Study guide
4.6 Non-Dwelling Load Calculation Workshop (0302)
ICC Commercial Electrical Inspector E2
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 Current Exam Facts 1.2 Exam Format, Scheduling & Logistics 1.3 Study Strategy & Timeline 1.4 NEC Navigation & Open-Book Tactics
2 General Requirements (Domain 01 — 10%)
2.1 Project Administration & Legal (0101) 2.2 Public Information: Terminology, Listing & Labeling (0102) 2.3 Conductors (0103) 2.4 Conductor Ampacity & Termination Workshop (0103)
3 Services (NEC Article 230 & 250)
3.1 Service Size, Rating & Installations (0201) 3.2 Service & Feeder Grounding & Bonding (0202) 3.3 Service Calculations, Clearances & Working Space (depth) 3.4 Service Conductor Installation, Raceways & Emergency Disconnects (0201) 3.5 Grounding Electrode Conductor Installation & Connections (0202) 3.6 Bonding of Metal Piping, Building Steel & Separately Derived Systems (0202)
4 Branch Circuits & Feeders (NEC Articles 210, 215, 220, 240)
4.1 Branch Circuit & Feeder Installation (0301) 4.2 Branch Circuit & Feeder Calculations (0302) 4.3 Branch Circuit Ratings & Overcurrent Protection (0303) 4.4 Equipment Grounding & Bonding (0304) 4.5 Feeder Installation & Buildings Supplied by a Feeder (0301) 4.6 Non-Dwelling Load Calculation Workshop (0302) 4.7 Transformer Secondary Conductors & Selective Coordination (0303) 4.8 Equipment Grounding Conductor Installation & Fault-Path Verification (0304)
5 Wiring Methods & Distribution Systems (NEC Chapters 3 & 4)
5.1 Branch Circuit Required Outlets (0401) 5.2 Boxes, Enclosures & Conduit Bodies (0402) 5.3 Panelboards & Switchboards (0403) 5.4 Raceways, Cables & Bus Ducts (0404) 5.5 Flexible Cords & Fixture Wires (0405) 5.6 Pull Boxes, Cabinets, Cutout Boxes & Accessibility (0402) 5.7 Panelboard Arrangement, Back-Fed Devices & Switchgear Inspection (0403) 5.8 Underground Raceways, Cover Depths & Cable Trays (0404)
6 General Use Equipment (NEC Chapter 4)
6.1 Switches, Receptacles & Light Fixtures (0501) 6.2 General Use Equipment & Appliances (0502) 6.3 Motors & Controllers (0503) 6.4 Transformers, Generators & Misc Equipment (0504)
7 Special Occupancies (NEC Chapter 5)
7.1 Hazardous Locations (0601) 7.2 Health Care Facilities (0602) 7.3 Miscellaneous Other Special Occupancies (0603) 7.4 Commercial Garages, Gas Stations & Bulk Stations (0604)
8 Special Equipment (NEC Chapter 6)
8.1 Swimming Pools, Fountains & Similar Installations (0701) 8.2 Miscellaneous Special Equipment (0702) 8.3 Pool Bonding, Underwater Luminaires & Spa Inspection Workshop (0701)
9 Special Systems (NEC Chapters 7 & 8)
9.1 Emergency Systems (0801) 9.2 Signaling Systems (0802) 9.3 Fire Alarm Systems (0803) 9.4 Communications Systems (0804)
4.6 Non-Dwelling Load Calculation Workshop (0302)
Key Takeaways Explain This Topic AI
Show-window lighting is calculated at 200 volt-amperes per linear foot of show window measured horizontally along its base (220.46).
Track lighting other than in dwelling units and hotel/motel guest rooms is calculated at 150 volt-amperes for every 2 ft of lighting track or fraction thereof (220.46).
Each required sign or outline lighting outlet is computed at a minimum of 1200 volt-amperes for the required branch circuit (220.14(F)).
Commercial kitchen equipment feeder and service loads may be reduced by the demand factors of 220.56 when there are three or more units, but the reduced load must never be less than the sum of the two largest kitchen equipment loads.
Where a load is a continuous load, the 125% factor is applied at the end, after all demand factors — never to the demand-reduced total of a non-continuous load.
