized Compressors 32.2 Crankcase & Evaporator Pressure Regulators & Unloaders 32.3 Cleaning Towers, Condensers, Foreign Matter & Condensate Drains
33 Jobsite Safety & Equipment
33.1 PPE: Hearing, Head, Eye, Face & Respiratory Protection 33.2 Lockout/Tagout, Warning Signs, Toxic Materials & Ventilation 33.3 Rigging, Hoists, Cranes, Forklifts, Backhoes & Excavation 33.4 Ladders, Scaffolds, Tools & Air Compressors
34 Energy Management
34.1 Envelope, Duct Pressure & Blower-Door Testing 34.2 Efficient Equipment, Zoning, ERVs, Wi-Fi Thermostats & Green Buildings 34.3 Energy Forms, R/U Factors, Window Heat Gain & Florida Load Calcs
35 Indoor Air Quality
35.1 Ventilation, Filtration, Humidity, UV & Air Cleaners 35.2 Contaminants, Source Control, TAB & Human Health Effects
22.1 Low, Medium & Ultra-Low Temperature Systems & EPA Rules
Key Takeaways Explain This Topic AI
EPA Section 608 (40 CFR 82 Subpart F) prohibits knowingly venting ODS refrigerants and most HFC substitutes; recover with certified equipment before opening a circuit. Federal 608 technician certification does not replace a CILB Class A or Class B license.
Type I covers small appliances of 5 pounds or less; Type II covers medium-, high- and very-high-pressure appliances; Type III covers low-pressure appliances; Universal covers all three.
Leak-repair trigger rates are 10 percent for comfort cooling, 20 percent for commercial refrigeration, and 30 percent for industrial process refrigeration (12-month leak rate), for ozone-depleting appliances of 50 pounds or more and, since 2026, HFC appliances of 15 pounds or more.
Medium-temperature boxes typically sit near 35–40°F with evaporators around 20–25°F SST; low-temperature freezers sit near 0 to −10°F with evaporators around −20°F SST; ultra-low work uses compound (same refrigerant, two stages) or cascade (two circuits) — true cryogenics are a different plant.
Ammonia (R-717) engine rooms are a Class A Trade C industrial item taught in Section 21.3 against FBC Mechanical Chapter 11 and IIAR 2; do not treat a supermarket HFC rack as an ammonia plant.
Last updated: October 2026
22.1 Low, Medium & Ultra-Low Temperature Systems & EPA Rules
Trade Area C (Installation of Refrigeration and HVAC Systems) is 23 percent of the Class A trade exam and 22 percent of Class B . After packaged splits, heat pumps, and the large-plant cluster in Chapter 21, the outline turns to low- and medium-temperature refrigeration, ultra-low (multistage and cryogenic) systems, and the EPA Section 608 overlay that sits on every refrigerant circuit. The 2026 Air Conditioning CBT books that carry this cluster are Refrigeration & Air Conditioning Technology , 9th Edition (2021), and Florida Building Code — Mechanical, 2023 Chapter 11. F.S. 489.105 still decides who may contract the plant. Ammonia (R-717) machinery rooms were covered as a Class A industrial item in Section 21.3 ; this section cross-references that room and spends its pages on the HFC/HCFC/blend racks a Florida HVAC contractor actually hangs in restaurants, stores, and process boxes.
Quick Answer: Recover before you open a circuit; venting is prohibited . A 608 card is federal and does not replace a CILB Class A or B license. Medium temp is a cooler; low temp is a freezer; ultra-low is compound or cascade . Leak-repair triggers on 50-pound-and-up charges are 10 / 20 / 30 percent (comfort / commercial refrigeration / industrial process).
Why temperature class is not “colder air conditioning”
Comfort cooling evaporators run near 40–50°F saturated suction temperature ( SST ) to put 55°F supply air into a 75°F room. A medium-temperature cooler is a food box , not a 55°F air handler. The box sits near 35–40°F (meat, dairy, produce); the evaporator SST is commonly 20–25°F so the coil is 10–20°F colder than the air. A low-temperature freezer box sits near 0 to −10°F ; SST is often near −20°F . Ultra-low work (ice-cream hardening, blast freezers, some biomedical boxes) drives SST to −40°F and below . At those suction temperatures a single-stage compressor’s compression ratio (absolute discharge pressure divided by absolute suction pressure) climbs, discharge temperature climbs, oil cokes, and volumetric efficiency collapses. That is why the outline splits low/medium from ultra-low / multistage / cryogenics .
