7.4 Bathtubs, Shower Compartments, and Seats
ICC Accessibility Inspector / Plans Examiner 21
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: General Administrative and Scoping Provisions
1.1 Occupancy Group Accessibility and IBC Chapter 11 Scoping 1.2 General Administration: Definitions, Conventions, and Code Editions 1.3 Existing Buildings: IEBC Section 306 Alterations, Additions, and Changes of Occupancy 1.4 Technical Infeasibility, Existing-Building Ramps, and Historic Structures
2 Chapter 2: Building Blocks (ICC A117.1 Chapter 3)
2.1 Walking and Floor Surfaces, Openings, and Level Changes 2.2 Turning Space and Clear Floor Space: New Versus Existing Buildings 2.3 Knee and Toe Clearances 2.4 Unobstructed and Obstructed Reach Ranges 2.5 Protruding Objects and Vertical Clearance
3 Chapter 3: Accessible Routes — Route Scoping, Entrances, and Doors
3.1 Accessible Route Scoping, Components, Slopes, and Clear Width 3.2 Accessible Entrances: Number, Location, and Power-Operated Doors 3.3 Doors, Doorways, and Gates: Clear Width and Maneuvering Clearances 3.4 Door Hardware, Forces, Closing Speed, Door Surfaces, and Windows
4 Chapter 4: Accessible Routes — Ramps, Curb Ramps, and Conveyance
4.1 Ramps: Slopes, Landings, and Clearances 4.2 Ramp Handrails, Edge Protection, and Cross Slopes 4.3 Curb Ramps, Blended Transitions, and Detectable Warnings at Crossings 4.4 Elevators, LULA Elevators, and Platform Lifts
5 Chapter 5: Accessible Means of Egress
5.1 Accessible Means of Egress: Number, Components, Elevators, and Stairways 5.2 Elevators, Platform Lifts, Areas of Refuge, and Exterior Areas for Assisted Rescue 5.3 Two-Way Communication, Egress Signage, and Instructions
6 Chapter 6: General Site and Building Elements
6.1 Accessible Parking: Scoping, Van Spaces, Dimensions, and Signs 6.2 Passenger Loading Zones, Bus Stops, and Rail Platforms 6.3 Site Accessibility: Site Routes, Routes Through Parking, EV Charging, and Fuel Dispensers 6.4 Stairways: Treads, Risers, Nosings, Visual Contrast, and Lighting 6.5 Stair Handrails: Location, Height, Profile, Continuity, and Extensions
7 Chapter 7: Plumbing Elements and Facilities
7.1 Water Closets and Toilet Compartments 7.2 Grab Bars: Locations, Cross Sections, Spacing, Strength, and Assisted Toileting 7.3 Toilet Rooms, Lavatories, Sinks, Mirrors, Urinals, and Accessories 7.4 Bathtubs, Shower Compartments, and Seats 7.5 Plumbing Scoping: Family Rooms, Adult Changing Stations, Drinking Fountains, Laundry, and Saunas
8 Chapter 8: Communication Elements and Features
8.1 Visible Alarms and Assistive Listening Systems 8.2 Accessible Signage: Visual Characters, Raised Characters, Braille, Pictograms, and Symbols 8.3 Telephones, ATMs and Fare Machines, Two-Way Communication Systems, and Detectable Warnings
9 Chapter 9: Special Rooms and Spaces
9.1 Assembly Areas: Wheelchair Spaces, Companion Seats, Dispersion, and Lines of Sight 9.2 Dressing and Locker Rooms, Courtrooms, Detention Cells, Self-Storage, and Classroom Acoustics 9.3 Kitchens and Kitchenettes
10 Chapter 10: Built-in Furnishings and Equipment
10.1 Dining Surfaces and Work Surfaces 10.2 Sales and Service Counters and Windows 10.3 Check-Out Aisles, Food Service Lines, Benches, Storage, Charging Stations, and Gaming
11 Chapter 11: Dwelling and Sleeping Units
11.1 Scoping Accessible, Type A, and Type B Units (IBC 1108) 11.2 Type A Units (A117.1 Section 1103) 11.3 Type B Units (A117.1 Section 1104) 11.4 Accessible Units: Hotels, Dormitories, Health Care and Residential Care (A117.1 Section 1102) 11.5 Type C (Visitable) Units and Units with Communication Features
12 Chapter 12: Recreational Facilities
12.1 Swimming Pools, Wading Pools, Hot Tubs, and Spas 12.2 Play Areas and Amusement Rides 12.3 Sports Facilities, Exercise Equipment, Golf, Boating, Fishing, and Shooting Facilities
7.4 Bathtubs, Shower Compartments, and Seats
Key Takeaways Explain This Topic AI
Bathtubs need a clearance 30 inches deep along the full length (extending 12 inches past the head end where a permanent seat is provided), a permanent or removable seat, and grab bars arranged for the seat type.
Transfer showers are 36 x 36 inches inside with a 36-inch entry and a clearance 52 inches long (48 inches existing) by 36 inches deep; the seat is on the wall opposite the controls.
Standard roll-in showers are 60 x 30 inches with a 60-inch entry and a 60 x 30-inch clearance; alternate roll-in showers are 60 x 36 inches with a 36-inch entry at one end.
Shower controls and hand showers are 38 to 48 inches above the shower floor; hand shower hoses are 59 inches long with a nonpositive shut-off.
Seats are 17 to 19 inches high and resist 250 pounds; shower and bathtub water is limited to 120 degrees F; roll-in thresholds are 1/2 inch maximum.
