11.1 Reading the Psychrometric Chart: Properties and Plotting

HVAC Excellence Certification Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Introduction, Safety, Tools, and Diagnostic Method

1.1 HVAC Excellence Certification, Industry Codes, and Standards 1.2 Electrical Safety, PPE, Lockout/Tagout, and Hazard Communication 1.3 Multimeters, Manifold Gauges, Micron Gauges, and Diagnostic Instruments 1.4 HVACR Mathematics, Unit Conversions, and Efficiency Ratings 1.5 OSHA Standards, Fall Protection, Rigging, and Confined Spaces 1.6 HVACR Industry Organizations, Energy Resources, and Building Energy Programs 1.7 Systematic Troubleshooting: Data Plates, Manufacturer Literature, and Diagnostic Method

2 Chapter 2: Electrical Fundamentals and Circuit Theory

2.1 Voltage, Current, Resistance, and Ohm's Law Calculations 2.2 Series, Parallel, and Series-Parallel Circuits and Power Calculations 2.3 AC Fundamentals, Single-Phase vs Three-Phase Power, and Control Transformers 2.4 Conductors, Insulators, Wire Sizing, Voltage Drop, and NEC Ampacity

3 Chapter 3: Electrical Components, Motors, and Schematics

3.1 Contactors, Relays, Switches, Overload Protection, and Thermostats 3.2 HVAC Motors (PSC, CSIR, CSCR, ECM, 3-Phase) and Run/Start Capacitors 3.3 Interpreting Ladder Diagrams, Schematics, and Point-to-Point Wiring 3.4 Motor Testing, Insulation Resistance, Bearings, and Belt Drives

4 Chapter 4: Thermodynamics and the Refrigeration Cycle

4.1 Heat Transfer, Temperature Scales, BTUs, Sensible vs Latent Heat, and Enthalpy 4.2 The Four Vapor-Compression Cycle Stages (Compression, Condensation, Expansion, Evaporation) 4.3 P-T Charts, Saturated Conditions, Target Superheat, and Subcooling Calculations 4.4 Pressure–Enthalpy Diagrams, Compression Ratio, and Cycle Analysis

5 Chapter 5: Refrigerants, Environmental Regulations, and Recovery

5.1 Refrigerant Types (CFC, HCFC, HFC, HFO, HC) and ASHRAE Safety Groups (A1, A2L, A3) 5.2 EPA Section 608 Regulations, Venting Prohibitions, and Evacuation Standards 5.3 Recovery/Recycling/Reclaiming Equipment, Procedures, and Leak Detection 5.4 Refrigerant Retrofits, Cylinder Handling, and Refrigerant Purity 5.5 A2L and Low-GWP Refrigerants: Codes, Charge Limits, and Service Practice

6 Chapter 6: Refrigeration System Components and Accessories

6.1 Compressor Mechanics (Reciprocating, Scroll, Rotary, Screw) and Failures 6.2 Expansion Devices (TXV/TEV, Fixed Orifice, EEV) and Superheat Control 6.3 Condensers, Evaporators, Filter-Driers, Accumulators, Receivers, and Solenoids 6.4 Pressure Controls, Capacity Controls, and System Protection 6.5 Refrigerant Line Sizing, Pressure Drop, Brazing, and Piping Practice

7 Chapter 7: Gas Heating, Combustion Analysis, and Fuel Piping

7.1 Combustion Theory, Fuel Gases (Natural Gas vs LP), and Gas Burners 7.2 Gas Valves, Ignition Systems (Standing Pilot, Spark, HSI), and Safety Limit Controls 7.3 Flue Venting, Draft Principles, Combustion Analysis, and CO Safety 7.4 Fuel-Gas and Oil Piping, Vent System Selection and Sizing, and Installation Practice

