6.4 Stairways: Treads, Risers, Nosings, Visual Contrast, and Lighting

ICC Accessibility Inspector / Plans Examiner 21

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: General Administrative and Scoping Provisions

1.1 Occupancy Group Accessibility and IBC Chapter 11 Scoping 1.2 General Administration: Definitions, Conventions, and Code Editions 1.3 Existing Buildings: IEBC Section 306 Alterations, Additions, and Changes of Occupancy 1.4 Technical Infeasibility, Existing-Building Ramps, and Historic Structures

2 Chapter 2: Building Blocks (ICC A117.1 Chapter 3)

2.1 Walking and Floor Surfaces, Openings, and Level Changes 2.2 Turning Space and Clear Floor Space: New Versus Existing Buildings 2.3 Knee and Toe Clearances 2.4 Unobstructed and Obstructed Reach Ranges 2.5 Protruding Objects and Vertical Clearance

3 Chapter 3: Accessible Routes — Route Scoping, Entrances, and Doors

3.1 Accessible Route Scoping, Components, Slopes, and Clear Width 3.2 Accessible Entrances: Number, Location, and Power-Operated Doors 3.3 Doors, Doorways, and Gates: Clear Width and Maneuvering Clearances 3.4 Door Hardware, Forces, Closing Speed, Door Surfaces, and Windows

4 Chapter 4: Accessible Routes — Ramps, Curb Ramps, and Conveyance

4.1 Ramps: Slopes, Landings, and Clearances 4.2 Ramp Handrails, Edge Protection, and Cross Slopes 4.3 Curb Ramps, Blended Transitions, and Detectable Warnings at Crossings 4.4 Elevators, LULA Elevators, and Platform Lifts

5 Chapter 5: Accessible Means of Egress

5.1 Accessible Means of Egress: Number, Components, Elevators, and Stairways 5.2 Elevators, Platform Lifts, Areas of Refuge, and Exterior Areas for Assisted Rescue 5.3 Two-Way Communication, Egress Signage, and Instructions

6 Chapter 6: General Site and Building Elements

6.1 Accessible Parking: Scoping, Van Spaces, Dimensions, and Signs 6.2 Passenger Loading Zones, Bus Stops, and Rail Platforms 6.3 Site Accessibility: Site Routes, Routes Through Parking, EV Charging, and Fuel Dispensers 6.4 Stairways: Treads, Risers, Nosings, Visual Contrast, and Lighting 6.5 Stair Handrails: Location, Height, Profile, Continuity, and Extensions

7 Chapter 7: Plumbing Elements and Facilities

7.1 Water Closets and Toilet Compartments 7.2 Grab Bars: Locations, Cross Sections, Spacing, Strength, and Assisted Toileting 7.3 Toilet Rooms, Lavatories, Sinks, Mirrors, Urinals, and Accessories 7.4 Bathtubs, Shower Compartments, and Seats 7.5 Plumbing Scoping: Family Rooms, Adult Changing Stations, Drinking Fountains, Laundry, and Saunas

8 Chapter 8: Communication Elements and Features

8.1 Visible Alarms and Assistive Listening Systems 8.2 Accessible Signage: Visual Characters, Raised Characters, Braille, Pictograms, and Symbols 8.3 Telephones, ATMs and Fare Machines, Two-Way Communication Systems, and Detectable Warnings

9 Chapter 9: Special Rooms and Spaces

9.1 Assembly Areas: Wheelchair Spaces, Companion Seats, Dispersion, and Lines of Sight 9.2 Dressing and Locker Rooms, Courtrooms, Detention Cells, Self-Storage, and Classroom Acoustics 9.3 Kitchens and Kitchenettes

10 Chapter 10: Built-in Furnishings and Equipment

10.1 Dining Surfaces and Work Surfaces 10.2 Sales and Service Counters and Windows 10.3 Check-Out Aisles, Food Service Lines, Benches, Storage, Charging Stations, and Gaming

11 Chapter 11: Dwelling and Sleeping Units

11.1 Scoping Accessible, Type A, and Type B Units (IBC 1108) 11.2 Type A Units (A117.1 Section 1103) 11.3 Type B Units (A117.1 Section 1104) 11.4 Accessible Units: Hotels, Dormitories, Health Care and Residential Care (A117.1 Section 1102) 11.5 Type C (Visitable) Units and Units with Communication Features

12 Chapter 12: Recreational Facilities

12.1 Swimming Pools, Wading Pools, Hot Tubs, and Spas 12.2 Play Areas and Amusement Rides 12.3 Sports Facilities, Exercise Equipment, Golf, Boating, Fishing, and Shooting Facilities

6.4 Stairways: Treads, Risers, Nosings, Visual Contrast, and Lighting

Key Takeaways Explain This Topic AI

A117.1 504.2 requires uniform risers 4 to 7 inches high and treads 11 inches deep; IBC 1011.5.4 limits variation within a flight to 3/8 inch.

Open risers are not permitted on accessible stairs (A117.1 504.3); IBC 1011.5.5.3 requires solid risers except on stairs not required to comply with 1009.3 where a 4-inch sphere cannot pass, and in limited occupancies.

A117.1 limits nosing radius and bevel to 1/2 inch, risers sloping back 30 degrees maximum, and nosing projection to 1 1/2 inches; the IBC limits projection to 1 1/4 inches and curvature to 9/16 inch.

