8.3 Sizing Horizontal Storm Drains, Storm Sewers & Gutters (UPC Tables 1103.2 and 1103.3)
Iowa Journeyperson Plumber Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Iowa Licensing, Exam Format, Code Adoption & UPC General Regulations
1.1 Iowa Licensing Tiers, PMSB Rules, Code Adoption, Permits & Inspections 1.2 UPC Chapter 3 General Regulations: Trenching, Protection of Piping & Iowa Burial Depths 1.3 Plumbing Mathematics, Pipe Sizing Formulas & Blueprint Reading 1.4 Hangers, Supports, Pipe Joints, and Material Compatibility 1.5 Exam Format, Approved References & Open-Book Lookup Strategy
2 Chapter 2: Plumbing Fixtures & Fixture Fittings (UPC Chapter 4)
2.1 Fixture Unit Values & Iowa Minimum Plumbing Fixture Requirements 2.2 Water Closets, Urinals, Bidets & Lavatories 2.3 Bathtubs, Showers, Sinks & Food Prep Fixtures 2.4 Plumbing Fixture Installation Standards & ADA Accessibility 2.5 Specialty Appliances, Floor Drains, Indirect Waste & Interceptors
3 Chapter 3: Sanitary Drainage & Building Sewers (UPC Chapter 7)
3.1 Sanitary Drainage System Components, Layout & Gravity Flow Principles 3.2 Drainage Fixture Unit (DFU) Values & Horizontal/Vertical Sizing 3.3 Building Sewers, Building Drains & Sewer Connection Standards 3.4 Drain Slopes, Velocities & Changes of Direction (UPC 706.0 and 708.0) 3.5 Cleanouts: Placement, Sizing, Clearances & Access Requirements 3.6 Sump Pumps, Sewage Ejectors & Backwater Valves 3.7 Drainage Materials, Joints, Prohibited Practices & DWV Testing 3.8 Sizing a Complete DWV System: Two Worked Walkthroughs
4 Chapter 4: Venting Systems (UPC Chapter 9)
4.1 Venting Fundamentals, Trap Seal Protection & the Iowa Trap Arm Table 4.2 Vent Sizing from UPC Table 703.2, Vent Stacks & Yoke Vents 4.3 Wet Venting Under UPC Section 908 and the Iowa Sizing Amendment 4.4 Venting Fixture Batteries: Common Vents, Relief Vents & Why Circuit Venting Is Not an Iowa Method 4.5 Air Admittance Valves, Combination Waste & Vent, and Island Venting 4.6 Vent Termination, Roof Penetrations & Flashings 4.7 Applying the Vent Rules: Worked Venting Walkthroughs 4.8 Diagnosing Venting Failures: Symptom-to-Cause Troubleshooting
5 Chapter 5: Traps, Interceptors & Indirect Waste (UPC Chapters 8 and 10)
5.1 Trap Design, Seals, Prohibited Traps & Trap Primers 5.2 Indirect & Special Waste Receptors and Air Gaps 5.3 Grease Interceptors & Trap Sizing (Hydromechanical & Gravity) 5.4 Oil, Sand, Flammable Liquid & Chemical Interceptors
6 Chapter 6: Water Supply & Distribution (UPC Chapter 6)
6.1 Water Service Piping, Main Sizing & Meter Installation 6.2 Water Supply Fixture Units (WSFU) & Pipe Sizing Calculations 6.3 Water Pressure Regulators, Pressure Relief & Thermal Expansion 6.4 Backflow Prevention: Cross-Connection Control & Device Selection 6.5 Potable Water Pipe Materials, Valves & Disinfection
7 Chapter 7: Water Heaters (UPC Chapter 5)
