8.2 Sizing Roof Drains, Leaders & Vertical Rainwater Piping (UPC Table 1103.1)
Iowa Journeyperson Plumber Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Iowa Licensing, Exam Format, Code Adoption & UPC General Regulations
1.1 Iowa Licensing Tiers, PMSB Rules, Code Adoption, Permits & Inspections 1.2 UPC Chapter 3 General Regulations: Trenching, Protection of Piping & Iowa Burial Depths 1.3 Plumbing Mathematics, Pipe Sizing Formulas & Blueprint Reading 1.4 Hangers, Supports, Pipe Joints, and Material Compatibility 1.5 Exam Format, Approved References & Open-Book Lookup Strategy
2 Chapter 2: Plumbing Fixtures & Fixture Fittings (UPC Chapter 4)
2.1 Fixture Unit Values & Iowa Minimum Plumbing Fixture Requirements 2.2 Water Closets, Urinals, Bidets & Lavatories 2.3 Bathtubs, Showers, Sinks & Food Prep Fixtures 2.4 Plumbing Fixture Installation Standards & ADA Accessibility 2.5 Specialty Appliances, Floor Drains, Indirect Waste & Interceptors
3 Chapter 3: Sanitary Drainage & Building Sewers (UPC Chapter 7)
3.1 Sanitary Drainage System Components, Layout & Gravity Flow Principles 3.2 Drainage Fixture Unit (DFU) Values & Horizontal/Vertical Sizing 3.3 Building Sewers, Building Drains & Sewer Connection Standards 3.4 Drain Slopes, Velocities & Changes of Direction (UPC 706.0 and 708.0) 3.5 Cleanouts: Placement, Sizing, Clearances & Access Requirements 3.6 Sump Pumps, Sewage Ejectors & Backwater Valves 3.7 Drainage Materials, Joints, Prohibited Practices & DWV Testing 3.8 Sizing a Complete DWV System: Two Worked Walkthroughs
4 Chapter 4: Venting Systems (UPC Chapter 9)
4.1 Venting Fundamentals, Trap Seal Protection & the Iowa Trap Arm Table 4.2 Vent Sizing from UPC Table 703.2, Vent Stacks & Yoke Vents 4.3 Wet Venting Under UPC Section 908 and the Iowa Sizing Amendment 4.4 Venting Fixture Batteries: Common Vents, Relief Vents & Why Circuit Venting Is Not an Iowa Method 4.5 Air Admittance Valves, Combination Waste & Vent, and Island Venting 4.6 Vent Termination, Roof Penetrations & Flashings 4.7 Applying the Vent Rules: Worked Venting Walkthroughs 4.8 Diagnosing Venting Failures: Symptom-to-Cause Troubleshooting
5 Chapter 5: Traps, Interceptors & Indirect Waste (UPC Chapters 8 and 10)
5.1 Trap Design, Seals, Prohibited Traps & Trap Primers 5.2 Indirect & Special Waste Receptors and Air Gaps 5.3 Grease Interceptors & Trap Sizing (Hydromechanical & Gravity) 5.4 Oil, Sand, Flammable Liquid & Chemical Interceptors
6 Chapter 6: Water Supply & Distribution (UPC Chapter 6)
6.1 Water Service Piping, Main Sizing & Meter Installation 6.2 Water Supply Fixture Units (WSFU) & Pipe Sizing Calculations 6.3 Water Pressure Regulators, Pressure Relief & Thermal Expansion 6.4 Backflow Prevention: Cross-Connection Control & Device Selection 6.5 Potable Water Pipe Materials, Valves & Disinfection
7 Chapter 7: Water Heaters (UPC Chapter 5)
7.1 Water Heater Types, Sizing, Recovery Rate & First-Hour Rating 7.2 Water Heater Safety: T&P Relief Valves, Drain Pans, Combustion Air & Anti-Scald Controls 7.3 Water Heater Venting: Appliance Categories, Vent Connectors, Chimneys & Terminations 7.4 Water Heater Location, Clearances, Supports, Replacement & Iowa Amendments
8 Chapter 8: Storm Drainage (UPC Chapter 11)
8.1 Storm Drainage Scope, Materials, Traps & Prohibited Connections 8.2 Sizing Roof Drains, Leaders & Vertical Rainwater Piping (UPC Table 1103.1) 8.3 Sizing Horizontal Storm Drains, Storm Sewers & Gutters (UPC Tables 1103.2 and 1103.3) 8.4 Side Walls Draining Onto a Roof, Secondary Roof Drainage & Controlled-Flow Roofs 8.5 Subsoil Drains, Areaway Drains, Storm Sumps & Building Storm Sewers
9 Chapter 9: Fuel Gas Piping & Appliance Venting (UPC Chapter 12)
7.1 Iowa Fuel Gas Authority (UPC Chapter 12), Gas Properties, System Types & Regulators 7.2 Gas Pipe Sizing Calculations, Longest Length & Branch Method 7.3 Gas Pipe Materials, Joining, CSST Rules Under the Iowa Amendments, Outlets & Valves 7.4 Fuel Gas Appliance Installation, Clearances & Combustion Air 7.5 Fuel Gas Venting Systems, Chimneys & Safety Testing
8.2 Sizing Roof Drains, Leaders & Vertical Rainwater Piping (UPC Table 1103.1)
Key Takeaways Explain This Topic AI
UPC Section 1103.1 sizes vertical conductors and leaders from the maximum projected roof area using Table 1103.1.
