3.6 Sump Pumps, Sewage Ejectors & Backwater Valves

Iowa Journeyperson Plumber Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Iowa Licensing, Exam Format, Code Adoption & UPC General Regulations

1.1 Iowa Licensing Tiers, PMSB Rules, Code Adoption, Permits & Inspections 1.2 UPC Chapter 3 General Regulations: Trenching, Protection of Piping & Iowa Burial Depths 1.3 Plumbing Mathematics, Pipe Sizing Formulas & Blueprint Reading 1.4 Hangers, Supports, Pipe Joints, and Material Compatibility 1.5 Exam Format, Approved References & Open-Book Lookup Strategy

2 Chapter 2: Plumbing Fixtures & Fixture Fittings (UPC Chapter 4)

2.1 Fixture Unit Values & Iowa Minimum Plumbing Fixture Requirements 2.2 Water Closets, Urinals, Bidets & Lavatories 2.3 Bathtubs, Showers, Sinks & Food Prep Fixtures 2.4 Plumbing Fixture Installation Standards & ADA Accessibility 2.5 Specialty Appliances, Floor Drains, Indirect Waste & Interceptors

3 Chapter 3: Sanitary Drainage & Building Sewers (UPC Chapter 7)

3.1 Sanitary Drainage System Components, Layout & Gravity Flow Principles 3.2 Drainage Fixture Unit (DFU) Values & Horizontal/Vertical Sizing 3.3 Building Sewers, Building Drains & Sewer Connection Standards 3.4 Drain Slopes, Velocities & Changes of Direction (UPC 706.0 and 708.0) 3.5 Cleanouts: Placement, Sizing, Clearances & Access Requirements 3.6 Sump Pumps, Sewage Ejectors & Backwater Valves 3.7 Drainage Materials, Joints, Prohibited Practices & DWV Testing 3.8 Sizing a Complete DWV System: Two Worked Walkthroughs

4 Chapter 4: Venting Systems (UPC Chapter 9)

4.1 Venting Fundamentals, Trap Seal Protection & the Iowa Trap Arm Table 4.2 Vent Sizing from UPC Table 703.2, Vent Stacks & Yoke Vents 4.3 Wet Venting Under UPC Section 908 and the Iowa Sizing Amendment 4.4 Venting Fixture Batteries: Common Vents, Relief Vents & Why Circuit Venting Is Not an Iowa Method 4.5 Air Admittance Valves, Combination Waste & Vent, and Island Venting 4.6 Vent Termination, Roof Penetrations & Flashings 4.7 Applying the Vent Rules: Worked Venting Walkthroughs 4.8 Diagnosing Venting Failures: Symptom-to-Cause Troubleshooting

5 Chapter 5: Traps, Interceptors & Indirect Waste (UPC Chapters 8 and 10)

5.1 Trap Design, Seals, Prohibited Traps & Trap Primers 5.2 Indirect & Special Waste Receptors and Air Gaps 5.3 Grease Interceptors & Trap Sizing (Hydromechanical & Gravity) 5.4 Oil, Sand, Flammable Liquid & Chemical Interceptors

6 Chapter 6: Water Supply & Distribution (UPC Chapter 6)

6.1 Water Service Piping, Main Sizing & Meter Installation 6.2 Water Supply Fixture Units (WSFU) & Pipe Sizing Calculations 6.3 Water Pressure Regulators, Pressure Relief & Thermal Expansion 6.4 Backflow Prevention: Cross-Connection Control & Device Selection 6.5 Potable Water Pipe Materials, Valves & Disinfection

7 Chapter 7: Water Heaters (UPC Chapter 5)

7.1 Water Heater Types, Sizing, Recovery Rate & First-Hour Rating 7.2 Water Heater Safety: T&P Relief Valves, Drain Pans, Combustion Air & Anti-Scald Controls 7.3 Water Heater Venting: Appliance Categories, Vent Connectors, Chimneys & Terminations 7.4 Water Heater Location, Clearances, Supports, Replacement & Iowa Amendments

8 Chapter 8: Storm Drainage (UPC Chapter 11)

8.1 Storm Drainage Scope, Materials, Traps & Prohibited Connections 8.2 Sizing Roof Drains, Leaders & Vertical Rainwater Piping (UPC Table 1103.1) 8.3 Sizing Horizontal Storm Drains, Storm Sewers & Gutters (UPC Tables 1103.2 and 1103.3) 8.4 Side Walls Draining Onto a Roof, Secondary Roof Drainage & Controlled-Flow Roofs 8.5 Subsoil Drains, Areaway Drains, Storm Sumps & Building Storm Sewers