Worked SST check. A Tampa walk-in cooler is specified 38°F box, 10°F coil-to-air difference: SST ≈ 28°F . That is medium temperature . A 0°F ice-cream cabinet with a 10°F difference wants SST ≈ −10°F — already low temperature , and it needs electric or hot-gas defrost , not off-cycle air defrost (Section 22.2). An −80°F cascade box is ultra-low . Treating all three as “just a colder rooftop” fails the cluster.
- Service Typical box / space Typical evaporator SST Plant style
- High-temp / comfort AC 72–78°F room 40–50°F Single-stage DX or chiller
- Medium-temp cooler 35–40°F 20–25°F Single-stage DX, walk-in or reach-in
- Low-temp freezer 0 to −10°F about −20°F Single-stage or two-stage DX; mandatory defrost
- Ultra-low −40°F and below far below −40°F Compound (same refrigerant) or cascade (two circuits)
- Cryogenic often below −150°F not ordinary SST Liquid nitrogen or specialized cascade — not a stretched walk-in
Capacity is still 12,000 Btu/h per ton , but the expanded-data table is read at the actual SST and SDT , not at an air-conditioning rating point (Chapter 21.1). An “8-ton” condensing unit selected at 20°F SST / 105°F SDT for a Florida cooler will not make 8 tons at −20°F SST . Class B’s 25-ton / 500,000 Btu cap (F.S. 489.105(3)(g) ) still applies to any one system . A 20-ton medium-temp rack with its own circuit is Class B work; a 40-ton supermarket rack on one circuit is Class A .
Ultra-low: compound, cascade, and what “cryogenic” actually means
A compound (two-stage, same-refrigerant) system takes vapor from the low-stage suction, compresses it to an intermediate pressure, cools it in a flash intercooler or desuperheater, then a high-stage compressor takes it to condensing pressure. One refrigerant, two compression ratios instead of one brutal ratio. That is the usual answer when the outline says multistage .
A cascade system is two independent circuits coupled by a cascade heat exchanger : the low-stage condenser is cooled by the high-stage evaporator . The low-stage refrigerant (historically something like an ultra-low blend) never sees the outdoor condenser. Cascade is how you get −80°F without asking one compressor to eat a 20-to-1 ratio.
Cryogenics on this outline is the next step down: temperatures where ordinary vapor-compression stops being the right tool and liquid nitrogen or a purpose-built cascade/auto-cascade appears. Do not call a −10°F walk-in freezer cryogenic. Do not bid a nitrogen freezer as if it were an R-404A walk-in.
Oil return, suction-line P-traps , and double suction risers get worse as SST drops (Section 22.2). Ammonia plants that make those temperatures in a food plant live in an engine room (Section 21.3) — they are not an HFC cascade in a restaurant mezzanine.
Refrigerants: CFCs, HCFCs, HFCs, blends, recovery, retrofit
Class I ozone-depleting substances are CFCs (R-12, R-11, R-502 as a CFC blend family). Class II are HCFCs (R-22, R-123). HFCs (R-134a, R-404A, R-410A, R-507) have no ozone-depletion number that matters here but are high global-warming-potential gases under the AIM Act phasedown — teach the phasedown exists ; do not invent a GWP table the open-book list does not print. HFO and HFO/HFC blends are the SNAP-listed replacements arriving on new equipment. Zeotropic blends (the 400 series) have temperature glide ; charge them as liquid . Azeotropes (500 series) behave like a single substance.
SNAP (Significant New Alternatives Policy) is EPA’s list of which substitutes are acceptable in which end-use. A retrofit is not “put 404A in a 22 system and hope.” Oil change (mineral to POE), expansion-device resize, pressure-control reset, and a listed retrofit procedure belong on the ticket. Recover the old charge; do not mix it into the new cylinder.
Recover means pull refrigerant into an external cylinder with certified recovery equipment. Recycle means clean it on the truck (oil separation, filter-drier) for return to the same owner’s equipment. Reclaim means a certified reclaimer processes it to AHRI 700 virgin specs. You may return recovered refrigerant to the appliance it came from, or to another appliance the same person owns, without reclaiming — you may not sell it as new.
EPA Section 608 — federal, and it does not replace CILB
Section 608 of the Clean Air Act, implemented at 40 CFR Part 82, Subpart F , is the National Recycling and Emission Reduction Program. Knowingly venting ozone-depleting refrigerants or most substitute refrigerants (including HFCs, since January 1, 2018) while maintaining, servicing, repairing, or disposing of appliances is prohibited . De minimis releases that happen during a good-faith recovery are the exception, not a loophole for “I cracked the high-side valve to check for liquid.” Nitrogen used as a holding charge or leak-test gas is not a refrigerant — but you still recover the refrigerant first . Never use the refrigerant itself as a blow-down gas.
