12.2 Water-Cooled Condensers, Cooling Towers, and Chilled-Water Systems
HVAC Excellence Certification Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Introduction, Safety, Tools, and Diagnostic Method
1.1 HVAC Excellence Certification, Industry Codes, and Standards 1.2 Electrical Safety, PPE, Lockout/Tagout, and Hazard Communication 1.3 Multimeters, Manifold Gauges, Micron Gauges, and Diagnostic Instruments 1.4 HVACR Mathematics, Unit Conversions, and Efficiency Ratings 1.5 OSHA Standards, Fall Protection, Rigging, and Confined Spaces 1.6 HVACR Industry Organizations, Energy Resources, and Building Energy Programs 1.7 Systematic Troubleshooting: Data Plates, Manufacturer Literature, and Diagnostic Method
2 Chapter 2: Electrical Fundamentals and Circuit Theory
2.1 Voltage, Current, Resistance, and Ohm's Law Calculations 2.2 Series, Parallel, and Series-Parallel Circuits and Power Calculations 2.3 AC Fundamentals, Single-Phase vs Three-Phase Power, and Control Transformers 2.4 Conductors, Insulators, Wire Sizing, Voltage Drop, and NEC Ampacity
3 Chapter 3: Electrical Components, Motors, and Schematics
3.1 Contactors, Relays, Switches, Overload Protection, and Thermostats 3.2 HVAC Motors (PSC, CSIR, CSCR, ECM, 3-Phase) and Run/Start Capacitors 3.3 Interpreting Ladder Diagrams, Schematics, and Point-to-Point Wiring 3.4 Motor Testing, Insulation Resistance, Bearings, and Belt Drives
4 Chapter 4: Thermodynamics and the Refrigeration Cycle
4.1 Heat Transfer, Temperature Scales, BTUs, Sensible vs Latent Heat, and Enthalpy 4.2 The Four Vapor-Compression Cycle Stages (Compression, Condensation, Expansion, Evaporation) 4.3 P-T Charts, Saturated Conditions, Target Superheat, and Subcooling Calculations 4.4 Pressure–Enthalpy Diagrams, Compression Ratio, and Cycle Analysis
5 Chapter 5: Refrigerants, Environmental Regulations, and Recovery
5.1 Refrigerant Types (CFC, HCFC, HFC, HFO, HC) and ASHRAE Safety Groups (A1, A2L, A3) 5.2 EPA Section 608 Regulations, Venting Prohibitions, and Evacuation Standards 5.3 Recovery/Recycling/Reclaiming Equipment, Procedures, and Leak Detection 5.4 Refrigerant Retrofits, Cylinder Handling, and Refrigerant Purity 5.5 A2L and Low-GWP Refrigerants: Codes, Charge Limits, and Service Practice
6 Chapter 6: Refrigeration System Components and Accessories
6.1 Compressor Mechanics (Reciprocating, Scroll, Rotary, Screw) and Failures 6.2 Expansion Devices (TXV/TEV, Fixed Orifice, EEV) and Superheat Control 6.3 Condensers, Evaporators, Filter-Driers, Accumulators, Receivers, and Solenoids 6.4 Pressure Controls, Capacity Controls, and System Protection 6.5 Refrigerant Line Sizing, Pressure Drop, Brazing, and Piping Practice
7 Chapter 7: Gas Heating, Combustion Analysis, and Fuel Piping
7.1 Combustion Theory, Fuel Gases (Natural Gas vs LP), and Gas Burners 7.2 Gas Valves, Ignition Systems (Standing Pilot, Spark, HSI), and Safety Limit Controls 7.3 Flue Venting, Draft Principles, Combustion Analysis, and CO Safety 7.4 Fuel-Gas and Oil Piping, Vent System Selection and Sizing, and Installation Practice
8 Chapter 8: Electric Heating, Oil Heat, and Hydronics
8.1 Electric Heating Elements, Sequencers, Limit Switches, and kW Calculations 8.2 Oil Burners, Fuel Pumps, Nozzles, Ignition Electrodes, and Primary Controls 8.3 Hydronic Boilers, Circulator Pumps, Expansion Tanks, and Zone Controls 8.4 Combustion Air, Water Heaters, and Combustion Appliance Zone Testing
