4.4 Pressure–Enthalpy Diagrams, Compression Ratio, and Cycle Analysis
HVAC Excellence Certification Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Introduction, Safety, Tools, and Diagnostic Method
1.1 HVAC Excellence Certification, Industry Codes, and Standards 1.2 Electrical Safety, PPE, Lockout/Tagout, and Hazard Communication 1.3 Multimeters, Manifold Gauges, Micron Gauges, and Diagnostic Instruments 1.4 HVACR Mathematics, Unit Conversions, and Efficiency Ratings 1.5 OSHA Standards, Fall Protection, Rigging, and Confined Spaces 1.6 HVACR Industry Organizations, Energy Resources, and Building Energy Programs 1.7 Systematic Troubleshooting: Data Plates, Manufacturer Literature, and Diagnostic Method
2 Chapter 2: Electrical Fundamentals and Circuit Theory
2.1 Voltage, Current, Resistance, and Ohm's Law Calculations 2.2 Series, Parallel, and Series-Parallel Circuits and Power Calculations 2.3 AC Fundamentals, Single-Phase vs Three-Phase Power, and Control Transformers 2.4 Conductors, Insulators, Wire Sizing, Voltage Drop, and NEC Ampacity
3 Chapter 3: Electrical Components, Motors, and Schematics
3.1 Contactors, Relays, Switches, Overload Protection, and Thermostats 3.2 HVAC Motors (PSC, CSIR, CSCR, ECM, 3-Phase) and Run/Start Capacitors 3.3 Interpreting Ladder Diagrams, Schematics, and Point-to-Point Wiring 3.4 Motor Testing, Insulation Resistance, Bearings, and Belt Drives
4 Chapter 4: Thermodynamics and the Refrigeration Cycle
4.1 Heat Transfer, Temperature Scales, BTUs, Sensible vs Latent Heat, and Enthalpy 4.2 The Four Vapor-Compression Cycle Stages (Compression, Condensation, Expansion, Evaporation) 4.3 P-T Charts, Saturated Conditions, Target Superheat, and Subcooling Calculations 4.4 Pressure–Enthalpy Diagrams, Compression Ratio, and Cycle Analysis
5 Chapter 5: Refrigerants, Environmental Regulations, and Recovery
5.1 Refrigerant Types (CFC, HCFC, HFC, HFO, HC) and ASHRAE Safety Groups (A1, A2L, A3) 5.2 EPA Section 608 Regulations, Venting Prohibitions, and Evacuation Standards 5.3 Recovery/Recycling/Reclaiming Equipment, Procedures, and Leak Detection 5.4 Refrigerant Retrofits, Cylinder Handling, and Refrigerant Purity 5.5 A2L and Low-GWP Refrigerants: Codes, Charge Limits, and Service Practice
6 Chapter 6: Refrigeration System Components and Accessories
6.1 Compressor Mechanics (Reciprocating, Scroll, Rotary, Screw) and Failures 6.2 Expansion Devices (TXV/TEV, Fixed Orifice, EEV) and Superheat Control 6.3 Condensers, Evaporators, Filter-Driers, Accumulators, Receivers, and Solenoids 6.4 Pressure Controls, Capacity Controls, and System Protection 6.5 Refrigerant Line Sizing, Pressure Drop, Brazing, and Piping Practice
7 Chapter 7: Gas Heating, Combustion Analysis, and Fuel Piping
7.1 Combustion Theory, Fuel Gases (Natural Gas vs LP), and Gas Burners 7.2 Gas Valves, Ignition Systems (Standing Pilot, Spark, HSI), and Safety Limit Controls 7.3 Flue Venting, Draft Principles, Combustion Analysis, and CO Safety 7.4 Fuel-Gas and Oil Piping, Vent System Selection and Sizing, and Installation Practice
8 Chapter 8: Electric Heating, Oil Heat, and Hydronics
8.1 Electric Heating Elements, Sequencers, Limit Switches, and kW Calculations 8.2 Oil Burners, Fuel Pumps, Nozzles, Ignition Electrodes, and Primary Controls 8.3 Hydronic Boilers, Circulator Pumps, Expansion Tanks, and Zone Controls 8.4 Combustion Air, Water Heaters, and Combustion Appliance Zone Testing
9 Chapter 9: Heat Pumps and Dual-Fuel Systems
9.1 Heat Pump Operation in Heating/Cooling Modes and Reversing Valve Operation 9.2 Defrost Controls (Time-Temperature, Demand Defrost), Sensors, and Sequences 9.3 Balance Points, Auxiliary/Emergency Heat, and Dual-Fuel (Hybrid) Systems 9.4 Heat Pump Diagnostics, Refrigerant Flow, and Troubleshooting Procedures 9.5 Heat Pump Types, Cold-Climate Performance, and Sizing Approaches
10 Chapter 10: Air Distribution, IAQ, and System Commissioning