Before opening an appliance (except the small-appliance rules below), evacuate the charge — the whole appliance, or an isolated portion that can be pumped into a receiver — to the Table 1 vacuum with certified recovery/recycling equipment, and verify the vacuum before you crack a fitting.
EPA has four technician certifications. You must hold the type that matches the appliance:
Type I — small appliances ( 5 pounds or less of refrigerant): domestic refrigerators, window units, small vending.
Type II — medium-, high- and very-high-pressure appliances except small appliances and MVAC (Section 609 is cars).
Type III — low-pressure appliances (R-11 / R-123 family centrifugal chillers).
Universal — Type I + II + III.
That card is federal . It is not a Florida contractor license. F.S. 489.105 still wants Class A or Class B (or a mechanical contractor) to contract the work. A helper with Universal 608 and no CILB qualifier is not a legal contractor. A Class A qualifier whose techs are not 608-certified still cannot legally open the circuit.
Small-appliance recovery (Type I): with recovery equipment manufactured on or after November 15, 1993, recover 90 percent if the compressor runs, 80 percent if it does not — or pull 4 inches of mercury vacuum. System-dependent (passive) recovery may not be used on appliances with a full charge of more than 15 pounds unless it is a permanently attached pump-out unit.
Required evacuation levels for everything except small appliances, MVACs, and MVAC-like appliances, using recovery equipment manufactured on or after November 15, 1993 :
- Appliance (EPA 40 CFR 82.156 Table 1) Vacuum to reach before opening
- Very high-pressure 0 in. Hg (0 psig)
- High-pressure, full charge < 200 lb 0 in. Hg
- High-pressure, full charge ≥ 200 lb 10 in. Hg
- Medium-pressure, full charge < 200 lb 10 in. Hg
- Medium-pressure, full charge ≥ 200 lb 15 in. Hg
- Low-pressure 25 mm Hg absolute
If leaks make the table vacuum unattainable, isolate leaking from non-leaking parts, pull the table vacuum on the tight part, and pull the leaking part to the lowest level you can without contaminating the recovered refrigerant , not higher than 0 psig .
Leak repair (40 CFR 82.157, ozone-depleting appliances with a full charge of 50 pounds or more ): the 12-month leak-rate trigger is 10 percent for comfort cooling , 20 percent for commercial refrigeration (food retail, cold storage), and 30 percent for industrial process refrigeration . Since January 1, 2026, 40 CFR 84.106 applies the same leak rates to appliances with 15 pounds or more of HFC refrigerant (GWP above 53), except residential and light commercial air conditioning and heat pumps. Below those charge sizes the leak-repair programs do not attach, but venting is still illegal and recovery is still required . Do not quote the retired 35/15 percent pair as current law.
Florida scenario
Gulfshore Mechanical holds a certified Class B license in Collier County. A grocer wants a new 18-ton medium-temperature rack (R-448A blend, ~38°F cases) and a 8-ton low-temperature rack (0°F well cases) as two independent refrigerant circuits , plus an −80°F cascade ice-cream hardening box in the back room. The 18-ton and 8-ton racks are each under 25 tons and under 500,000 Btu heat, so Class B may contract them if they are truly separate systems. The technicians who open those circuits need Type II or Universal 608 . They recover to the Table 1 vacuum (this is high-pressure commercial refrigeration; if a rack holds 200 pounds or more , that is a 10 in. Hg pull on post-1993 equipment, not a “until the gauge looks low” pull). The −80°F cascade is ultra-low: two circuits, cascade heat exchanger, not a stretched walk-in. If that cascade is still under 25 tons as its own system, Class B may install the hardware ; the physics is still a cascade question. If the grocer instead wants a 40-ton single rack feeding the whole store, that is Class A . If the grocer wants ammonia , that is Section 21.3 and not this HFC rack. Venting the old R-22 into the alley “because it is already leaking” is a 608 violation even when the leak-repair percentage program does not attach because the charge is under 50 pounds.
Traps: (1) Treating 608 as a substitute for CILB. (2) Calling a 0°F freezer cryogenic . (3) Charging a 400-series blend as vapor. (4) Using the comfort-cooling 10 percent leak trigger on a supermarket rack (that is 20 percent ; an HFC rack of 15 lb+ is covered under 40 CFR 84.106 since 2026). (5) Opening a 250-pound high-pressure receiver after pulling “a little vacuum” instead of 10 in. Hg . (6) Mixing recovered R-22 into a 448A cylinder as a “retrofit.”