8 Chapter 8: Electric Heating, Oil Heat, and Hydronics

8.1 Electric Heating Elements, Sequencers, Limit Switches, and kW Calculations 8.2 Oil Burners, Fuel Pumps, Nozzles, Ignition Electrodes, and Primary Controls 8.3 Hydronic Boilers, Circulator Pumps, Expansion Tanks, and Zone Controls 8.4 Combustion Air, Water Heaters, and Combustion Appliance Zone Testing

9 Chapter 9: Heat Pumps and Dual-Fuel Systems

9.1 Heat Pump Operation in Heating/Cooling Modes and Reversing Valve Operation 9.2 Defrost Controls (Time-Temperature, Demand Defrost), Sensors, and Sequences 9.3 Balance Points, Auxiliary/Emergency Heat, and Dual-Fuel (Hybrid) Systems 9.4 Heat Pump Diagnostics, Refrigerant Flow, and Troubleshooting Procedures 9.5 Heat Pump Types, Cold-Climate Performance, and Sizing Approaches

10 Chapter 10: Air Distribution, IAQ, and System Commissioning

10.1 Airflow Fundamentals, CFM Measurement, External Static Pressure, and Fan Laws 10.2 Duct Sizing Principles, Supply/Return Distribution, Dampers, and Air Balancing 10.3 Indoor Air Quality, MERV Ratings, Electronic Cleaners, Humidification, and Dehumidification 10.4 Deep Vacuum Evacuation (Micron Gauge), Subcooling/Superheat Charging, and System Commissioning 10.5 Duct Leakage, Blower Door Testing, and Building Envelope Performance

11 Chapter 11: Psychrometrics, Airside Calculations, and Load Estimation

11.1 Reading the Psychrometric Chart: Properties and Plotting 11.2 The Eight Air-Conditioning Processes and the Process Triangle 11.3 Mixed Air, Ventilation, and Infiltration Calculations 11.4 Residential Heat Loss, Heat Gain, and Equipment Sizing

12 Chapter 12: Light Commercial Air Conditioning

12.1 Packaged Rooftop and Split Light-Commercial Systems 12.2 Water-Cooled Condensers, Cooling Towers, and Chilled-Water Systems 12.3 Economizers, Demand-Controlled Ventilation, and VAV Air Distribution 12.4 Light-Commercial Start-Up, Commissioning, and Troubleshooting

13 Chapter 13: Light Commercial Refrigeration

13.1 Temperature Ranges, Box Loads, and Refrigeration System Types 13.2 Evaporators, Defrost Methods, and Defrost Controls 13.3 Condensing Units, Parallel Racks, Oil Management, and Capacity Control 13.4 Refrigeration Control Valves and Automatic Pump-Down 13.5 Commercial Refrigeration Diagnostics and Ice Machines

14 Chapter 14: Ductless, Mini-Split, and VRF Systems

14.1 Mini-Split Architecture and Inverter-Driven Compressors 14.2 Multi-Zone and VRF Operation, Electronic Expansion Valves, and Controls 14.3 Ductless Installation, Evacuation, Charging, and Diagnostics

15 Chapter 15: Building Automation and Digital Controls

15.1 DDC Fundamentals, Control Loops, and Sequences of Operation 15.2 BAS Networks, Protocols, and NEC-Compliant Cabling 15.3 Building Automation Controllers: Supervisory, Field, and Room Devices 15.4 Digital Logic, Numbering Systems, and Controller Programming 15.5 Sensor Selection, Installation, and Input Point Configuration 15.6 Actuators, Output Devices, and VFD Integration 15.7 Commercial Prints, Equipment Schedules, and BAS Documentation

11.1 Reading the Psychrometric Chart: Properties and Plotting

Key Takeaways Explain This Topic AI

Any two independent air properties fix a point on the psychrometric chart, and every other property can then be read from that point.

Dry-bulb temperature lines run vertically, wet-bulb and enthalpy lines slope down to the right, and relative humidity curves arc upward with the saturation curve at 100% RH.