10.1 Airflow Fundamentals, CFM Measurement, External Static Pressure, and Fan Laws 10.2 Duct Sizing Principles, Supply/Return Distribution, Dampers, and Air Balancing 10.3 Indoor Air Quality, MERV Ratings, Electronic Cleaners, Humidification, and Dehumidification 10.4 Deep Vacuum Evacuation (Micron Gauge), Subcooling/Superheat Charging, and System Commissioning 10.5 Duct Leakage, Blower Door Testing, and Building Envelope Performance
11 Chapter 11: Psychrometrics, Airside Calculations, and Load Estimation
11.1 Reading the Psychrometric Chart: Properties and Plotting 11.2 The Eight Air-Conditioning Processes and the Process Triangle 11.3 Mixed Air, Ventilation, and Infiltration Calculations 11.4 Residential Heat Loss, Heat Gain, and Equipment Sizing
12 Chapter 12: Light Commercial Air Conditioning
12.1 Packaged Rooftop and Split Light-Commercial Systems 12.2 Water-Cooled Condensers, Cooling Towers, and Chilled-Water Systems 12.3 Economizers, Demand-Controlled Ventilation, and VAV Air Distribution 12.4 Light-Commercial Start-Up, Commissioning, and Troubleshooting
13 Chapter 13: Light Commercial Refrigeration
13.1 Temperature Ranges, Box Loads, and Refrigeration System Types 13.2 Evaporators, Defrost Methods, and Defrost Controls 13.3 Condensing Units, Parallel Racks, Oil Management, and Capacity Control 13.4 Refrigeration Control Valves and Automatic Pump-Down 13.5 Commercial Refrigeration Diagnostics and Ice Machines
14 Chapter 14: Ductless, Mini-Split, and VRF Systems
14.1 Mini-Split Architecture and Inverter-Driven Compressors 14.2 Multi-Zone and VRF Operation, Electronic Expansion Valves, and Controls 14.3 Ductless Installation, Evacuation, Charging, and Diagnostics
15 Chapter 15: Building Automation and Digital Controls
15.1 DDC Fundamentals, Control Loops, and Sequences of Operation 15.2 BAS Networks, Protocols, and NEC-Compliant Cabling 15.3 Building Automation Controllers: Supervisory, Field, and Room Devices 15.4 Digital Logic, Numbering Systems, and Controller Programming 15.5 Sensor Selection, Installation, and Input Point Configuration 15.6 Actuators, Output Devices, and VFD Integration 15.7 Commercial Prints, Equipment Schedules, and BAS Documentation
4.4 Pressure–Enthalpy Diagrams, Compression Ratio, and Cycle Analysis
Key Takeaways Explain This Topic AI
Plotting the refrigeration cycle on a pressure-enthalpy chart is an explicit competency on five separate HVAC Excellence task-list sheets.
The P-H chart's saturated liquid line and saturated vapor line meet at the critical point, dividing the chart into subcooled liquid, the saturated mixture region, and superheated vapor.
Net refrigerating effect is the enthalpy gained across the evaporator, and heat of compression is the enthalpy added by the compressor.
Compression ratio equals absolute discharge pressure divided by absolute suction pressure, using psia rather than psig; ratios above about 10:1 sharply reduce volumetric efficiency.
Coefficient of performance from the P-H chart equals net refrigerating effect divided by heat of compression, so a cycle with 65 BTU/lb of effect and 20 BTU/lb of compression work has a COP of 3.25.
Last updated: August 2026
4.4 Pressure–Enthalpy Diagrams, Compression Ratio, and Cycle Analysis
"Plotting the refrigeration cycle on a pressure enthalpy chart" appears verbatim on the Residential Air Conditioning, Commercial Air Conditioning, Commercial Refrigeration, Mini-Splits, and Low-GWP sheets of the HVAC Excellence Competency and Task List. It is one of the most heavily repeated competencies in the entire document, and it is the tool that turns two gauge readings and two temperatures into a statement about energy .
Section 4.3 covered pressure–temperature relationships, superheat, and subcooling. The P-H chart adds the third axis of the story: enthalpy , the total heat content per pound of refrigerant.
