Study guide

1.4 HVACR Mathematics, Unit Conversions, and Efficiency Ratings

HVAC Excellence Certification Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Introduction, Safety, Tools, and Diagnostic Method

1.1 HVAC Excellence Certification, Industry Codes, and Standards 1.2 Electrical Safety, PPE, Lockout/Tagout, and Hazard Communication 1.3 Multimeters, Manifold Gauges, Micron Gauges, and Diagnostic Instruments 1.4 HVACR Mathematics, Unit Conversions, and Efficiency Ratings 1.5 OSHA Standards, Fall Protection, Rigging, and Confined Spaces 1.6 HVACR Industry Organizations, Energy Resources, and Building Energy Programs 1.7 Systematic Troubleshooting: Data Plates, Manufacturer Literature, and Diagnostic Method

2 Chapter 2: Electrical Fundamentals and Circuit Theory

2.1 Voltage, Current, Resistance, and Ohm's Law Calculations 2.2 Series, Parallel, and Series-Parallel Circuits and Power Calculations 2.3 AC Fundamentals, Single-Phase vs Three-Phase Power, and Control Transformers 2.4 Conductors, Insulators, Wire Sizing, Voltage Drop, and NEC Ampacity

3 Chapter 3: Electrical Components, Motors, and Schematics

3.1 Contactors, Relays, Switches, Overload Protection, and Thermostats 3.2 HVAC Motors (PSC, CSIR, CSCR, ECM, 3-Phase) and Run/Start Capacitors 3.3 Interpreting Ladder Diagrams, Schematics, and Point-to-Point Wiring 3.4 Motor Testing, Insulation Resistance, Bearings, and Belt Drives

4 Chapter 4: Thermodynamics and the Refrigeration Cycle

4.1 Heat Transfer, Temperature Scales, BTUs, Sensible vs Latent Heat, and Enthalpy 4.2 The Four Vapor-Compression Cycle Stages (Compression, Condensation, Expansion, Evaporation) 4.3 P-T Charts, Saturated Conditions, Target Superheat, and Subcooling Calculations 4.4 Pressure–Enthalpy Diagrams, Compression Ratio, and Cycle Analysis

5 Chapter 5: Refrigerants, Environmental Regulations, and Recovery

5.1 Refrigerant Types (CFC, HCFC, HFC, HFO, HC) and ASHRAE Safety Groups (A1, A2L, A3) 5.2 EPA Section 608 Regulations, Venting Prohibitions, and Evacuation Standards 5.3 Recovery/Recycling/Reclaiming Equipment, Procedures, and Leak Detection 5.4 Refrigerant Retrofits, Cylinder Handling, and Refrigerant Purity 5.5 A2L and Low-GWP Refrigerants: Codes, Charge Limits, and Service Practice

6 Chapter 6: Refrigeration System Components and Accessories

6.1 Compressor Mechanics (Reciprocating, Scroll, Rotary, Screw) and Failures 6.2 Expansion Devices (TXV/TEV, Fixed Orifice, EEV) and Superheat Control 6.3 Condensers, Evaporators, Filter-Driers, Accumulators, Receivers, and Solenoids 6.4 Pressure Controls, Capacity Controls, and System Protection 6.5 Refrigerant Line Sizing, Pressure Drop, Brazing, and Piping Practice

7 Chapter 7: Gas Heating, Combustion Analysis, and Fuel Piping

7.1 Combustion Theory, Fuel Gases (Natural Gas vs LP), and Gas Burners 7.2 Gas Valves, Ignition Systems (Standing Pilot, Spark, HSI), and Safety Limit Controls 7.3 Flue Venting, Draft Principles, Combustion Analysis, and CO Safety 7.4 Fuel-Gas and Oil Piping, Vent System Selection and Sizing, and Installation Practice

8 Chapter 8: Electric Heating, Oil Heat, and Hydronics

8.1 Electric Heating Elements, Sequencers, Limit Switches, and kW Calculations 8.2 Oil Burners, Fuel Pumps, Nozzles, Ignition Electrodes, and Primary Controls 8.3 Hydronic Boilers, Circulator Pumps, Expansion Tanks, and Zone Controls 8.4 Combustion Air, Water Heaters, and Combustion Appliance Zone Testing

9 Chapter 9: Heat Pumps and Dual-Fuel Systems

9.1 Heat Pump Operation in Heating/Cooling Modes and Reversing Valve Operation 9.2 Defrost Controls (Time-Temperature, Demand Defrost), Sensors, and Sequences 9.3 Balance Points, Auxiliary/Emergency Heat, and Dual-Fuel (Hybrid) Systems 9.4 Heat Pump Diagnostics, Refrigerant Flow, and Troubleshooting Procedures 9.5 Heat Pump Types, Cold-Climate Performance, and Sizing Approaches