9 Chapter 9: Heat Pumps and Dual-Fuel Systems
9.1 Heat Pump Operation in Heating/Cooling Modes and Reversing Valve Operation 9.2 Defrost Controls (Time-Temperature, Demand Defrost), Sensors, and Sequences 9.3 Balance Points, Auxiliary/Emergency Heat, and Dual-Fuel (Hybrid) Systems 9.4 Heat Pump Diagnostics, Refrigerant Flow, and Troubleshooting Procedures 9.5 Heat Pump Types, Cold-Climate Performance, and Sizing Approaches
10 Chapter 10: Air Distribution, IAQ, and System Commissioning
10.1 Airflow Fundamentals, CFM Measurement, External Static Pressure, and Fan Laws 10.2 Duct Sizing Principles, Supply/Return Distribution, Dampers, and Air Balancing 10.3 Indoor Air Quality, MERV Ratings, Electronic Cleaners, Humidification, and Dehumidification 10.4 Deep Vacuum Evacuation (Micron Gauge), Subcooling/Superheat Charging, and System Commissioning 10.5 Duct Leakage, Blower Door Testing, and Building Envelope Performance
11 Chapter 11: Psychrometrics, Airside Calculations, and Load Estimation
11.1 Reading the Psychrometric Chart: Properties and Plotting 11.2 The Eight Air-Conditioning Processes and the Process Triangle 11.3 Mixed Air, Ventilation, and Infiltration Calculations 11.4 Residential Heat Loss, Heat Gain, and Equipment Sizing
12 Chapter 12: Light Commercial Air Conditioning
12.1 Packaged Rooftop and Split Light-Commercial Systems 12.2 Water-Cooled Condensers, Cooling Towers, and Chilled-Water Systems 12.3 Economizers, Demand-Controlled Ventilation, and VAV Air Distribution 12.4 Light-Commercial Start-Up, Commissioning, and Troubleshooting
13 Chapter 13: Light Commercial Refrigeration
13.1 Temperature Ranges, Box Loads, and Refrigeration System Types 13.2 Evaporators, Defrost Methods, and Defrost Controls 13.3 Condensing Units, Parallel Racks, Oil Management, and Capacity Control 13.4 Refrigeration Control Valves and Automatic Pump-Down 13.5 Commercial Refrigeration Diagnostics and Ice Machines
14 Chapter 14: Ductless, Mini-Split, and VRF Systems
14.1 Mini-Split Architecture and Inverter-Driven Compressors 14.2 Multi-Zone and VRF Operation, Electronic Expansion Valves, and Controls 14.3 Ductless Installation, Evacuation, Charging, and Diagnostics
15 Chapter 15: Building Automation and Digital Controls
15.1 DDC Fundamentals, Control Loops, and Sequences of Operation 15.2 BAS Networks, Protocols, and NEC-Compliant Cabling 15.3 Building Automation Controllers: Supervisory, Field, and Room Devices 15.4 Digital Logic, Numbering Systems, and Controller Programming 15.5 Sensor Selection, Installation, and Input Point Configuration 15.6 Actuators, Output Devices, and VFD Integration 15.7 Commercial Prints, Equipment Schedules, and BAS Documentation
12.2 Water-Cooled Condensers, Cooling Towers, and Chilled-Water Systems
Key Takeaways Explain This Topic AI
A water-cooled condenser rejects heat to water rather than air, and a water regulating valve modulates flow to maintain the target condensing pressure.
A cooling tower rejects heat by evaporating roughly 1% of the circulating water for every 10 degrees Fahrenheit of range, and its performance is limited by the outdoor wet-bulb temperature.
Tower approach is condenser water leaving temperature minus outdoor wet bulb, and range is entering minus leaving water temperature.
Blowdown or bleed removes concentrated dissolved solids; cycles of concentration equal makeup water divided by blowdown, and inadequate blowdown causes scale.
