3.2 Accessible Entrances: Number, Location, and Power-Operated Doors
ICC Accessibility Inspector / Plans Examiner 21
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: General Administrative and Scoping Provisions
1.1 Occupancy Group Accessibility and IBC Chapter 11 Scoping 1.2 General Administration: Definitions, Conventions, and Code Editions 1.3 Existing Buildings: IEBC Section 306 Alterations, Additions, and Changes of Occupancy 1.4 Technical Infeasibility, Existing-Building Ramps, and Historic Structures
2 Chapter 2: Building Blocks (ICC A117.1 Chapter 3)
2.1 Walking and Floor Surfaces, Openings, and Level Changes 2.2 Turning Space and Clear Floor Space: New Versus Existing Buildings 2.3 Knee and Toe Clearances 2.4 Unobstructed and Obstructed Reach Ranges 2.5 Protruding Objects and Vertical Clearance
3 Chapter 3: Accessible Routes — Route Scoping, Entrances, and Doors
3.1 Accessible Route Scoping, Components, Slopes, and Clear Width 3.2 Accessible Entrances: Number, Location, and Power-Operated Doors 3.3 Doors, Doorways, and Gates: Clear Width and Maneuvering Clearances 3.4 Door Hardware, Forces, Closing Speed, Door Surfaces, and Windows
4 Chapter 4: Accessible Routes — Ramps, Curb Ramps, and Conveyance
4.1 Ramps: Slopes, Landings, and Clearances 4.2 Ramp Handrails, Edge Protection, and Cross Slopes 4.3 Curb Ramps, Blended Transitions, and Detectable Warnings at Crossings 4.4 Elevators, LULA Elevators, and Platform Lifts
5 Chapter 5: Accessible Means of Egress
5.1 Accessible Means of Egress: Number, Components, Elevators, and Stairways 5.2 Elevators, Platform Lifts, Areas of Refuge, and Exterior Areas for Assisted Rescue 5.3 Two-Way Communication, Egress Signage, and Instructions
6 Chapter 6: General Site and Building Elements
6.1 Accessible Parking: Scoping, Van Spaces, Dimensions, and Signs 6.2 Passenger Loading Zones, Bus Stops, and Rail Platforms 6.3 Site Accessibility: Site Routes, Routes Through Parking, EV Charging, and Fuel Dispensers 6.4 Stairways: Treads, Risers, Nosings, Visual Contrast, and Lighting 6.5 Stair Handrails: Location, Height, Profile, Continuity, and Extensions
7 Chapter 7: Plumbing Elements and Facilities
7.1 Water Closets and Toilet Compartments 7.2 Grab Bars: Locations, Cross Sections, Spacing, Strength, and Assisted Toileting 7.3 Toilet Rooms, Lavatories, Sinks, Mirrors, Urinals, and Accessories 7.4 Bathtubs, Shower Compartments, and Seats 7.5 Plumbing Scoping: Family Rooms, Adult Changing Stations, Drinking Fountains, Laundry, and Saunas
8 Chapter 8: Communication Elements and Features
8.1 Visible Alarms and Assistive Listening Systems 8.2 Accessible Signage: Visual Characters, Raised Characters, Braille, Pictograms, and Symbols 8.3 Telephones, ATMs and Fare Machines, Two-Way Communication Systems, and Detectable Warnings
9 Chapter 9: Special Rooms and Spaces
9.1 Assembly Areas: Wheelchair Spaces, Companion Seats, Dispersion, and Lines of Sight 9.2 Dressing and Locker Rooms, Courtrooms, Detention Cells, Self-Storage, and Classroom Acoustics 9.3 Kitchens and Kitchenettes
10 Chapter 10: Built-in Furnishings and Equipment
10.1 Dining Surfaces and Work Surfaces 10.2 Sales and Service Counters and Windows 10.3 Check-Out Aisles, Food Service Lines, Benches, Storage, Charging Stations, and Gaming
11 Chapter 11: Dwelling and Sleeping Units
11.1 Scoping Accessible, Type A, and Type B Units (IBC 1108) 11.2 Type A Units (A117.1 Section 1103) 11.3 Type B Units (A117.1 Section 1104) 11.4 Accessible Units: Hotels, Dormitories, Health Care and Residential Care (A117.1 Section 1102) 11.5 Type C (Visitable) Units and Units with Communication Features
12 Chapter 12: Recreational Facilities
12.1 Swimming Pools, Wading Pools, Hot Tubs, and Spas 12.2 Play Areas and Amusement Rides 12.3 Sports Facilities, Exercise Equipment, Golf, Boating, Fishing, and Shooting Facilities
3.2 Accessible Entrances: Number, Location, and Power-Operated Doors
Key Takeaways Explain This Topic AI
At least 60 percent of all public entrances must be accessible, in addition to the specific entrances required by IBC 1105.1.2 through 1105.1.8.
In A occupancies with a building occupant load over 300, and B, M or R-1 over 500, each accessible public entrance needs a power-operated or low-energy power-operated door (Table 1105.1.1).
Direct pedestrian access from parking structures, tunnels and elevated walkways must be accessible, and at least one restricted entrance, detainee entrance and each tenant must have an accessible entrance.
A service entrance must be accessible only if it is the only entrance to the building or tenant space.