A117.1-2017 requires a 1 to 2 inch contrasting stripe at the leading edge of every tread and landing (or durable warning markings required by the building code) and interior stair lighting of 1 footcandle idle and 10 footcandles in use.

Stairs need handrails on both sides complying with 505, and enclosed stairs need raised character and braille floor identification signs at each floor-level landing.

Last updated: October 2026

6.4 Stairways: Treads, Risers, Nosings, Visual Contrast, and Lighting

The Ramps, Stairways and Handrails subtopic (3%) in the General Site domain tests stairs that are part of an accessible means of egress or that the scoping provisions require to be accessible. A117.1 Section 504 sets the technical criteria, and IBC Section 1011 sets the general egress stair rules that apply at the same time. Where the two differ, the more restrictive rule governs the design.

Treads and Risers

  • Item A117.1 504 IBC 1011.5
  • Riser height 4 in. min, 7 in. max , uniform (504.2) 4 in. min, 7 in. max (1011.5.2)
  • Tread depth 11 in. min, uniform (504.2) 11 in. min (1011.5.2)

Uniformity All steps in a flight uniform Largest minus smallest riser or tread 3/8 in. max in a flight (1011.5.4)

  • Open risers Not permitted (504.3) Solid risers required (1011.5.5.3), with exceptions
  • Tread surface Comply with 302; slope not steeper than 1:48 (504.4) Not steeper than 1:48 (1011.7.1)

IBC exceptions allow open risers on stairs not required to comply with 1009.3 where the opening does not pass a 4-in. sphere , in Group I-3, and in F, H and S occupancies other than areas accessible to the public, and on spiral stairs. A stair that serves as part of an accessible means of egress therefore always has solid risers.

Nosings (A117.1 504.5 and IBC 1011.5.5)

  • Item A117.1 504.5 IBC 1011.5.5
  • Uniformity Nosings within a stairway uniform Projections uniform, including the top landing
  • Rounded leading edge Radius 1/2 in. max Curvature or bevel 1/16 in. min, 9/16 in. max
  • Beveled leading edge 45 degrees, extending 1/2 in. max horizontally (within the 9/16 in. limit)
  • Underside of projecting nosings Curved or beveled -
  • Sloped risers 30 degrees max from vertical 30 degrees max from vertical
  • Projection 1 1/2 in. max over the tread or floor below 1 1/4 in. max beyond the tread below

Apply both: an accessible stair with solid risers can project no more than 1 1/4 inches (IBC) and have a leading edge radius no more than 1/2 inch (A117.1).

Visual Contrast (A117.1 504.6, new in 2017)

Visual contrast complies with one of:

The leading 1 to 2 inches of every tread and landing, measured from the leading edge of the nosing, is a solid color with dark-on-light or light-on-dark contrast from the rest of the tread; the durable marking extends from one side of each tread to the other; or

Durable distinctive warning markings required by the adopted building code or an ANSI safety standard.

Other A117.1 504 Requirements

  • Section Requirement
  • 504.7 Handrails Comply with 505 (both sides; see Section 6.5)
  • 504.8 Wet conditions Treads and landings subject to wet conditions designed to prevent water accumulation

504.9.1 Lighting levels Interior stairs: 1 footcandle minimum when not in use and 10 footcandles minimum during use, measured at the center of treads and on landings within 24 in. of nosings; motion-sensor switching between them is allowed if fail-safe, activated by movement on the stair or landing, with timers of 15 minutes minimum

504.9.2 Lighting controls Occupancy sensing controls light the entrance landing, adjacent flights and landings above and below before any step is used

504.10 Tactile signage within stair enclosures Raised character and braille floor-level signs at each floor landing in enclosed stairways, next to the door into the corridor; the exit door to the outside or level of exit discharge has a raised character and braille "EXIT" sign

504.11 Tactile signage at exits Raised character and braille "EXIT" signs adjacent to doors to areas of refuge with stair access, exterior areas for assisted rescue, exit stairways, exit ramps, exit passageways and the exit discharge

IBC Width, Headroom and Landings

IBC section Requirement

1011.2 Width per capacity, 44 in. minimum (36 in. where serving fewer than 50 occupants); stairs in an accessible means of egress comply with 1009.3 (48 in. between handrails unless sprinklered)

  • 1011.3 Headroom 80 in. minimum
  • 1011.5.3 Winder treads not permitted in means of egress stairways except within a dwelling unit

1011.6 Landings at top and bottom, as wide as the stair, depth equal to the stair width or 48 in., whichever is less; doors may not reduce the landing to less than half its required width and may project 7 in. max when fully open; wheelchair spaces for areas of refuge are outside the required landing width and doors may not swing over them

Worked Example

A new two-story library's open exit access stair has 6 3/4-inch risers, 11-inch treads, open risers with 3-inch gaps, nosings that project 1 1/2 inches with a 1/4-inch radius, and no tread markings.

Risers and treads comply (4 to 7 in., 11 in.).

Open risers: if this stair is part of an accessible means of egress, A117.1 504.3 and IBC 1011.5.5.3 require solid risers; the 4-inch sphere exception does not apply to 1009.3 stairs.

Projection: 1 1/2 in. meets A117.1 but exceeds the IBC 1 1/4 in. limit, so it fails.

Visual contrast: a 1 to 2 inch contrasting stripe is required at the leading edge of each tread and landing under 504.6.