11.2 The Eight Air-Conditioning Processes and the Process Triangle
HVAC Excellence Certification Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Introduction, Safety, Tools, and Diagnostic Method
1.1 HVAC Excellence Certification, Industry Codes, and Standards 1.2 Electrical Safety, PPE, Lockout/Tagout, and Hazard Communication 1.3 Multimeters, Manifold Gauges, Micron Gauges, and Diagnostic Instruments 1.4 HVACR Mathematics, Unit Conversions, and Efficiency Ratings 1.5 OSHA Standards, Fall Protection, Rigging, and Confined Spaces 1.6 HVACR Industry Organizations, Energy Resources, and Building Energy Programs 1.7 Systematic Troubleshooting: Data Plates, Manufacturer Literature, and Diagnostic Method
2 Chapter 2: Electrical Fundamentals and Circuit Theory
2.1 Voltage, Current, Resistance, and Ohm's Law Calculations 2.2 Series, Parallel, and Series-Parallel Circuits and Power Calculations 2.3 AC Fundamentals, Single-Phase vs Three-Phase Power, and Control Transformers 2.4 Conductors, Insulators, Wire Sizing, Voltage Drop, and NEC Ampacity
3 Chapter 3: Electrical Components, Motors, and Schematics
3.1 Contactors, Relays, Switches, Overload Protection, and Thermostats 3.2 HVAC Motors (PSC, CSIR, CSCR, ECM, 3-Phase) and Run/Start Capacitors 3.3 Interpreting Ladder Diagrams, Schematics, and Point-to-Point Wiring 3.4 Motor Testing, Insulation Resistance, Bearings, and Belt Drives
4 Chapter 4: Thermodynamics and the Refrigeration Cycle
4.1 Heat Transfer, Temperature Scales, BTUs, Sensible vs Latent Heat, and Enthalpy 4.2 The Four Vapor-Compression Cycle Stages (Compression, Condensation, Expansion, Evaporation) 4.3 P-T Charts, Saturated Conditions, Target Superheat, and Subcooling Calculations 4.4 Pressure–Enthalpy Diagrams, Compression Ratio, and Cycle Analysis
5 Chapter 5: Refrigerants, Environmental Regulations, and Recovery
5.1 Refrigerant Types (CFC, HCFC, HFC, HFO, HC) and ASHRAE Safety Groups (A1, A2L, A3) 5.2 EPA Section 608 Regulations, Venting Prohibitions, and Evacuation Standards 5.3 Recovery/Recycling/Reclaiming Equipment, Procedures, and Leak Detection 5.4 Refrigerant Retrofits, Cylinder Handling, and Refrigerant Purity 5.5 A2L and Low-GWP Refrigerants: Codes, Charge Limits, and Service Practice
6 Chapter 6: Refrigeration System Components and Accessories
6.1 Compressor Mechanics (Reciprocating, Scroll, Rotary, Screw) and Failures 6.2 Expansion Devices (TXV/TEV, Fixed Orifice, EEV) and Superheat Control 6.3 Condensers, Evaporators, Filter-Driers, Accumulators, Receivers, and Solenoids 6.4 Pressure Controls, Capacity Controls, and System Protection 6.5 Refrigerant Line Sizing, Pressure Drop, Brazing, and Piping Practice
7 Chapter 7: Gas Heating, Combustion Analysis, and Fuel Piping
7.1 Combustion Theory, Fuel Gases (Natural Gas vs LP), and Gas Burners 7.2 Gas Valves, Ignition Systems (Standing Pilot, Spark, HSI), and Safety Limit Controls 7.3 Flue Venting, Draft Principles, Combustion Analysis, and CO Safety 7.4 Fuel-Gas and Oil Piping, Vent System Selection and Sizing, and Installation Practice
8 Chapter 8: Electric Heating, Oil Heat, and Hydronics
8.1 Electric Heating Elements, Sequencers, Limit Switches, and kW Calculations 8.2 Oil Burners, Fuel Pumps, Nozzles, Ignition Electrodes, and Primary Controls 8.3 Hydronic Boilers, Circulator Pumps, Expansion Tanks, and Zone Controls 8.4 Combustion Air, Water Heaters, and Combustion Appliance Zone Testing
9 Chapter 9: Heat Pumps and Dual-Fuel Systems
9.1 Heat Pump Operation in Heating/Cooling Modes and Reversing Valve Operation 9.2 Defrost Controls (Time-Temperature, Demand Defrost), Sensors, and Sequences 9.3 Balance Points, Auxiliary/Emergency Heat, and Dual-Fuel (Hybrid) Systems 9.4 Heat Pump Diagnostics, Refrigerant Flow, and Troubleshooting Procedures 9.5 Heat Pump Types, Cold-Climate Performance, and Sizing Approaches