At a 1 inch per hour rainfall rate, Table 1103.1 allows 2,880 square feet on a 2-inch leader, 8,800 on a 3-inch, 18,400 on a 4-inch, 34,600 on a 5-inch, 54,000 on a 6-inch, and 116,000 on an 8-inch.
For a rainfall rate the table does not list, divide the area in the 1 inch per hour column by the desired rainfall rate.
The flow column of Table 1103.1 is the maximum discharge capacity in gallons per minute with approximately 1-3/4 inches of head of water at the drain.
Vertical rainwater piping may be round, square, or rectangular; a rectangular leader must have at least the same cross-sectional area as its equivalent round pipe and a side ratio not exceeding 3 to 1.
Last updated: August 2026
- Sizing Roof Drains, Leaders & Vertical Rainwater Piping
- The one sentence that drives this section
UPC Section 1103.1 : vertical conductors and leaders shall be sized by the maximum projected roof area and Table 1103.1.
Two inputs, one table, one answer. The whole difficulty is in reading the table correctly and in getting the projected area right.
1. Projected roof area, not surface area
" Maximum projected horizontal roof area " means the area of the roof as it would appear looking straight down — its footprint , not the sloped surface. A gable roof measuring 40 feet by 60 feet in plan drains 2,400 square feet no matter how steep the pitch, because rain falls vertically and a steeper roof simply catches the same column of water over a smaller sloped area.
This is the first place candidates lose the question. If a problem gives you rafter length and building width, convert to plan dimensions before you touch the table.
2. Table 1103.1 — Sizing Roof Drains, Leaders, and Vertical Rainwater Piping
Maximum allowable horizontal projected roof area, in square feet:
- Size (in) Flow (gpm) 1 in/h 2 in/h 3 in/h 4 in/h 5 in/h 6 in/h 8 in/h 10 in/h 12 in/h
- 2 30 2,880 1,440 960 720 575 480 360 290 240
- 3 92 8,800 4,400 2,930 2,200 1,760 1,470 1,100 880 730
- 4 192 18,400 9,200 6,130 4,600 3,680 3,070 2,300 1,840 1,530
- 5 360 34,600 17,300 11,530 8,650 6,920 5,765 4,325 3,460 2,880
- 6 563 54,000 27,000 17,995 13,500 10,800 9,000 6,750 5,400 4,500
- 8 1,208 116,000 58,000 38,660 29,000 23,200 19,315 14,500 11,600 9,600
(The published table also carries 7, 9, and 11 inch-per-hour columns; the rows above are the ones worth committing to memory as anchors.)
The three notes that turn into questions
The gpm column is a capacity, measured under a stated condition. It is the maximum discharge capacity in gallons per minute with approximately 1-3/4 inches (44 mm) of head of water at the drain . That head figure is the reason a 4-inch roof drain body is rated at 192 gpm here and a 4-inch horizontal storm drain at 1/8 inch per foot is rated at only 78 gpm in the next table — vertical flow with head behind it moves far more water than a partly full horizontal pipe.
Unlisted rainfall rates are a division problem. For rainfall rates other than those listed, determine the allowable roof area by dividing the area given in the 1 inch per hour column by the desired rainfall rate. At 2.5 inches per hour, a 4-inch leader handles 18,400 ÷ 2.5 = 7,360 square feet .
Shape is flexible; area is not. Vertical piping may be round, square, or rectangular . A square leader is sized to enclose its equivalent round pipe. A rectangular leader must have not less than the same cross-sectional area as its equivalent round pipe, and the ratio of its side dimensions shall not exceed 3 to 1 — so a 2-inch by 6-inch rectangular leader is at the limit, and a 2-inch by 8-inch is not permitted.
3. Worked example: a warehouse roof
Given: a warehouse measuring 180 feet by 240 feet in plan, drained by six roof drains that split the roof evenly. Design rainfall rate 3 inches per hour . Size the leaders.
Total projected area: 180 × 240 = 43,200 square feet .
Area per drain: 43,200 ÷ 6 = 7,200 square feet .
Read the 3 in/h column for a value at or above 7,200:
4-inch handles 6,130 — too small.
5-inch handles 11,530 — adequate.
Answer: 5-inch leaders , and each roof drain body is sized to match.
Now change one variable. If the design rate is 2.5 inches per hour instead, use note 2: a 4-inch leader handles 18,400 ÷ 2.5 = 7,360 square feet, which now covers 7,200. 4-inch leaders suffice. A half-inch per hour of design rainfall changed the pipe size for the whole building — which is why the rainfall rate is never a detail to skim past.
4. Choosing the rainfall rate in Iowa
Storm systems are designed to a 100-year, 1-hour rainfall rate for the building's location, and the design rate is set by the AHJ or the design documents. Iowa's design rates generally fall in the 3 to 4 inch per hour range, and a local ordinance may specify a value or a return period different from the state default.
Two exam habits follow. First, if the problem states a rate, use the stated rate — never substitute a number you remember from another jurisdiction. Second, if the problem states a city and no rate , the intended answer is almost always the rate printed in whatever rainfall table the exam expects you to consult, so look for it rather than guessing.
5. A checklist for any vertical storm sizing question
Convert to projected horizontal area .
Divide by the number of drains if the roof is split.
Add anything Section 8.4 requires for vertical walls draining onto the roof.
Find the rainfall rate column, or divide the 1 in/h value by the rate.
Read down the size column to the first row that equals or exceeds your area.
Confirm the drain body, the leader, and everything downstream never decreases in the direction of flow.