7.2 Gas Pipe Sizing Calculations, Longest Length & Branch Method

Iowa Journeyperson Plumber Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Iowa Licensing, Exam Format, Code Adoption & UPC General Regulations

1.1 Iowa Licensing Tiers, PMSB Rules, Code Adoption, Permits & Inspections 1.2 UPC Chapter 3 General Regulations: Trenching, Protection of Piping & Iowa Burial Depths 1.3 Plumbing Mathematics, Pipe Sizing Formulas & Blueprint Reading 1.4 Hangers, Supports, Pipe Joints, and Material Compatibility 1.5 Exam Format, Approved References & Open-Book Lookup Strategy

2 Chapter 2: Plumbing Fixtures & Fixture Fittings (UPC Chapter 4)

2.1 Fixture Unit Values & Iowa Minimum Plumbing Fixture Requirements 2.2 Water Closets, Urinals, Bidets & Lavatories 2.3 Bathtubs, Showers, Sinks & Food Prep Fixtures 2.4 Plumbing Fixture Installation Standards & ADA Accessibility 2.5 Specialty Appliances, Floor Drains, Indirect Waste & Interceptors

3 Chapter 3: Sanitary Drainage & Building Sewers (UPC Chapter 7)

3.1 Sanitary Drainage System Components, Layout & Gravity Flow Principles 3.2 Drainage Fixture Unit (DFU) Values & Horizontal/Vertical Sizing 3.3 Building Sewers, Building Drains & Sewer Connection Standards 3.4 Drain Slopes, Velocities & Changes of Direction (UPC 706.0 and 708.0) 3.5 Cleanouts: Placement, Sizing, Clearances & Access Requirements 3.6 Sump Pumps, Sewage Ejectors & Backwater Valves 3.7 Drainage Materials, Joints, Prohibited Practices & DWV Testing 3.8 Sizing a Complete DWV System: Two Worked Walkthroughs

4 Chapter 4: Venting Systems (UPC Chapter 9)

4.1 Venting Fundamentals, Trap Seal Protection & the Iowa Trap Arm Table 4.2 Vent Sizing from UPC Table 703.2, Vent Stacks & Yoke Vents 4.3 Wet Venting Under UPC Section 908 and the Iowa Sizing Amendment 4.4 Venting Fixture Batteries: Common Vents, Relief Vents & Why Circuit Venting Is Not an Iowa Method 4.5 Air Admittance Valves, Combination Waste & Vent, and Island Venting 4.6 Vent Termination, Roof Penetrations & Flashings 4.7 Applying the Vent Rules: Worked Venting Walkthroughs 4.8 Diagnosing Venting Failures: Symptom-to-Cause Troubleshooting

5 Chapter 5: Traps, Interceptors & Indirect Waste (UPC Chapters 8 and 10)

5.1 Trap Design, Seals, Prohibited Traps & Trap Primers 5.2 Indirect & Special Waste Receptors and Air Gaps 5.3 Grease Interceptors & Trap Sizing (Hydromechanical & Gravity) 5.4 Oil, Sand, Flammable Liquid & Chemical Interceptors

6 Chapter 6: Water Supply & Distribution (UPC Chapter 6)

6.1 Water Service Piping, Main Sizing & Meter Installation 6.2 Water Supply Fixture Units (WSFU) & Pipe Sizing Calculations 6.3 Water Pressure Regulators, Pressure Relief & Thermal Expansion 6.4 Backflow Prevention: Cross-Connection Control & Device Selection 6.5 Potable Water Pipe Materials, Valves & Disinfection

7 Chapter 7: Water Heaters (UPC Chapter 5)

7.1 Water Heater Types, Sizing, Recovery Rate & First-Hour Rating 7.2 Water Heater Safety: T&P Relief Valves, Drain Pans, Combustion Air & Anti-Scald Controls 7.3 Water Heater Venting: Appliance Categories, Vent Connectors, Chimneys & Terminations 7.4 Water Heater Location, Clearances, Supports, Replacement & Iowa Amendments

8 Chapter 8: Storm Drainage (UPC Chapter 11)

8.1 Storm Drainage Scope, Materials, Traps & Prohibited Connections 8.2 Sizing Roof Drains, Leaders & Vertical Rainwater Piping (UPC Table 1103.1) 8.3 Sizing Horizontal Storm Drains, Storm Sewers & Gutters (UPC Tables 1103.2 and 1103.3) 8.4 Side Walls Draining Onto a Roof, Secondary Roof Drainage & Controlled-Flow Roofs 8.5 Subsoil Drains, Areaway Drains, Storm Sumps & Building Storm Sewers

9 Chapter 9: Fuel Gas Piping & Appliance Venting (UPC Chapter 12)

7.1 Iowa Fuel Gas Authority (UPC Chapter 12), Gas Properties, System Types & Regulators 7.2 Gas Pipe Sizing Calculations, Longest Length & Branch Method 7.3 Gas Pipe Materials, Joining, CSST Rules Under the Iowa Amendments, Outlets & Valves 7.4 Fuel Gas Appliance Installation, Clearances & Combustion Air 7.5 Fuel Gas Venting Systems, Chimneys & Safety Testing

7.2 Gas Pipe Sizing Calculations, Longest Length & Branch Method

Key Takeaways Explain This Topic AI

Under the Longest Length Method, the measured distance from the point of delivery (meter/regulator) to the single most remote appliance outlet determines the sizing column used for every pipe section in the system.