Where not all entrances are accessible, accessible entrances get the International Symbol of Accessibility and inaccessible entrances get directional signs (IBC 1112.1 and 1112.3).
Last updated: October 2026
3.2 Accessible Entrances: Number, Location, and Power-Operated Doors
Accessible Entrances is a 4% subtopic on the ICC 21 outline: "verify compliance of the number and location of accessible entrances." The scoping is in IBC Section 1105 , signage is in IBC Section 1112 , and the door hardware, vestibule and automatic door criteria are in A117.1 Section 404 .
Public Entrances (1105.1)
In addition to accessible entrances required by Sections 1105.1.2 through 1105.1.8, at least 60 percent of all public entrances shall be accessible.
Exceptions: an accessible entrance is not required to areas not required to be accessible, and loading and service entrances that are not the only entrance to a tenant space are not counted.
The 60% rule is calculated on public entrances. Because the code says at least 60 percent, round any fraction up: a building with 4 public entrances needs 0.60 x 4 = 2.4, so 3 must be accessible; a building with 5 public entrances needs exactly 3.
Power-Operated Doors (1105.1.1)
The 2021 IBC introduced automatic door requirements at public entrances, and the 2024 IBC retitled them "power-operated doors at public entrances."
- Occupancy Building occupant load greater than
- A-1, A-2, A-3, A-4 300
- B, M, R-1 500
Where the threshold is exceeded, each public entrance required to be accessible must have at least one door that is a full power-operated door or a low-energy power-operated door. Where the entrance includes a vestibule, the 2021 IBC requires at least one door into and one door out of the vestibule to comply; the 2024 IBC requires one set of two doors in series to comply. The 2024 edition adds two exceptions: a tenant space with its own exterior public entrance is treated as a separate building, and in mixed-use buildings the requirement does not apply where the sum of the ratios of each occupancy's load to its threshold is less than 1.
A117.1 Section 404.3.1 states that where an automatic door is required at a public entrance, it must be a full powered automatic or low-energy automatic door (power-assist doors do not satisfy it). Section 404.3.2 requires that, where an entrance includes a vestibule, at least one exterior and one interior vestibule door have the same type of automatic opener. Full powered doors follow ANSI/BHMA A156.10; power-assist and low-energy doors follow A156.19.
Specific Entrances (1105.1.2 to 1105.1.8)
Section Entrance Requirement
1105.1.2 Parking garage Where provided, direct pedestrian access from parking structures to building entrances must be accessible
1105.1.3 Tunnels and elevated walkways At least one entrance from each tunnel or walkway must be accessible
1105.1.4 Restricted entrances (used only by tenants, employees or a select group) At least one restricted entrance must be accessible
1105.1.5 Inmate and detainee entrances at judicial, detention and correctional facilities At least one such entrance must be accessible
1105.1.6 Service entrances Must be accessible only if it is the only entrance to a building or tenant space
1105.1.7 Tenant spaces At least one accessible entrance to each tenant ; not required for self-service storage facilities not required to be accessible
1105.1.8 Dwelling and sleeping units At least one accessible entrance to each unit, except units not required to be Accessible, Type A or Type B units
Entrance Signage (IBC 1112)
1112.1 Item 5 : Accessible entrances must be identified by the International Symbol of Accessibility where not all entrances are accessible.
1112.3 Item 1 : Directional signs at inaccessible building entrances indicate the route to the nearest accessible entrance, include the International Symbol of Accessibility, and use visual characters complying with A117.1.
If every entrance is accessible, no ISA sign is needed at the entrances.
A117.1 Provisions at Entrance Doors
Topic Section Requirement
Doors in series (vestibules) 404.2.5 48 in. minimum between doors plus the width of any door swinging into the space; the space between the doors must provide a turning space
Automatic doors in series 404.3.6 Exception Where both doors are low-energy or full power automatic doors, a turning space between them is not required
Automatic door clear width 404.3.3 32 in. in power-on and power-off modes
Controls for automatic doors 404.3.7 Comply with 309; the clear floor space at the control must be beyond the arc of the door swing
- Thresholds 404.2.4 1/2 in. maximum (existing or altered thresholds up to 3/4 in. with beveled edges)
- Revolving doors and turnstiles 402.3 Not part of an accessible route
- Worked Example
A new 620-occupant Group M store has five public entrances, a separate loading dock door and a tenant-only employee entrance from the parking garage.
Public entrances: 60% of 5 = 3 accessible public entrances.
The store is Group M with an occupant load over 500, so each of the three accessible public entrances needs at least one power-operated or low-energy power-operated door. If an entrance has a vestibule, the vestibule doors comply as the edition requires.
The garage entrance is direct pedestrian access from a parking structure, so it must be accessible (1105.1.2).
The loading dock is not the only entrance, so it need not be accessible.
ISA signs identify the accessible entrances, and directional signs at the two inaccessible public entrances point to the nearest accessible one.
Exam Traps
The 60% count excludes loading and service entrances that are not the only entrance.
The occupant load thresholds are "greater than" 300 and 500; exactly 300 does not trigger the A requirement.
A service entrance used as the only entrance to a tenant space must be accessible.
Turning space, not merely clear floor space, is required between manual doors in series.