10 Chapter 10: Air Distribution, IAQ, and System Commissioning
10.1 Airflow Fundamentals, CFM Measurement, External Static Pressure, and Fan Laws 10.2 Duct Sizing Principles, Supply/Return Distribution, Dampers, and Air Balancing 10.3 Indoor Air Quality, MERV Ratings, Electronic Cleaners, Humidification, and Dehumidification 10.4 Deep Vacuum Evacuation (Micron Gauge), Subcooling/Superheat Charging, and System Commissioning 10.5 Duct Leakage, Blower Door Testing, and Building Envelope Performance
11 Chapter 11: Psychrometrics, Airside Calculations, and Load Estimation
11.1 Reading the Psychrometric Chart: Properties and Plotting 11.2 The Eight Air-Conditioning Processes and the Process Triangle 11.3 Mixed Air, Ventilation, and Infiltration Calculations 11.4 Residential Heat Loss, Heat Gain, and Equipment Sizing
12 Chapter 12: Light Commercial Air Conditioning
12.1 Packaged Rooftop and Split Light-Commercial Systems 12.2 Water-Cooled Condensers, Cooling Towers, and Chilled-Water Systems 12.3 Economizers, Demand-Controlled Ventilation, and VAV Air Distribution 12.4 Light-Commercial Start-Up, Commissioning, and Troubleshooting
13 Chapter 13: Light Commercial Refrigeration
13.1 Temperature Ranges, Box Loads, and Refrigeration System Types 13.2 Evaporators, Defrost Methods, and Defrost Controls 13.3 Condensing Units, Parallel Racks, Oil Management, and Capacity Control 13.4 Refrigeration Control Valves and Automatic Pump-Down 13.5 Commercial Refrigeration Diagnostics and Ice Machines
14 Chapter 14: Ductless, Mini-Split, and VRF Systems
14.1 Mini-Split Architecture and Inverter-Driven Compressors 14.2 Multi-Zone and VRF Operation, Electronic Expansion Valves, and Controls 14.3 Ductless Installation, Evacuation, Charging, and Diagnostics
15 Chapter 15: Building Automation and Digital Controls
15.1 DDC Fundamentals, Control Loops, and Sequences of Operation 15.2 BAS Networks, Protocols, and NEC-Compliant Cabling 15.3 Building Automation Controllers: Supervisory, Field, and Room Devices 15.4 Digital Logic, Numbering Systems, and Controller Programming 15.5 Sensor Selection, Installation, and Input Point Configuration 15.6 Actuators, Output Devices, and VFD Integration 15.7 Commercial Prints, Equipment Schedules, and BAS Documentation
11.2 The Eight Air-Conditioning Processes and the Process Triangle
Key Takeaways Explain This Topic AI
The eight air-conditioning processes are sensible heating, sensible cooling, humidification, dehumidification, and the four combinations of those pairs.
The process triangle resolves any diagonal process line into a horizontal sensible leg and a vertical latent leg, so total heat equals sensible plus latent.
Sensible heat ratio equals sensible heat divided by total heat; a residential cooling coil typically operates between 0.75 and 0.85.
Evaporative cooling follows a constant wet-bulb line, lowering dry bulb while raising humidity ratio with essentially no change in total heat.
A cooling coil's process line is straight from the entering-air point toward the apparatus dew point on the saturation curve, and how far it travels depends on the coil bypass factor.
Last updated: August 2026
11.2 The Eight Air-Conditioning Processes and the Process Triangle
The HVAC Excellence task list requires the technician to "describe the eight processes of air conditioning and how to plot each on a psychrometric chart," and to "define and use the Process Triangle on the psychrometric chart to calculate sensible heat, latent heat and total heat." These are two halves of one skill: identify what the equipment is doing to the air, then quantify it.