9 Chapter 9: Fuel Gas Piping & Appliance Venting (UPC Chapter 12)

7.1 Iowa Fuel Gas Authority (UPC Chapter 12), Gas Properties, System Types & Regulators 7.2 Gas Pipe Sizing Calculations, Longest Length & Branch Method 7.3 Gas Pipe Materials, Joining, CSST Rules Under the Iowa Amendments, Outlets & Valves 7.4 Fuel Gas Appliance Installation, Clearances & Combustion Air 7.5 Fuel Gas Venting Systems, Chimneys & Safety Testing

3.6 Sump Pumps, Sewage Ejectors & Backwater Valves

Key Takeaways Explain This Topic AI

Sewage ejector sumps require a gas-tight, liquid-tight basin with a bolted gasketed cover and an independent vent; air admittance valves may not vent a sump or tank unless the vent system is engineered.

Discharge piping from an ejector receiving water closet waste is a minimum 2 inches with a check valve nearest the pump followed by an accessible fullway shutoff valve.

Iowa amends UPC Section 710.1 so a backwater valve is required only when the Authority Having Jurisdiction determines it necessary based on local conditions.

When Iowa requires a backwater valve, it will be a manually operated gate valve or fullway ball valve; an automatic backwater valve may also be installed but is not required.

Fixtures above the next upstream manhole cover must bypass any backwater valve so upper-floor discharge cannot back up through lower fixtures.

Last updated: August 2026

  • Sump Pumps, Sewage Ejectors & Backwater Valves
  • Sub-Grade Drainage: Gravity vs. Mechanical Lift

Whenever plumbing fixtures (water closets, showers, laundry trays, floor drains) are installed in basements or sub-grade levels where their flood level rims lie below the invert of the public sewer main or building sewer, their waste cannot drain by gravity.

Under UPC Section 710.0 , all sub-grade fixtures must discharge into an approved liquid-tight and gas-tight sump basin, where an automatic sewage ejector pump lifts the waste and discharges it into the gravity building drain.

Sump Pumps vs. Sewage Ejectors

It is vital to distinguish between clear-water sump pumps and sewage ejectors:

Parameter Clear-Water Sump Pump Sewage Ejector Pump

Fluid Handled Subsurface groundwater, rainwater, foundation tile condensate Raw sanitary sewage containing human waste and solids

Solids Passing Capacity Max 1/2-inch spherical solids Min 2-inch spherical solids (or grinder pump)

Basin Construction Perforated or unsealed pit acceptable Gas-tight, liquid-tight sealed basin with gasketed lid

  • Venting Requirement Venting not required Mandatory independent vent (Min 2-inch) routed to outdoor air
  • Air Admittance Valve Use Permitted in some clear water applications STRICTLY PROHIBITED on ejector sumps
  • Point of Discharge Storm sewer, surface drainage, or swale Gravity sanitary building drain
  • Sewage Ejector Installation & Piping Rules [ To Outdoor Vent Termination ]
  • ▲
  • │ Min 2" Vent Pipe
  • To Gravity │
  • Building Drain ◄───[ Fullway Gate/Ball Valve ] (Shutoff Valve)
  • ▲
  • │
  • [ Swing Check Valve ] (Prevents Backflow into Sump)
  • ▲
  • │ Min 2" Discharge Line
  • ┌──────────┴───────────────────────────┐
  • │ GASKETED GAS-TIGHT COVER │
  • ──────┴──────────────────────────────────────┴────── Basement Floor
  • │ ┌──────────────────────────────────────┐ │
  • │ │ │ │
  • │ │ SEWAGE EJECTOR PUMP │ │
  • │ │ (Handling 2" Solids) │ │
  • │ └──────────────────────────────────────┘ │
  • └────────────────────────────────────────────┘
  • Basin and Venting Standards (UPC Section 710.2)

Basin Cover: Sumps receiving sewage must be enclosed in a gas-tight, liquid-tight pit with a bolted, gasketed cover.

Vent Sizing: Sumps must be vented to prevent air locking when sewage enters and to exhaust foul gases. The vent pipe must be at least 2 inches in diameter (or sized per UPC Table 710.1 based on pump GPM and pipe length).