A flooded chiller evaporator holds liquid refrigerant around water tubes and uses a float or orifice metering device rather than a thermostatic expansion valve.
Last updated: August 2026
12.2 Water-Cooled Condensers, Cooling Towers, and Chilled-Water Systems
The Commercial Air Conditioning sheet names "condensers water cooled," "installing a water cooled system and adjusting a water regulating valve," "describing a chilled water system and its operation," "describing cooling towers and their operating limitations," and "describing the operation and function of a flooded evaporator and its metering device." Water is a far better heat-transfer medium than air, and once a building is large enough, rejecting heat to water becomes the efficient choice.
1. Water-Cooled Condensers
Type Construction Application
Tube-in-tube (double pipe) One tube inside another; refrigerant in the annulus, water in the inner tube, counterflow Small systems, ice machines, self-contained units
Shell-and-coil A coiled tube inside a shell Small to medium
Shell-and-tube A bundle of straight tubes inside a cylindrical shell, with removable heads for mechanical cleaning Medium to large; the standard for chillers
Why water wins. Water's specific heat is about 1.0 BTU/lb·°F versus air's 0.24, and its density is roughly 800 times greater. A water-cooled condenser can hold condensing temperature within about 10°F of the entering water , while an air-cooled condenser typically runs 20–30°F above ambient . Lower condensing temperature means lower compression ratio, higher capacity, and lower power draw.
The heat-rejection equation for water: Q = 500 × GPM × Δ T Q = 500 \times \text{GPM} \times \Delta T Q = 500 × GPM × Δ T
where 500 = 8.33 lb/gal × 60 min/hr × 1.0 BTU/lb·°F. A condenser circulating 30 GPM with a 10°F rise rejects 500 × 30 × 10 = 150,000 BTU/hr 500 \times 30 \times 10 = 150{,}000\text{ BTU/hr} 500 × 30 × 10 = 150 , 000 BTU/hr .
Rule of thumb: about 3 GPM per ton of cooling for a cooling-tower condenser water loop, producing a 10°F range.
The water regulating valve
A water regulating valve (sometimes called a head pressure control valve) is a pressure-actuated valve in the condenser water line. It senses discharge pressure through a capillary and modulates water flow to hold condensing pressure at setpoint.
Rising head pressure opens the valve, admitting more water.
Falling head pressure closes it, conserving water and preventing the head from dropping too low to feed the metering device.
On city-water (once-through) systems it also conserves water, which is the reason many jurisdictions now prohibit once-through cooling entirely.
Adjustment: run the system at steady load, then turn the adjusting stem until discharge pressure stabilizes at the manufacturer's target condensing temperature — commonly about 105°F saturated for a tower system.
Failure signs: a valve stuck closed produces high head and eventual high-pressure trips; stuck open produces low head, low capacity, and possible TXV starving in cool weather.
2. Cooling Towers
A cooling tower rejects building heat to the atmosphere by evaporating a small fraction of the circulating water . Evaporating one pound of water absorbs roughly 1,000 BTU , which is why a tower can reject enormous heat with modest water flow.
Types
Induced draft, counterflow — fan at the top pulls air up through falling water; the most common package tower.
Induced draft, crossflow — air moves horizontally across falling water; lower fan power, easier access.
Forced draft — fan at the base pushes air through; more prone to recirculation of saturated discharge air.
Closed-circuit (fluid cooler) — the building loop stays inside a coil while spray water evaporates over it; keeps the building loop clean at the cost of a higher approach.
Performance metrics
- Term Definition Typical value
- Range Entering water temperature − leaving water temperature 10°F
- Approach Leaving water temperature − outdoor wet-bulb temperature 7–10°F
- Design condition e.g. 95°F in, 85°F out, 78°F wet bulb Range 10, approach 7
Wet bulb, not dry bulb, is the limit. Because the process is evaporative, the theoretical minimum water temperature is the outdoor wet-bulb temperature (the same physics as Process 7 in Section 11.2). A tower can never produce water colder than the ambient wet bulb, and a real tower approaches it by 7–10°F. This is the single most important operating limitation on the exam: on a humid day with a 78°F wet bulb, an 85°F leaving-water design is achievable; a 70°F leaving-water expectation is physically impossible.