10 Chapter 10: Air Distribution, IAQ, and System Commissioning

10.1 Airflow Fundamentals, CFM Measurement, External Static Pressure, and Fan Laws 10.2 Duct Sizing Principles, Supply/Return Distribution, Dampers, and Air Balancing 10.3 Indoor Air Quality, MERV Ratings, Electronic Cleaners, Humidification, and Dehumidification 10.4 Deep Vacuum Evacuation (Micron Gauge), Subcooling/Superheat Charging, and System Commissioning 10.5 Duct Leakage, Blower Door Testing, and Building Envelope Performance

11 Chapter 11: Psychrometrics, Airside Calculations, and Load Estimation

11.1 Reading the Psychrometric Chart: Properties and Plotting 11.2 The Eight Air-Conditioning Processes and the Process Triangle 11.3 Mixed Air, Ventilation, and Infiltration Calculations 11.4 Residential Heat Loss, Heat Gain, and Equipment Sizing

12 Chapter 12: Light Commercial Air Conditioning

12.1 Packaged Rooftop and Split Light-Commercial Systems 12.2 Water-Cooled Condensers, Cooling Towers, and Chilled-Water Systems 12.3 Economizers, Demand-Controlled Ventilation, and VAV Air Distribution 12.4 Light-Commercial Start-Up, Commissioning, and Troubleshooting

13 Chapter 13: Light Commercial Refrigeration

13.1 Temperature Ranges, Box Loads, and Refrigeration System Types 13.2 Evaporators, Defrost Methods, and Defrost Controls 13.3 Condensing Units, Parallel Racks, Oil Management, and Capacity Control 13.4 Refrigeration Control Valves and Automatic Pump-Down 13.5 Commercial Refrigeration Diagnostics and Ice Machines

14 Chapter 14: Ductless, Mini-Split, and VRF Systems

14.1 Mini-Split Architecture and Inverter-Driven Compressors 14.2 Multi-Zone and VRF Operation, Electronic Expansion Valves, and Controls 14.3 Ductless Installation, Evacuation, Charging, and Diagnostics

15 Chapter 15: Building Automation and Digital Controls

15.1 DDC Fundamentals, Control Loops, and Sequences of Operation 15.2 BAS Networks, Protocols, and NEC-Compliant Cabling 15.3 Building Automation Controllers: Supervisory, Field, and Room Devices 15.4 Digital Logic, Numbering Systems, and Controller Programming 15.5 Sensor Selection, Installation, and Input Point Configuration 15.6 Actuators, Output Devices, and VFD Integration 15.7 Commercial Prints, Equipment Schedules, and BAS Documentation

1.4 HVACR Mathematics, Unit Conversions, and Efficiency Ratings

Key Takeaways Explain This Topic AI

Ohm's Law, the sensible heat formula, and area/volume math are all tested as applied arithmetic: the exam gives you a field scenario and expects one number back.

One ton of refrigeration equals 12,000 BTU/hr, derived from the 288,000 BTU required to melt one ton of ice over 24 hours.

SEER2, EER2, and HSPF2 replaced SEER, EER, and HSPF in 2023 because AHRI 210/240 raised the external static pressure test condition from roughly 0.10-0.20 in. w.c. to 0.50 in. w.c.

AFUE measures seasonal fuel-burning efficiency as a percentage; COP is a dimensionless ratio of heat moved to energy consumed, and a COP of 3.0 equals roughly 10.2 BTU/watt-hour.

Life-cycle cost analysis compares first cost plus lifetime energy, maintenance, and replacement cost, which is why a higher-SEER2 unit can win on total cost while losing on purchase price.

Last updated: August 2026

1.4 HVACR Mathematics, Unit Conversions, and Efficiency Ratings

The first sheet of the HVAC Excellence Competency and Task List is General Studies , and it opens with mathematics. That placement is deliberate: almost every technical competency later in the list resolves into a calculation. Sizing a duct, verifying a charge, checking a temperature rise, or proving a compressor is pumping all end with a number that either falls inside the manufacturer's window or does not. The exam does not test mathematics abstractly — it embeds it inside field scenarios.

1. The Arithmetic the Task List Actually Names

The task list requires proficiency in decimals, fractions, negative numbers, squares, cubes, roots, ratios, proportions, basic equations, and conversion between English (inch-pound) and metric (SI) measurement.

Fractions and Decimals in Tubing and Sheet Metal Work

Refrigerant tubing is sold in fractional outside diameters (1/4", 3/8", 1/2", 5/8", 7/8", 1-1/8"). Manometers and static pressure readings are decimal (0.35 in. w.c.). You will constantly move between the two.