7.1 Water Heater Types, Sizing, Recovery Rate & First-Hour Rating 7.2 Water Heater Safety: T&P Relief Valves, Drain Pans, Combustion Air & Anti-Scald Controls 7.3 Water Heater Venting: Appliance Categories, Vent Connectors, Chimneys & Terminations 7.4 Water Heater Location, Clearances, Supports, Replacement & Iowa Amendments
8 Chapter 8: Storm Drainage (UPC Chapter 11)
8.1 Storm Drainage Scope, Materials, Traps & Prohibited Connections 8.2 Sizing Roof Drains, Leaders & Vertical Rainwater Piping (UPC Table 1103.1) 8.3 Sizing Horizontal Storm Drains, Storm Sewers & Gutters (UPC Tables 1103.2 and 1103.3) 8.4 Side Walls Draining Onto a Roof, Secondary Roof Drainage & Controlled-Flow Roofs 8.5 Subsoil Drains, Areaway Drains, Storm Sumps & Building Storm Sewers
9 Chapter 9: Fuel Gas Piping & Appliance Venting (UPC Chapter 12)
7.1 Iowa Fuel Gas Authority (UPC Chapter 12), Gas Properties, System Types & Regulators 7.2 Gas Pipe Sizing Calculations, Longest Length & Branch Method 7.3 Gas Pipe Materials, Joining, CSST Rules Under the Iowa Amendments, Outlets & Valves 7.4 Fuel Gas Appliance Installation, Clearances & Combustion Air 7.5 Fuel Gas Venting Systems, Chimneys & Safety Testing
8.3 Sizing Horizontal Storm Drains, Storm Sewers & Gutters (UPC Tables 1103.2 and 1103.3)
Key Takeaways Explain This Topic AI
UPC Section 1103.2 sizes building storm drains, storm sewers, and their horizontal branches from the maximum projected roof or paved area using Table 1103.2.
Table 1103.2 is divided into three slope blocks — 1/8, 1/4, and 1/2 inch per foot — and the sizing data are based on the pipes flowing full.
At 1 inch per hour and 1/8 inch per foot slope, Table 1103.2 allows 3,288 square feet on 3-inch, 7,520 on 4-inch, 13,360 on 5-inch, 21,400 on 6-inch, and 46,000 on 8-inch pipe.
Doubling the slope from 1/8 to 1/4 inch per foot raises the capacity of a given horizontal storm pipe by roughly 40 percent.
UPC Section 1103.3 sizes semi-circular gutters from Table 1103.3, which is organized by gutter diameter, slope, and rainfall rate.
Last updated: August 2026
- Sizing Horizontal Storm Drains, Storm Sewers & Gutters
- The horizontal table works differently from the vertical one
Vertical rainwater piping runs with head behind it and does not care about slope. Horizontal storm piping runs on grade, and UPC Table 1103.2 is therefore divided into three separate slope blocks : 1/8 inch per foot, 1/4 inch per foot, and 1/2 inch per foot. Note 1 to the table states the assumption behind the numbers — the sizing data for horizontal piping are based on the pipes flowing full , which is the opposite of the half-full assumption behind sanitary drainage sizing.
UPC Section 1103.2 : the size of building storm drains, or building storm sewers or their horizontal branches shall be based on the maximum projected roof or paved area to be handled and Table 1103.2. Note that phrase — roof or paved area . Parking lots, plazas, drives, and courts feed the same table as roofs.