Prohibition of AAVs: Air Admittance Valves (AAVs) rely on gravity to close and cannot handle positive air displacement when a pump rapidly discharges. AAVs are strictly prohibited on sewage ejector sumps.

Discharge Piping and Valve Requirements (UPC Section 710.4)

Discharge Diameter: The discharge pipe serving a non-grinder sewage ejector receiving water closet waste must be at least 2 inches in diameter.

Valve Sequence: Every ejector discharge line must be equipped with two valves, installed in a specific sequence moving away from the pump toward the building drain:

Step 1 (Closest to Pump): An approved swing check valve or quiet check valve to prevent backflow of liquid from the vertical stack back into the sump when the pump stops.

Step 2 (Downstream of Check Valve): An accessible fullway gate valve or ball valve installed downstream of the check valve. This shutoff valve allows isolation so the check valve can be serviced without draining the entire horizontal building drain system.

Sump Pump Sizing Calculations

Pump capacity is calculated based on total connected DFU load converted to peak GPM, plus required dynamic head pressure.

Peak Flow Rate Formula

For residential ejector applications serving water closets, the pump must deliver a flow rate sufficient to achieve self-scouring velocity (2.0 fps) in the 2-inch discharge line: Min Velocity = 2.0 fps in 2" pipe ⟹ Min Pump Rate ≈ 21 GPM \text{Min Velocity} = 2.0 \text{ fps in 2" pipe} \implies \text{Min Pump Rate} \approx 21 \text{ GPM} Min Velocity = 2.0 fps in 2" pipe ⟹ Min Pump Rate ≈ 21 GPM

Standard sewage ejector pumps are specified to deliver 20 to 30 GPM at a minimum 15 to 20 feet of Total Dynamic Head (TDH) .

Duplex Systems: In commercial buildings, public facilities, or multi-family dwellings, duplex pump systems (two pumps installed in a single basin) are mandatory. The control panel automatically alternates pump duty and activates both pumps simultaneously if a high-water alarm is triggered.

Backwater Valves (UPC Section 710.1)

A backwater valve is a mechanical check valve installed in a drainage branch to prevent public sewer surcharges from backing up into basement plumbing fixtures during torrential rainstorms or municipal main blockages. STREET LEVEL MANHOLE COVER ELEVATION

  • ═════════════════════════════
  • │
  • FLOOD LEVEL RIM │ PUBLIC SEWER SURCHARGE LEVEL
  • OF BASEMENT SINK │
  • ─────────┬─────── ▼
  • │ (Sewer Surcharge Hazard Zone!)
  • ▼
  • ┌──────────────────────┐
  • │ Basement Fixture │ ───► [ BACKWATER VALVE ] ───► Public Sewer Main
  • │ (Protected Branch) │ (Flap Closes on Backflow)
  • └──────────────────────┘
  • The base rule and the Iowa amendment (UPC Section 710.1)

The model UPC rule is familiar: drainage piping serving fixtures whose flood level rims are below the elevation of the cover of the next upstream manhole of the public sewer must be protected from backflow.

Important

Iowa rewrites the trigger and the hardware. Rule 481—425.4(5)"b" adds to Section 710.1: "The requirement for the installation of a backwater valve shall apply only when determined necessary by the Authority Having Jurisdiction based on local conditions. When a valve is required by the Authority Having Jurisdiction, it will be a manually operated gate valve or fullway ball valve . An automatic backwater valve may also be installed but is not required ."

Two exam-relevant consequences follow. First, in Iowa the below-manhole geometry alone does not make a backwater valve mandatory — the AHJ's determination does. Second, the device the Iowa code names is a manual gate or fullway ball valve; the spring- or gravity-operated automatic flap valve is optional additional protection, not the required item. Answers written from the unamended UPC will read "an approved automatic backwater valve is required," and on an Iowa exam that is the wrong answer.

Construction and Operation

Backwater valves feature a smooth internal body containing a weighted, floating, or spring-assisted mechanical flap (gate).

Under normal forward flow, wastewater pushes the flap open.

When the public sewer surcharges and wastewater flows backward, hydrostatic head forces the flap tightly against its seat, sealing off the building interior.

Caution

Upper-Floor Isolation Rule (UPC 710.1): Fixtures located above the upstream manhole cover MUST NOT drain through the backwater valve! They must bypass the backwater valve and connect directly to the building drain downstream. If upper-floor fixtures drain through a closed backwater valve during a storm, the upper-floor discharge will overflow out of the lowest basement fixtures, completely defeating the valve's purpose.