Fraction to decimal: divide numerator by denominator. 7 / 8 = 0.875 7/8 = 0.875 7/8 = 0.875 .

Decimal to fraction (to the nearest 1/16): multiply by 16 and round. 0.44 × 16 = 7.04 → 7 / 16 0.44 \times 16 = 7.04 \rightarrow 7/16 0.44 × 16 = 7.04 → 7/16 .

Adding fractions requires a common denominator: a run of 3 1 2 3\tfrac{1}{2} 3 2 1 ​ " plus 2 3 4 2\tfrac{3}{4} 2 4 3 ​ " equals 3 2 4 + 2 3 4 = 5 5 4 = 6 1 4 3\tfrac{2}{4} + 2\tfrac{3}{4} = 5\tfrac{5}{4} = 6\tfrac{1}{4} 3 4 2 ​ + 2 4 3 ​ = 5 4 5 ​ = 6 4 1 ​ inches.

Negative Numbers and Delta-T

Δ T \Delta T Δ T ("delta T") is simply the difference between two temperatures, and the task list calls it out by name. Sign matters when one temperature is below zero.

Evaporator entering air 75 ∘ F 75^\circ\text{F} 7 5 ∘ F , leaving air 56 ∘ F 56^\circ\text{F} 5 6 ∘ F : Δ T = 75 − 56 = 19 ∘ F \Delta T = 75 - 56 = 19^\circ\text{F} Δ T = 75 − 56 = 1 9 ∘ F (a normal residential temperature split).

Walk-in freezer box air − 10 ∘ F -10^\circ\text{F} − 1 0 ∘ F , coil saturation − 20 ∘ F -20^\circ\text{F} − 2 0 ∘ F : Δ T = − 10 − ( − 20 ) = 10 ∘ F \Delta T = -10 - (-20) = 10^\circ\text{F} Δ T = − 10 − ( − 20 ) = 1 0 ∘ F TD across the coil.

Area and Volume

Rectangular duct area (sq ft) = width (in) × height (in) 144 = \dfrac{\text{width (in)} \times \text{height (in)}}{144} = 144 width (in) × height (in) ​ . A 20" × 8" duct is 160 ÷ 144 = 1.11 sq ft 160 \div 144 = 1.11\text{ sq ft} 160 ÷ 144 = 1.11 sq ft .

Round duct area (sq ft) = π r 2 144 = \dfrac{\pi r^2}{144} = 144 π r 2 ​ . A 10" round duct has r = 5 r = 5 r = 5 ", so area = ( 3.1416 × 25 ) ÷ 144 = 0.545 sq ft = (3.1416 \times 25) \div 144 = 0.545\text{ sq ft} = ( 3.1416 × 25 ) ÷ 144 = 0.545 sq ft .

Box or room volume = L × W × H = L \times W \times H = L × W × H . A walk-in 12 ′ × 10 ′ × 8 ′ 12' \times 10' \times 8' 1 2 ′ × 1 0 ′ × 8 ′ holds 960 ft 3 960\text{ ft}^3 960 ft 3 — the starting number for infiltration load and for blower-door conditioned-volume math.

Velocity, area, and CFM tie together: CFM = Velocity (FPM) × Area (sq ft) \text{CFM} = \text{Velocity (FPM)} \times \text{Area (sq ft)} CFM = Velocity (FPM) × Area (sq ft) . At 900 FPM through the 1.11 sq ft duct above, CFM = 900 × 1.11 = 999 CFM \text{CFM} = 900 \times 1.11 = 999\text{ CFM} CFM = 900 × 1.11 = 999 CFM .

Ratios and Proportions

The task list specifically asks you to manipulate ratios for compressors, pumps, drives, and fans. The pulley (sheave) proportion is the classic: Driven RPM Driver RPM = Driver diameter Driven diameter \frac{\text{Driven RPM}}{\text{Driver RPM}} = \frac{\text{Driver diameter}}{\text{Driven diameter}} Driver RPM Driven RPM ​ = Driven diameter Driver diameter ​

A 1725 RPM motor with a 4" sheave driving a 10" blower sheave turns the blower at 1725 × ( 4 / 10 ) = 690 RPM 1725 \times (4/10) = 690\text{ RPM} 1725 × ( 4/10 ) = 690 RPM . Opening an adjustable motor sheave makes it functionally smaller, which lowers blower RPM and airflow — a fact that trips up candidates every year.