Fuel gas pipe sizing tables for natural gas assume a specific gravity baseline of 0.60; when sizing for propane (SG = 1.50), table capacities must be multiplied by a conversion factor of 0.632 or dedicated LP tables must be used.

Gas demand must be calculated in Cubic Feet per Hour (CFH) by dividing appliance input ratings in BTU/hr by 1,000 for natural gas or by 2,500 for propane gas.

Each section of fuel gas piping must be sized based on the cumulative gas demand of all downstream appliances it supplies.

Corrugated Stainless Steel Tubing (CSST) relies on Equivalent Hydraulic Diameter (EHD) sizing values supplied by manufacturers and code tables rather than nominal pipe diameters due to internal corrugated flow turbulence.

Last updated: August 2026

7.2 Gas Pipe Sizing Calculations, Longest Length & Branch Method

Proper sizing of fuel gas piping is essential to ensure that every connected gas appliance receives adequate volumetric gas flow at the required manifold working pressure during peak simultaneous operation. Undersized gas piping causes severe pressure drops, resulting in incomplete fuel combustion, yellow flame soot deposition, elevated carbon monoxide ( C O CO CO ) generation, pilot light outages, and premature appliance failure.

Both the International Fuel Gas Code (IFGC Chapter 4) and the Uniform Plumbing Code (UPC Chapter 12) prescribe rigorous mathematical procedures and tabular lookup methods to size fuel gas piping. Plumbers must master the primary code methodology known as the Longest Length Method .

1. Hydraulic Factors & Pipe Sizing Variables

Calculating fuel gas pipe capacity depends on five fundamental physical variables:

Total Volumetric Demand (CFH) : The combined maximum gas consumption of all downstream appliances operating at full fire.

Total Developed Length (Feet) : The measured distance from the point of delivery (utility gas meter outlet or LP second-stage regulator) along the pipe path to the outlet being evaluated, including equivalent length additions for fittings.

Allowable Pressure Drop (in. w.c. or psi) : The allowable pressure loss between the point of delivery and the appliance inlet. For standard low-pressure natural gas systems ( 0.5 psi 0.5 \text{ psi} 0.5 psi supply), maximum pressure drop is typically set at 0.5 inches w.c. (or 0.3 inches w.c. under conservative utility rules).

Specific Gravity of Gas ( S G SG SG ) : Gas density relative to air ( 1.00 1.00 1.00 ). Baseline code capacity tables assume natural gas at S G = 0.60 SG = 0.60 SG = 0.60 .

Pipe Material Smoothness : Interior wall roughness factors (e.g., Schedule 40 black steel vs. semi-rigid copper vs. corrugated CSST).

Specific Gravity Multiplier for Propane Sizing

Because propane is denser than natural gas ( S G = 1.50 SG = 1.50 SG = 1.50 vs. 0.60 0.60 0.60 ), it experiences greater friction drag inside pipe walls. When utilizing standard natural gas code tables to size piping for propane, the tabular capacity values must be multiplied by a Specific Gravity Correction Multiplier ( F F F ) : F = S G Base S G Actual = 0.60 1.50 = 0.40 ≈ 0.632 F = \sqrt{\frac{SG_{\text{Base}}}{SG_{\text{Actual}}}} = \sqrt{\frac{0.60}{1.50}} = \sqrt{0.40} \approx 0.632 F = S G Actual ​ S G Base ​ ​ ​ = 1.50 0.60 ​ ​ = 0.40 ​ ≈ 0.632

Rule : To size a propane pipe using natural gas capacity tables, divide the required propane CFH demand by 0.632 to determine the equivalent natural gas table capacity required.

2. Step-by-Step Procedure: The Longest Length Method

The Longest Length Method is the standard procedure required by IFGC Section 402.4 and UPC Section 1208.4. It guarantees adequate terminal pressure by sizing every segment of the piping network against the maximum friction loss pathway in the building. [ Gas Meter / Point of Delivery ]

  • |
  • (Main Trunk Section 1)
  • |
  • +------+------+
  • | |
  • (Branch A) (Sub-Main Section 2)
  • Furnace |
  • (45 ft) +-----+----+
  • | |
  • (Branch B) (Branch C: Furthest Appliance)
  • Water Htr Patio Grill
  • (60 ft) (95 ft <--- SYSTEM LONGEST LENGTH)

Procedure Rules:

Step 1: Determine Appliance Load : Calculate the maximum hourly input rating (BTU/hr) for each appliance. Divide by 1,000 for Natural Gas (or 2,500 for Propane) to express demand in CFH .