1. The Eight Processes
Every change to an airstream moves its state point in one of eight directions from the origin point. Four are pure; four are combinations. Humidifying
- ^
- |
- Cooling & | Heating &
- Humidifying \ | / Humidifying
- \ | /
- \ | /
- Sensible <------------ ORIGIN ------------> Sensible
- Cooling / | \ Heating
- / | \
- Cooling & / | \ Heating &
- Dehumidifying | Dehumidifying
- |
- v
- Dehumidifying
- # Process Direction on chart DB Grains Equipment
- 1 Sensible heating Horizontal right ↑ — Furnace heat exchanger, electric strip heat, reheat coil
- 2 Sensible cooling Horizontal left ↓ — Dry coil above dew point, economizer with cool dry air
- 3 Humidifying Vertical up — ↑ Steam humidifier (isothermal)
- 4 Dehumidifying Vertical down — ↓ Desiccant wheel (idealized; real desiccants add heat)
- 5 Cooling and dehumidifying Down and left ↓ ↓ The DX cooling coil — by far the most common
- 6 Heating and humidifying Up and right ↑ ↑ Furnace plus humidifier; some direct-fired gas makeup air units
- 7 Cooling and humidifying Down and right ↓ ↑ Evaporative (swamp) cooler — follows a constant wet-bulb line
- 8 Heating and dehumidifying Up and left ↑ ↓ Solid desiccant dehumidification; chemical dehumidifier
Two of these deserve special attention.
Process 5 — the cooling coil. Air entering a coil whose surface is below the entering air's dew point is cooled and dehumidified simultaneously. The process line runs from the entering-air state point in a straight line toward the coil's apparatus dew point on the saturation curve. How far along that line the air actually travels depends on bypass factor — the fraction of air that passes between fins without contacting a cold surface. Slow air over a deep, clean coil has a low bypass factor and travels far down the line (cold, dry supply air). Fast air over a shallow or fouled coil has a high bypass factor and stops short (warmer, wetter supply air, poor dehumidification).
Process 7 — evaporative cooling. Water sprayed into or evaporated from a media pad absorbs its latent heat of vaporization from the airstream itself . Sensible heat leaves the air and returns as latent heat in the added vapor, so total heat is essentially unchanged. The process is therefore adiabatic and follows a constant wet-bulb (constant enthalpy) line down and to the right. This is why evaporative cooling works in Phoenix (large wet-bulb depression, lots of room to move) and fails in Houston (small depression). The theoretical limit is the entering air's wet-bulb temperature; practical media reach 70–90% of that depression, called the saturation effectiveness .
2. The Process Triangle
A cooling coil's process line is a diagonal. The process triangle decomposes it into two right-angle legs whose meanings are unambiguous: Return air point (1) ●────────────────────┐ ← horizontal leg = SENSIBLE
- \ │
- \ (hypotenuse │ vertical leg = LATENT
- \ = TOTAL) │
- Supply air point (2) ●────────────────┘
The horizontal leg connects the two points at constant humidity ratio: it is the sensible change (temperature only).
The vertical leg connects at constant dry bulb: it is the latent change (moisture only).
The hypotenuse — the actual process line — is the total change.
Because enthalpy accounts for both, the three legs relate as: Q total = Q sensible + Q latent Q_{\text{total}} = Q_{\text{sensible}} + Q_{\text{latent}} Q total = Q sensible + Q latent
The three airside formulas Q sensible = 1.08 × CFM × Δ T DB Q_{\text{sensible}} = 1.08 \times \text{CFM} \times \Delta T_{\text{DB}} Q sensible = 1.08 × CFM × Δ T DB Q latent = 0.68 × CFM × Δ W grains Q_{\text{latent}} = 0.68 \times \text{CFM} \times \Delta W_{\text{grains}} Q latent = 0.68 × CFM × Δ W grains Q total = 4.5 × CFM × Δ h Q_{\text{total}} = 4.5 \times \text{CFM} \times \Delta h Q total = 4.5 × CFM × Δ h
Where the constants come from — the task list asks you to "learn the properties of air used to calculate the sensible heat factor," and reconstructing them beats memorizing them:
1.08 = 0.075 lb/ft 3 × 0.24 BTU/lb ⋅ ∘ F × 60 min/hr 1.08 = 0.075\ \text{lb/ft}^3 \times 0.24\ \text{BTU/lb}\cdot ^\circ\text{F} \times 60\ \text{min/hr} 1.08 = 0.075 lb/ft 3 × 0.24 BTU/lb ⋅ ∘ F × 60 min/hr
4.5 = 0.075 lb/ft 3 × 60 min/hr 4.5 = 0.075\ \text{lb/ft}^3 \times 60\ \text{min/hr} 4.5 = 0.075 lb/ft 3 × 60 min/hr
0.68 = 4.5 × 1,060 BTU/lb ÷ 7,000 grains/lb 0.68 = 4.5 \times 1{,}060\ \text{BTU/lb} \div 7{,}000\ \text{grains/lb} 0.68 = 4.5 × 1 , 060 BTU/lb ÷ 7 , 000 grains/lb (1,060 BTU/lb is the latent heat of vaporization of water at typical coil conditions)
All three assume standard air. At altitude, correct for density — at 5,000 feet, multiply by roughly 0.83.