1. Table 1103.2 — Sizing of Horizontal Rainwater Piping
Maximum allowable horizontal projected roof area, in square feet:
At 1/8 inch per foot slope
- Size (in) Flow (gpm) 1 in/h 2 in/h 3 in/h 4 in/h 5 in/h 6 in/h
- 3 34 3,288 1,644 1,096 822 657 548
- 4 78 7,520 3,760 2,506 1,880 1,504 1,253
- 5 139 13,360 6,680 4,453 3,340 2,672 2,227
- 6 222 21,400 10,700 7,133 5,350 4,280 3,566
- 8 478 46,000 23,000 15,330 11,500 9,200 7,670
- 10 860 82,800 41,400 27,600 20,700 16,580 13,800
- 12 1,384 133,200 66,600 44,400 33,300 26,650 22,200
- At 1/4 inch per foot slope
- Size (in) Flow (gpm) 1 in/h 2 in/h 3 in/h 4 in/h 5 in/h 6 in/h
- 3 48 4,640 2,320 1,546 1,160 928 773
- 4 110 10,600 5,300 3,533 2,650 2,120 1,766
- 5 196 18,880 9,440 6,293 4,720 3,776 3,146
- 6 314 30,200 15,100 10,066 7,550 6,040 5,033
- 8 677 65,200 32,600 21,733 16,300 13,040 10,866
- 10 1,214 116,800 58,400 38,950 29,200 23,350 19,450
- 12 1,953 188,000 94,000 62,600 47,000 37,600 31,350
- At 1/2 inch per foot slope
- Size (in) Flow (gpm) 1 in/h 2 in/h 3 in/h 4 in/h 5 in/h 6 in/h
- 3 68 6,576 3,288 2,192 1,644 1,310 1,096
- 4 156 15,040 7,520 5,010 3,760 3,010 2,500
- 5 278 26,720 13,360 8,900 6,680 5,320 4,450
- 6 445 42,800 21,400 14,267 10,700 8,580 7,140
- 8 956 92,000 46,000 30,650 23,000 18,400 15,320
The pattern worth internalizing: going from 1/8 to 1/4 inch per foot buys about 40 percent more capacity; going from 1/8 to 1/2 buys about 100 percent . And notice the symmetry across the table — the 1/8 inch per foot 1 in/h value equals the 1/4 inch per foot 2 in/h value doubled, and so on. Note 2 gives the same division rule as the vertical table: for rainfall rates other than those listed, divide the area in the 1 inch per hour column by the desired rate.
2. Worked example: an office building storm drain
Given: a 22,000 square foot roof plus a 14,000 square foot paved parking area, both draining into one building storm drain. Design rainfall 3 inches per hour . The drain is run at 1/8 inch per foot because the storm sewer is shallow.
Total area: 22,000 + 14,000 = 36,000 square feet (Section 1103.2 covers roof or paved area).
Read the 1/8 inch per foot block, 3 in/h column:
8-inch handles 15,330 — too small.
10-inch handles 27,600 — still too small.
12-inch handles 44,400 — adequate.
Answer at 1/8 inch per foot: 12 inches.
Now re-grade it. If the run can be pitched at 1/4 inch per foot , the 10-inch line handles 38,950 square feet, which covers 36,000. 10 inches. Two extra inches of fall per 8 feet of run saved a pipe size across the whole building — the kind of trade-off a good estimator makes before the trench is dug.
3. Gutters — UPC Section 1103.3 and Table 1103.3
Section 1103.3 : the size of semi-circular gutters shall be based on the maximum projected roof area and Table 1103.3. Gutters get their own table because an open channel behaves differently from a closed pipe, and because gutters are commonly run at very flat slopes.
Maximum roof area in square feet, semi-circular gutters:
- Gutter diameter (in) 1/16 in/ft @ 4 in/h 1/8 in/ft @ 4 in/h 1/4 in/ft @ 4 in/h 1/2 in/ft @ 4 in/h
- 4 360 510 720 1,020
- 5 625 880 1,250 1,770
- 6 960 1,360 1,920 2,770
- 8 1,990 2,800 3,980 5,600
- 10 3,600 5,100 7,200 10,000
Read across a single row and the slope effect is obvious: a 6-inch gutter carries 960 square feet at 1/16 inch per foot and 2,770 square feet at 1/2 inch per foot for the same 4-inch-per-hour rain — nearly triple. Read down a column and the diameter effect is equally sharp. The full published table covers 3 through 10 inch gutters at 2, 3, 4, 5, and 6 inches per hour for each of four slopes; find it, tab it, and read the correct block.
4. Three rules that outrank the tables
Never reduce size in the direction of flow. If a vertical leader computes to 5 inches and the horizontal drain it lands in computes to 4, the horizontal drain is still 5 inches.
Combine before you size. A horizontal branch collecting three leaders carries the sum of their tributary areas, not the largest one.
Use the stated slope. Half the wrong answers on horizontal storm questions come from reading the 1/4 inch per foot block when the problem said 1/8.