Last updated: October 2026
- 7.4 Bathtubs, Shower Compartments, and Seats
- Bathtubs (A117.1 Section 607)
Item Section Requirement
Clearance 607.2 Full length of the tub, 30 in. deep; where a permanent seat is at the head end, the clearance extends 12 in. beyond the head-end wall
Seat 607.3 Permanent seat at the head end or removable in-tub seat, per 610
Controls 607.5 On an end wall, between the rim and grab bar, and between the open side and the centerline of the tub width; comply with 309.4
Hand shower 607.6 Hose 59 in. minimum, usable as a fixed head and a hand shower, with a nonpositive shut-off; a vertical-bar mount may not obstruct grab bars
- Enclosures 607.7 May not obstruct controls or transfer; no tracks on the tub rim
- Water temperature 607.8 120 degrees F maximum
- Bathtub Grab Bars (607.4)
Bar Tub with permanent seat (607.4.1) Tub with removable seat (607.4.2)
Back wall, upper Per 609.4 (33 to 36 in.), within 15 in. of the head end wall, to within 12 in. of the control end wall 24 in. minimum long, within 24 in. of the head end wall, to within 12 in. of the control end wall
- Back wall, lower 8 to 10 in. above the rim, same extents 8 to 10 in. above the rim, same extents
- Control end wall, horizontal 24 in. minimum, from near the front edge toward the inside corner Same
Control end wall, vertical 18 in. minimum, 3 to 6 in. above the horizontal bar, 4 in. maximum inward from the front edge Same
Head end wall - 12 in. minimum at the front edge
An L-shaped continuous bar of equivalent dimensions may replace the separate control-end horizontal and vertical bars.
Shower Compartments (A117.1 Section 608)
Type Inside size Entry Clearance Seat
Transfer-type (608.2.1) 36 x 36 in. 36 in. New: 52 in. long x 36 in. deep adjacent to the open face, measured from the control wall or from 4 in. behind it; existing: 48 x 36 in. Folding or non-folding seat on the wall opposite the control wall
Standard roll-in (608.2.2) 60 in. wide x 30 in. deep 60 in. 60 x 30 in. adjacent to the 60 in. open face; a lavatory may be at the end opposite the seat Folding seat on an end wall (fixed seat allowed if outside the minimum inside dimension)
Alternate roll-in (608.2.3) 60 in. wide x 36 in. deep 36 in. at one end of the 60 in. width - Folding seat on a seat wall 24 to 36 in. long on the entry side, opposite the back wall
Shower Grab Bars (608.3)
Required horizontal bars are at the same height where multiple bars are used.
Transfer showers : across the control wall and on the back wall to a point 18 in. from the control wall, plus a vertical bar 18 in. minimum, 3 to 6 in. above the horizontal bar and 4 in. maximum in from the front edge.
Standard roll-in : back-wall bar from the edge of the seat, not above the seat, extending within 6 in. of the side wall opposite the seat (need not exceed 48 in.); where a side wall is opposite the seat within 72 in. , a side-wall bar (need not exceed 30 in.) and a vertical bar are required.
Alternate roll-in : bars on the back wall and the side wall adjacent to the seat, not above the seat, within 6 in. of the adjacent wall.
Controls and Hand Showers (608.4 and 608.5)
Shower Control location
Transfer On the control wall opposite the seat, 38 to 48 in. above the shower floor, 15 in. maximum from the centerline of the control wall toward the opening
Standard roll-in On the back wall above the seat, 38 to 48 in. high, 16 to 27 in. from the wall behind the seat
Alternate roll-in 38 to 48 in. high; on the end wall adjacent to the seat 16 to 27 in. from the wall behind the seat, or on the back wall within 15 in. of the seat centerline
Hand showers have a 59 in. minimum hose, a nonpositive shut-off, and a holder 38 to 48 in. above the shower floor. In other than Accessible and Type A units, a fixed shower head 48 in. maximum above the shower floor may replace the hand shower.
Thresholds, Enclosures and Temperature
Thresholds (608.6) : Roll-in showers 1/2 in. maximum per 303; transfer showers 1/2 in. maximum, beveled, rounded or vertical. In existing transfer showers where a 1/2 in. threshold would disturb the slab reinforcement, up to 2 in. is allowed.
Enclosures (608.7) : May not obstruct controls or transfer.
Water temperature (608.8) : 120 degrees F maximum.
Seats (Section 610)
- Seat Requirement
- Height (610.2, 610.3) 17 to 19 in. above the bathroom floor to the top of the seat
- Removable in-tub seat 15 to 16 in. deep, capable of secure placement
Permanent tub seat 15 in. minimum deep, from the back wall to or beyond the outer edge of the tub, at the head end
Shower seat extent Transfer and alternate roll-in: along the seat wall to within 3 in. of the entry; standard roll-in: from the control wall to within 3 in. of the entry
Rectangular shower seat Rear edge 2 1/2 in. maximum and front edge 15 to 16 in. from the seat wall; side edge 1 1/2 in. maximum from the back wall (transfer) or control wall (roll-in)
- Strength (610.4) 250 lb vertical or horizontal at any point
- Assisted Bathing (IBC 1110.2.3)
Where Section 1108 permits, bathrooms serving Accessible units may use a standard roll-in shower designed for assisted bathing : 60 x 30 in. minimum with a 60-in. entry and a 60 x 30 in. clearance; grab bars on three walls at the same height; no wall-mounted folding seats ; controls and hand shower 38 to 48 in. high located to facilitate caregiver access.