Wet-bulb depression is dry-bulb minus wet-bulb temperature, and it is zero at saturation, which is why the wet-bulb, dew point, and dry-bulb temperatures are all equal on the saturation curve.

Standard air is defined as 0.075 pounds per cubic foot at 70 degrees Fahrenheit and 29.92 inches of mercury, and every airside constant such as 1.08 and 4.5 is derived from that density.

Humidity ratio is measured in grains of moisture per pound of dry air, and 7,000 grains equal one pound of water.

Last updated: August 2026

11.1 Reading the Psychrometric Chart: Properties and Plotting

The HVAC Excellence Competency and Task List asks candidates to "identify what property each line on a psychrometric chart represents," to demonstrate "the ability to plot any two basic points on the psychrometric chart and evaluate the data," and to understand "the thermodynamics of air and water vapor." The requirement appears on five separate competency sheets . No other single skill is repeated as often.

A psychrometric chart is a graphical solution to a set of equations relating the properties of moist air at one barometric pressure — normally sea level, 29.92 in. Hg. Air conditioning is not temperature control; it is the simultaneous control of temperature and moisture , and the chart is where those two are handled together.

1. Air and Water Vapor

Atmospheric air is a mixture of dry air (78% nitrogen, 21% oxygen, 1% other) and water vapor . The two behave independently: Dalton's Law of partial pressures states that each gas in a mixture exerts pressure as though it alone occupied the volume, and total pressure is the sum. The vapor's partial pressure is what drives condensation and evaporation.

The water vapor cycle — a named task-list item — is the same process at atmospheric scale: solar energy evaporates surface water, moist air rises and cools, vapor condenses into clouds at the dew point, and precipitation returns it. An air conditioner runs one leg of that cycle deliberately, cooling air below its dew point to force condensation on the coil.

Standard air is the reference condition for every airside calculation:

  • Density: 0.075 lb/ft³
  • Temperature: 70°F , barometric pressure 29.92 in. Hg
  • Specific volume: 13.33 ft³/lb (the reciprocal of density)

Density falls with altitude and with temperature. At 5,000 feet, air is roughly 83% as dense as at sea level, so all the standard constants must be corrected — a fact that matters for both duct sizing and gas furnace derating.

2. The Seven Properties on the Chart

Learn the direction of each line; the numbers follow.

Property Line direction Units What it measures

Dry-bulb temperature (DB) Vertical lines; scale along the bottom °F Sensible heat — what an ordinary thermometer reads

Wet-bulb temperature (WB) Sloping down to the right ; scale along the saturation curve °F Total heat content — what a wetted-wick thermometer reads

Relative humidity (RH) Curved lines arcing up to the right % Ratio of actual vapor pressure to saturation vapor pressure at that dry bulb

Humidity ratio (W) Horizontal lines; scale on the right edge grains/lb or lb/lb Actual mass of moisture per pound of dry air

Dew point (DP) Read horizontally left to the saturation curve °F Temperature at which the air becomes saturated

Enthalpy (h) Sloping down to the right, nearly parallel to WB; scale on the upper-left diagonal BTU/lb of dry air Total heat, sensible plus latent

Specific volume (v) Steeply sloping, nearly vertical, down to the right ft³/lb Volume occupied by one pound of dry air

The saturation curve is the left/upper boundary of the chart — 100% RH . On it, dry-bulb, wet-bulb, and dew point are all the same temperature . Air cannot exist to the left of the curve; moisture would condense out.

Understanding wet bulb

A wet-bulb thermometer has a water-soaked wick. Water evaporates from the wick, and evaporation absorbs latent heat from the thermometer, cooling it. The drier the air, the faster the evaporation and the lower the wet-bulb reading.

Wet-bulb depression = DB − WB. It is the direct indicator of how much moisture the air can still absorb:

Large depression (say 78°F DB / 62°F WB, 16°F depression) → dry air.

Small depression (78°F DB / 76°F WB, 2°F depression) → very humid air.