2. Unit Conversions You Must Know Cold

Quantity Conversion

Temperature ∘ F = ( ∘ C × 1.8 ) + 32 ^\circ F = (^\circ C \times 1.8) + 32 ∘ F = ( ∘ C × 1.8 ) + 32 ; ∘ C = ( ∘ F − 32 ) ÷ 1.8 ^\circ C = (^\circ F - 32) \div 1.8 ∘ C = ( ∘ F − 32 ) ÷ 1.8

Absolute temperature ∘ R = ∘ F + 460 ^\circ R = ^\circ F + 460 ∘ R = ∘ F + 460 ; K = ∘ C + 273 \text{K} = ^\circ C + 273 K = ∘ C + 273

  • Refrigeration capacity 1 ton = 12,000 BTU/hr = 200 BTU/min
  • Electrical heat 1 kW = 3,412 BTU/hr ; 1 W = 3.412 BTU/hr
  • Horsepower 1 HP = 746 W = 2,545 BTU/hr
  • Pressure 1 psi = 2.036 in. Hg = 27.7 in. w.c.; 1 atm = 14.696 psia = 29.92 in. Hg
  • Vacuum 1 in. Hg = 25.4 mm Hg = 25,400 microns; 1 mm Hg (torr) = 1,000 microns
  • Length / volume 1 in = 25.4 mm; 1 gal = 3.785 L = 231 in³

Where the ton comes from: melting one ton (2,000 lb) of ice absorbs 2,000 × 144 BTU/lb = 288,000 BTU 2{,}000 \times 144\text{ BTU/lb} = 288{,}000\text{ BTU} 2 , 000 × 144 BTU/lb = 288 , 000 BTU (144 BTU/lb is the latent heat of fusion of water). Spread over 24 hours that is 288,000 ÷ 24 = 12,000 BTU/hr 288{,}000 \div 24 = 12{,}000\text{ BTU/hr} 288 , 000 ÷ 24 = 12 , 000 BTU/hr . Reconstructing the derivation is safer than memorizing it, because the exam sometimes asks for the 288,000 figure directly.

3. Efficiency Ratings and the Acronyms on the Task List

The General Studies sheet lists a specific block of acronyms you are expected to define. They fall into three families.

Cooling and heat pump ratings

  • Rating What it measures Units
  • EER / EER2 Steady-state cooling efficiency at one rating condition BTU/hr per watt
  • SEER / SEER2 Seasonal cooling efficiency across a range of outdoor temperatures BTU/hr per watt
  • HSPF / HSPF2 Seasonal heating efficiency of a heat pump over a heating season BTU/hr per watt
  • COP Heat moved divided by energy consumed, same units top and bottom dimensionless
  • IEER Part-load weighted efficiency for larger commercial equipment BTU/hr per watt

The "2" ratings arrived in 2023 with the revised AHRI Standard 210/240 M1 test procedure , which raised the external static pressure used during testing from roughly 0.10–0.20 in. w.c. to 0.50 in. w.c. The equipment did not get worse; the test got more realistic, so a 14 SEER unit re-rated at roughly 13.4 SEER2. Because COP is dimensionless, converting from an EER-style rating requires dividing out the BTU-per-watt-hour constant: COP = EER ÷ 3.412 \text{COP} = \text{EER} \div 3.412 COP = EER ÷ 3.412 . A heat pump with a COP of 3.0 is delivering about 10.2 BTU per watt-hour.

Fuel-burning ratings

AFUE (Annual Fuel Utilization Efficiency) is a percentage of fuel energy converted to usable heat over a heating season, including cycling and off-cycle losses. It is not the same number a combustion analyzer reports: a combustion analyzer computes steady-state efficiency , which is always higher than AFUE for the same appliance. A furnace at 82% steady-state may carry an 80% AFUE label.

Buildings, energy, and cost

BIM — Building Information Modeling. CBECS — Commercial Buildings Energy Consumption Survey. EIA — Energy Information Administration. ECM — in this context, Energy Conservation Measure (the same three letters also mean Electronically Commutated Motor; the task list contains both, and context decides).

USGBC / LEED and GBI / Green Globes are the two major green-building rating programs. DOE is the U.S. Department of Energy, which sets minimum equipment efficiency standards.

Renewable vs. sustainable: renewable energy replenishes on a human timescale (solar, wind, geothermal, biomass). Sustainable practice meets present needs without compromising future supply — a broader idea that includes efficiency and material choice, not just the fuel source.

Life-cycle cost analysis (LCCA) totals first cost, installation, energy over the expected service life, maintenance, and disposal or replacement. It is the argument a technician uses to justify a higher-efficiency unit: a $1,200 price premium that saves $300 per year in energy pays back in four years and then earns for the remaining life of the equipment.