Step 2: Measure the System Longest Length : Measure the linear piping distance from the Point of Delivery (meter outlet or second-stage LP regulator) to the single furthest appliance outlet in the entire piping network. This single maximum measurement is the System Longest Length .

Step 3: Select Code Sizing Table : Choose the correct sizing table corresponding to the pipe material (Schedule 40 metallic pipe, CSST, etc.), operating pressure (e.g., < 0.5 psi <0.5 \text{ psi} < 0.5 psi ), and design pressure drop (e.g., 0.5 in. w.c. 0.5 \text{ in. w.c.} 0.5 in. w.c. ).

Step 4: Establish Table Length Column : Locate the column in the sizing table corresponding to the System Longest Length (rounding up to the next tabular length increment, e.g., 90 ft or 100 ft). CRITICAL RULE : This exact same length column MUST be used to size every single section of pipe throughout the entire system—including the main trunk, sub-mains, and short individual branch lines .

Step 5: Determine Section Gas Loads : For each pipe section being sized, calculate the cumulative total CFH load passing through that specific section (i.e., the sum of all downstream appliances served by that pipe segment).

Step 6: Select Pipe Diameter : Look down the established Longest Length column to find a gas capacity equal to or greater than the cumulative CFH load required for that section. Select the corresponding nominal pipe size.

3. Worked Sizing Calculation Example

Consider a residential Natural Gas system ( 0.5 psi 0.5 \text{ psi} 0.5 psi supply, 0.5 in. w.c. 0.5 \text{ in. w.c.} 0.5 in. w.c. pressure drop, S G = 0.60 SG = 0.60 SG = 0.60 , Schedule 40 metallic pipe) with the following appliance schedule:

  • Outlet Appliance Description Input Rating (BTU/hr) Demand (CFH) Distance from Meter
  • Outlet A Gas Furnace 100,000 BTU/hr 100 CFH 35 Feet
  • Outlet B Water Heater 40,000 BTU/hr 40 CFH 50 Feet
  • Outlet C Gas Cooking Range 65,000 BTU/hr 65 CFH 65 Feet
  • Outlet D Clothes Dryer 35,000 BTU/hr 35 CFH 85 Feet (Furthest Outlet)
  • TOTAL Combined Full Load 240,000 BTU/hr 240 CFH —

Step-by-Step Execution:

Longest Length Determination : The furthest appliance is Outlet D at 85 feet. In the standard Schedule 40 pipe table (0.5 psi, 0.5" drop), round up to the 90-Foot Column .

Sizing Main Trunk Section 1 (Meter to Junction A) :

Carries load for Appliances A + B + C + D = 100 + 40 + 65 + 35 = 240 CFH 100 + 40 + 65 + 35 = \mathbf{240 \text{ CFH}} 100 + 40 + 65 + 35 = 240 CFH .

Check 90-ft column: 3/4" pipe carries 161 CFH (too small); 1" pipe carries 304 CFH (sufficient).

Selection: 1-Inch Pipe .

Sizing Sub-Main Section 2 (Junction A to Junction B) :

Carries load for Appliances B + C + D = 40 + 65 + 35 = 140 CFH 40 + 65 + 35 = \mathbf{140 \text{ CFH}} 40 + 65 + 35 = 140 CFH .

Check 90-ft column: 3/4" pipe carries 161 CFH (sufficient).

Selection: 3/4-Inch Pipe .

Sizing Individual Branch Lines (evaluated strictly against the 90-ft column ):

Branch A (Furnace, 100 CFH) : 3/4" carries 161 CFH → \rightarrow → 3/4-Inch Pipe .

Branch B (Water Heater, 40 CFH) : 1/2" carries 73 CFH → \rightarrow → 1/2-Inch Pipe .

Branch C (Range, 65 CFH) : 1/2" carries 73 CFH → \rightarrow → 1/2-Inch Pipe .

Branch D (Dryer, 35 CFH) : 1/2" carries 73 CFH → \rightarrow → 1/2-Inch Pipe .

4. CSST Equivalent Hydraulic Diameter (EHD) Sizing

Corrugated Stainless Steel Tubing (CSST) features a helical or annular corrugated internal wall structure. Internal corrugation generates turbulent boundary layer eddies, causing higher flow resistance and pressure loss than smooth black iron pipe.

EHD System Principles:

CSST is designated by an Equivalent Hydraulic Diameter (EHD) number (e.g., EHD 19, EHD 23, EHD 30, EHD 31) rather than standard fractional inch sizes.

EHD values represent a normalized measure of hydraulic flow capacity under ANSI LC 1 testing.

Because internal corrugation geometry varies between manufacturers (Gastite, TracPipe, WardFlex), CSST MUST BE SIZED EXCLUSIVELY USING THE SPECIFIC MANUFACTURER’S CAPACITY TABLES or the dedicated CSST tables in IFGC Chapter 4 / UPC Chapter 12. Interchanging brand capacity tables is prohibited.