1. Reading the Chart
A pressure–enthalpy (Mollier) diagram is refrigerant-specific — an R-410A chart cannot be used for R-454B.
Vertical axis: absolute pressure (psia) , on a logarithmic scale. Logarithmic spacing compresses the enormous pressure range into readable space and makes the constant-pressure processes plot as straight horizontal lines.
Horizontal axis: enthalpy (BTU per pound) , linear. Moving right means the refrigerant contains more heat.
The saturation dome: the saturated liquid line on the left and the saturated vapor line on the right meet at the critical point at the top. Above the critical point no amount of pressure will condense the refrigerant.
Three regions: left of the liquid line is subcooled liquid ; inside the dome is a saturated liquid-vapor mixture ; right of the vapor line is superheated vapor .
Quality lines inside the dome mark the percentage of vapor by weight — the 0.2 line means 20% of the mass has flashed to vapor.
Constant temperature lines run vertically in the subcooled region, horizontally inside the dome (because temperature and pressure are locked together during a phase change), and drop steeply to the right in the superheat region.
Constant entropy lines run steeply up and to the right in the superheat region; ideal compression follows one of them.
2. Plotting the Four Processes
Consider an R-410A system with a 40°F evaporator (118 psig / 132.7 psia), a 120°F condenser (418 psig / 432.7 psia), 10°F of superheat, and 12°F of subcooling.
Point Location State Enthalpy
1 Compressor suction 50°F vapor at 132.7 psia (40°F sat + 10°F SH) h 1 = 121 BTU/lb h_1 = 121\text{ BTU/lb} h 1 = 121 BTU/lb
2 Compressor discharge Superheated vapor at 432.7 psia h 2 = 141 BTU/lb h_2 = 141\text{ BTU/lb} h 2 = 141 BTU/lb
3 Liquid line, metering-device inlet 108°F liquid at 432.7 psia (120°F sat − 12°F SC) h 3 = 56 BTU/lb h_3 = 56\text{ BTU/lb} h 3 = 56 BTU/lb
4 Evaporator inlet 40°F mixture at 132.7 psia, about 22% flash gas h 4 = 56 BTU/lb h_4 = 56\text{ BTU/lb} h 4 = 56 BTU/lb
1 → 2: Compression. Up and to the right, following (approximately) a constant-entropy line. Pressure and enthalpy both rise. 2 → 3: Condensation. Straight left at constant pressure. The line crosses the vapor line (desuperheating ends), traverses the dome (latent condensation), crosses the liquid line, and continues into the subcooled region. 3 → 4: Expansion. Straight down , vertically. Expansion through a fixed orifice or TXV is isenthalpic — constant enthalpy — because no heat and no work cross the boundary. The refrigerant does not lose heat in the metering device; some of its liquid flashes to vapor, and that flash gas cools the remaining liquid to the new saturation temperature. 4 → 1: Evaporation. Straight right at constant pressure, crossing the vapor line and continuing into superheat.
3. The Numbers the Chart Gives You
Net Refrigerating Effect (NRE) — the useful cooling each pound performs: NRE = h 1 − h 4 = 121 − 56 = 65 BTU/lb \text{NRE} = h_1 - h_4 = 121 - 56 = 65\text{ BTU/lb} NRE = h 1 − h 4 = 121 − 56 = 65 BTU/lb
Heat of Compression — work the compressor adds: HOC = h 2 − h 1 = 141 − 121 = 20 BTU/lb \text{HOC} = h_2 - h_1 = 141 - 121 = 20\text{ BTU/lb} HOC = h 2 − h 1 = 141 − 121 = 20 BTU/lb
Total Heat of Rejection (THOR) — everything the condenser must remove: THOR = h 2 − h 3 = 141 − 56 = 85 BTU/lb = NRE + HOC \text{THOR} = h_2 - h_3 = 141 - 56 = 85\text{ BTU/lb} = \text{NRE} + \text{HOC} THOR = h 2 − h 3 = 141 − 56 = 85 BTU/lb = NRE + HOC
This is why a condenser is always larger than the evaporator: it rejects both the heat absorbed indoors and the work the compressor added.