Zero depression → saturated air at 100% RH.

A sling psychrometer or digital psychrometer takes both readings at once; the task list names it as a required instrument. Sling for 30–60 seconds until the wet-bulb reading stops falling, and read the wet bulb first because it rises as soon as slinging stops.

Humidity ratio and grains

Humidity ratio is expressed in grains of moisture per pound of dry air . There are 7,000 grains in one pound of water. Typical values: comfortable indoor air at 75°F/50% RH holds about 65 grains/lb ; humid outdoor air at 90°F/70% RH holds about 155 grains/lb . The difference between entering and leaving grains is exactly what a cooling coil removes.

Relative humidity is a ratio, not a quantity

Air at 40°F and 90% RH holds far less moisture than air at 90°F and 40% RH, because warm air can hold much more vapor. This is why winter air is dry indoors: cold outdoor air at high RH, heated to 70°F without adding moisture, arrives at a very low RH. Plot it — the point moves horizontally right along a constant humidity ratio line, crossing RH curves downward.

3. Plotting a Point

Any two independent properties fix a point. Once plotted, every other property is read from that location. In the field the two you measure are almost always dry bulb and wet bulb .

Worked example. Return air measures 75°F DB / 63°F WB .

Find 75°F on the bottom scale and follow the vertical dry-bulb line up.

Find 63°F on the saturation curve and follow the wet-bulb line down and to the right.

Mark the intersection. That is the state point.

Read the rest:

  • RH ≈ 51% (interpolate between the 50% and 60% curves)
  • Humidity ratio ≈ 65 grains/lb (horizontal, right-hand scale)
  • Dew point ≈ 55°F (horizontal left to the saturation curve)
  • Enthalpy ≈ 28.6 BTU/lb (diagonal scale, upper left)
  • Specific volume ≈ 13.68 ft³/lb

Second worked example — supply air. Measure 55°F DB / 54°F WB off the coil. Plot it: RH ≈ 94%, humidity ratio ≈ 60 grains/lb, dew point ≈ 53°F, enthalpy ≈ 22.6 BTU/lb. Comparing the two points tells you the coil removed 28.6 − 22.6 = 6.0 28.6 - 22.6 = 6.0 28.6 − 22.6 = 6.0 BTU per pound of air, and 65 − 60 = 5 65 - 60 = 5 65 − 60 = 5 grains per pound of moisture.

  • 4. What the Chart Tells You in the Field
  • Comfort zone

ASHRAE Standard 55 defines an acceptable comfort region on the chart — roughly 68–78°F DB and 30–60% RH for typical clothing and activity. The task list requires explaining "the comfort zone and the different temperatures and relative humidity's effect on human comfort."

Above 60% RH: evaporation from skin slows, the space feels warmer than the thermostat says, and mold and dust-mite growth accelerate.

Below 30% RH: rapid evaporation makes the space feel cold at the same dry bulb, and occupants report static shock, dry skin, and respiratory irritation.

Raising RH from 30% to 50% lets many buildings drop the dry-bulb setpoint 2–3°F with no loss of comfort — a real energy saving.

Diagnosing a coil from two plotted points

Observation on the chart Meaning

Supply point nearly vertically below return (little moisture removed) Airflow too high, coil too warm, or the load is nearly all sensible

Supply point far down and left with a large grain drop Low airflow, or a very high latent load

Supply air at high RH but only a small DB drop Low airflow across a cold coil — check filter and static pressure

Return air at 80°F DB / 72°F WB in a residence Very high latent load: infiltration, unbalanced ventilation, or duct leakage from a crawlspace

Apparatus dew point (ADP) is where the coil's process line, extended, crosses the saturation curve — the effective surface temperature of the coil. Comparing the actual leaving-air point to the ADP gives the coil bypass factor , the fraction of air that slips through without touching a fin. A dirty or badly configured coil has a high bypass factor and poor dehumidification even when the total capacity looks acceptable.