A rising approach is the classic tower fault. If leaving water temperature climbs while wet bulb stays the same, the tower is losing capacity: scaled or clogged fill, plugged spray nozzles, low water flow, a slipping or reversed fan, restricted air inlet louvers, or discharge air recirculating back into the inlet.
Water losses and treatment
- Loss Mechanism Magnitude
- Evaporation The cooling process itself ≈ 1% of flow per 10°F of range
- Drift Water droplets carried out in the airstream 0.005–0.2% (drift eliminators minimize it)
- Blowdown (bleed) Deliberate discharge of concentrated water Set by water chemistry
Evaporation removes pure water and leaves dissolved minerals behind, so the remaining water concentrates. Cycles of concentration = makeup ÷ blowdown. Without adequate blowdown, calcium carbonate scale forms on the condenser tubes and the fill, and heat transfer collapses.
Treatment addresses four problems: scale (hardness), corrosion (dissolved oxygen and low pH), biological growth , and suspended solids. Legionella is the safety-critical one: warm, nutrient-rich, aerosolized tower water is a proven transmission route, which is why ASHRAE Standard 188 requires a written water management plan for building water systems including cooling towers, and why drift eliminators, biocide programs, and regular cleaning are not optional.
Freeze protection in cold climates: a basin heater, an indoor sump or remote sump, bypass piping around the fill, and variable-speed or cycling fan control to prevent overcooling.
3. Chilled-Water Systems
Instead of moving refrigerant to the load, a chilled-water system moves water and keeps the refrigerant in a machine room.
Components: the chiller (evaporator, compressor, condenser), chilled-water pumps , an expansion tank , an air separator , air-handling units or fan coils with chilled-water coils and control valves, and a cooling tower with condenser-water pumps on water-cooled machines.
Typical design: 44°F supply, 54°F return — a 10°F ΔT. Flow follows the same equation: GPM = Q 500 × Δ T \text{GPM} = \frac{Q}{500 \times \Delta T} GPM = 500 × Δ T Q
A 100-ton load (1,200,000 BTU/hr) at 10°F ΔT requires 1,200,000 ÷ ( 500 × 10 ) = 240 GPM 1{,}200{,}000 \div (500 \times 10) = 240\text{ GPM} 1 , 200 , 000 ÷ ( 500 × 10 ) = 240 GPM , which is the origin of the 2.4 GPM per ton rule of thumb for chilled water.
Low delta-T syndrome is the classic chilled-water plant complaint: return water comes back too cold, so the plant must circulate excess flow to meet the load, wasting pump energy. Causes include coil control valves stuck open, three-way valves bypassing, fouled coils, improper coil selection, and uncontrolled bypasses.
Flooded evaporators
Large chillers use a flooded evaporator : refrigerant fills the shell and water flows through the tubes , with the tube bundle submerged in boiling liquid refrigerant. Advantages are excellent heat transfer (the tubes are wetted continuously) and a very small temperature difference between refrigerant and water.
A flooded evaporator does not use a TXV. Because the shell is deliberately full of liquid, there is no superheat at the outlet for a TXV to sense. Metering is by:
Low-side float valve — maintains a liquid level in the evaporator; opens as level falls.
High-side float valve — maintains a level in the condenser and passes everything else downstream.
Fixed orifice plates — common on modern centrifugal machines.
Because there is no superheat, a flooded evaporator requires a suction line accumulator or an eliminator section in the shell to prevent liquid carryover to the compressor.
Freeze protection is critical. Water in the tubes at 44°F is only 12°F from freezing. Chillers carry a low chilled-water temperature cutout , a flow switch proving water flow before the compressor can start, and interlocks with the pump starter. The Type III EPA rules in Section 5.2 exist for exactly this reason: pulling a low-pressure chiller into a deep vacuum with no water flowing will freeze and split the tubes.