Coefficient of Performance (theoretical): COP = NRE HOC = 65 20 = 3.25 \text{COP} = \frac{\text{NRE}}{\text{HOC}} = \frac{65}{20} = 3.25 COP = HOC NRE = 20 65 = 3.25
Mass flow rate required for a given capacity: m ˙ = Capacity (BTU/hr) NRE (BTU/lb) \dot m = \frac{\text{Capacity (BTU/hr)}}{\text{NRE (BTU/lb)}} m ˙ = NRE (BTU/lb) Capacity (BTU/hr)
A 3-ton system (36,000 BTU/hr) needs 36,000 ÷ 65 = 554 lb/hr 36{,}000 \div 65 = 554\text{ lb/hr} 36 , 000 ÷ 65 = 554 lb/hr , or 9.2 lb/min.
Why subcooling matters, quantitatively. Increase subcooling from 12°F to 22°F and h 3 h_3 h 3 falls to roughly 51 BTU/lb. NRE becomes 121 − 51 = 70 BTU/lb 121 - 51 = 70\text{ BTU/lb} 121 − 51 = 70 BTU/lb — a 7.7% capacity increase for the same compressor work , and flash gas at the metering device drops from about 22% to about 17%. This is the entire argument for liquid-line subcooling and for head-pressure control on low-ambient systems.
4. Compression Ratio CR = Absolute discharge pressure (psia) Absolute suction pressure (psia) \text{CR} = \frac{\text{Absolute discharge pressure (psia)}}{\text{Absolute suction pressure (psia)}} CR = Absolute suction pressure (psia) Absolute discharge pressure (psia)
Absolute, not gauge. Add 14.7 to each gauge reading. Using psig produces a wildly wrong answer, and that error is a favorite exam distractor.
For the example above: CR = 432.7 ÷ 132.7 = 3.26 : 1 \text{CR} = 432.7 \div 132.7 = 3.26{:}1 CR = 432.7 ÷ 132.7 = 3.26 : 1 — comfortable for an air conditioner.
- Application Typical CR
- Residential/commercial air conditioning 2.5:1 to 4:1
- Medium-temperature refrigeration 4:1 to 8:1
- Low-temperature refrigeration (single stage) 8:1 to 12:1
- Above 12:1 Two-stage or cascade required
- Consequences of a high compression ratio
Volumetric efficiency collapses. Vapor trapped in the compressor's clearance volume re-expands on the down-stroke and blocks the suction valve from opening until pressure falls below suction. The higher the ratio, the longer that re-expansion takes and the less fresh vapor enters. At 10:1 a reciprocating compressor may move less than half its displacement.
Discharge temperature rises. Less mass flow means less returning suction vapor to cool the motor and less oil circulation, so windings and discharge valves overheat. Sustained discharge temperatures above roughly 225°F at the line (about 300°F internally) begin breaking down oil, forming acid and carbon.
Diagnostic value. A low-temperature freezer running at 14:1 is not a compressor problem — it is a symptom. Look for a dirty or undersized condenser (high head), a starved evaporator or restricted suction line (low suction), or non-condensables raising head pressure.
5. Using the Chart to Diagnose
Chart symptom Physical cause
Point 1 far right of the vapor line (high superheat) with low suction pressure Undercharge, restriction, or starved metering device
Point 1 on or left of the vapor line (no superheat) Flooding — overcharge, oversized/hunting TXV, low airflow; liquid is reaching the compressor
Point 3 on the liquid line (zero subcooling) with a sight glass full of bubbles Undercharge, or a restricted liquid-line drier
Point 3 far left of the liquid line (very high subcooling) with high head Overcharge, or liquid backed up in the condenser from a restriction downstream
The 2 → 3 pressure line sitting abnormally high Dirty condenser, low condenser airflow, high ambient, or non-condensables
h 2 − h 1 h_2 - h_1 h 2 − h 1 abnormally small with normal pressures Compressor not compressing — worn rings, leaking valves, or a broken scroll
A worked field example. A walk-in freezer using R-404A reads 8 psig suction and 235 psig discharge. CR = 235 + 14.7 8 + 14.7 = 249.7 22.7 = 11.0 : 1 \text{CR} = \frac{235 + 14.7}{8 + 14.7} = \frac{249.7}{22.7} = 11.0{:}1 CR = 8 + 14.7 235 + 14.7 = 22.7 249.7 = 11.0 : 1
That is at the practical single-stage limit. The technician cleans the condenser and head pressure falls to 190 psig: CR = 204.7 ÷ 22.7 = 9.0 : 1 \text{CR} = 204.7 \div 22.7 = 9.0{:}1 CR = 204.7 ÷ 22.7 = 9.0 : 1 . Volumetric efficiency recovers, the box pulls down, discharge temperature drops, and the oil stops degrading — all diagnosed from two gauges and a division.