Worked example
A residential system moves 1,200 CFM . Return air is 75°F DB / 63°F WB (65 grains/lb, 28.6 BTU/lb). Supply air is 55°F DB / 54°F WB (60 grains/lb, 22.6 BTU/lb). Q s = 1.08 × 1,200 × ( 75 − 55 ) = 1.08 × 1,200 × 20 = 25,920 BTU/hr Q_s = 1.08 \times 1{,}200 \times (75 - 55) = 1.08 \times 1{,}200 \times 20 = 25{,}920\text{ BTU/hr} Q s = 1.08 × 1 , 200 × ( 75 − 55 ) = 1.08 × 1 , 200 × 20 = 25 , 920 BTU/hr Q l = 0.68 × 1,200 × ( 65 − 60 ) = 0.68 × 1,200 × 5 = 4,080 BTU/hr Q_l = 0.68 \times 1{,}200 \times (65 - 60) = 0.68 \times 1{,}200 \times 5 = 4{,}080\text{ BTU/hr} Q l = 0.68 × 1 , 200 × ( 65 − 60 ) = 0.68 × 1 , 200 × 5 = 4 , 080 BTU/hr Q t = 4.5 × 1,200 × ( 28.6 − 22.6 ) = 4.5 × 1,200 × 6.0 = 32,400 BTU/hr Q_t = 4.5 \times 1{,}200 \times (28.6 - 22.6) = 4.5 \times 1{,}200 \times 6.0 = 32{,}400\text{ BTU/hr} Q t = 4.5 × 1 , 200 × ( 28.6 − 22.6 ) = 4.5 × 1 , 200 × 6.0 = 32 , 400 BTU/hr
Check: 25,920 + 4,080 = 30,000 25{,}920 + 4{,}080 = 30{,}000 25 , 920 + 4 , 080 = 30 , 000 , against a total of 32,400 — about 7% apart, which is normal for chart-read enthalpy values and rounding. On the exam the arithmetic is expected to close; in the field, treat a large disagreement as a sign that one of the four measurements is bad.
3. Sensible Heat Ratio SHR = Q sensible Q total \text{SHR} = \frac{Q_{\text{sensible}}}{Q_{\text{total}}} SHR = Q total Q sensible
Using the numbers above: SHR = 25,920 ÷ 32,400 = 0.80 \text{SHR} = 25{,}920 \div 32{,}400 = 0.80 SHR = 25 , 920 ÷ 32 , 400 = 0.80 .
- SHR Meaning Typical application
- 1.0 All sensible, no moisture removed Dry-climate cooling, computer room with no occupancy
- 0.85–0.95 Mostly sensible Arid climates, data centers, high-sensible retail
- 0.75–0.85 Typical residential and light commercial comfort cooling Most jobs
- 0.60–0.75 High latent load Humid coastal climates, restaurants, natatoriums, high occupancy
- Below 0.60 Latent-dominated Kitchens, laundries, indoor pools; usually needs dedicated dehumidification
Why SHR matters practically. Equipment is rated at a design SHR. If the building's actual SHR is much lower than the equipment's, the coil cannot remove enough moisture and the space stays humid even while the thermostat is satisfied. Remedies: lower the airflow per ton (from 400 CFM/ton toward 350 CFM/ton, which lowers coil surface temperature and increases moisture removal), select equipment with a lower rated SHR, add a variable-capacity system that runs longer at part load, or add dedicated dehumidification.
Conversely, running too much airflow raises coil temperature above the dew point, and the coil stops dehumidifying entirely — a common cause of "the house is 72°F and clammy."
On the chart, SHR is a slope. Most charts carry a protractor in the upper-left corner: draw a line from the reference point through the SHR value on the protractor scale, then draw a parallel line through the room design point. That line is the room sensible heat ratio line , and the supply air must be plotted somewhere along it to satisfy the room's combined sensible and latent load.