Last updated: August 2026
The Order of Operations
A commercial load calculation goes wrong far more often from sequence than from arithmetic. Fix the order in your head and the problems become mechanical:
General lighting — floor area × the unit load from Table 220.42(A).
Specific lighting loads — show windows, track lighting, and signs, each with their own rule.
Receptacles — 180 VA per strap (220.14(I)).
Specific equipment — kitchen equipment, motors, HVAC, water heaters, each under its own article.
Apply demand factors — Table 220.45 for lighting (only four occupancy families get one), 220.44 for receptacles, 220.56 for commercial kitchen equipment.
Apply the 125% continuous adder to the continuous portion — last , after demand factors.
Convert to amperes , select the overcurrent device from 240.6(A), then select conductors and check 110.14(C).
Step 6 is the one to watch. The 125% factor multiplies the continuous load , and a demand factor is a separate reduction applied to a specific category. Applying 125% before a demand factor, or applying a demand factor to a load that does not get one, are the two errors that show up most in practice sets.
The Specific Lighting Rules
- Load Rule Reference
- Show window lighting 200 VA per linear foot of show window, measured horizontally along its base 220.46
Track lighting (other than dwelling units and hotel/motel guest rooms) 150 VA for each 2 ft of track or fraction thereof 220.46
- Sign / outline lighting outlet A minimum of 1200 VA for each required branch circuit 220.14(F)
- Heavy-duty lampholders 600 VA minimum per outlet 220.14(E)
Multioutlet assemblies (non-dwelling) 180 VA per 5 ft where appliances are unlikely to be used simultaneously; 180 VA per 1 ft where they are 220.14(H)
Show-window lighting is a favorite exam item because it is measured per linear foot of window , not per fixture and not per square foot. A 20 ft show window is 20 × 200 = 4000 VA whether it holds two floodlights or twenty.
Commercial Kitchen Equipment — 220.56
Where a feeder or service supplies commercial electric cooking equipment, dishwasher boosters, water heaters, and other kitchen equipment , 220.56 permits a demand factor based on the number of units:
- Number of units of equipment Demand factor
- 1 100%
- 2 100%
- 3 90%
- 4 80%
- 5 70%
- 6 and over 65%
There is one hard floor: the feeder or service demand load shall not be less than the sum of the two largest kitchen equipment loads . If applying 65% to six units drops you below the sum of the two biggest ones, you use the sum of the two biggest ones instead. Space-heating, ventilating, and air-conditioning equipment is not included in this demand — it is calculated separately.
Worked Calculation — A 3,000 ft² Restaurant
A restaurant occupies 3,000 ft², served at 208Y/120 V, three phase . Inventory:
- General lighting, operating more than 3 hours (continuous)
- A 15 ft show window , continuous
- 24 ft of lighting track in the dining room, continuous
- One required sign outlet , continuous
- 40 general-purpose receptacle straps , non-continuous
Kitchen equipment: a 12 kVA range, a 9 kVA fryer, a 6 kVA dishwasher booster, a 5 kVA steam table, and a 4 kVA warming cabinet — five units, non-continuous
Step 1 — General lighting
Table 220.42(A): restaurants are 2 VA/ft² . 3,000 × 2 = 6,000 VA . Restaurants are not in Table 220.45, so they fall under "All others" at 100% — no reduction. Continuous.
- Step 2 — Specific lighting loads
- Show window: 15 ft × 200 VA = 3,000 VA , continuous
- Track lighting: 24 ft ÷ 2 = 12 units × 150 VA = 1,800 VA , continuous
- Sign outlet: 1,200 VA minimum, continuous
- Step 3 — Receptacles
40 straps × 180 VA = 7,200 VA. Apply 220.44: the first 10 kVA at 100% covers all of it, so 7,200 VA , non-continuous.
Step 4 — Kitchen equipment with the 220.56 demand
Connected: 12 + 9 + 6 + 5 + 4 = 36 kVA across five units . Demand factor for five units is 70% : 36,000 × 0.70 = 25,200 VA .
Check the floor: the two largest loads are 12 kVA and 9 kVA, summing to 21,000 VA. Our demand load of 25,200 VA is larger, so the demand result stands. (Had the mix been six small units, the floor would have governed.)
Step 5 — Total, with the continuous adder applied last
- Category VA Treatment
- General lighting 6,000 Continuous
- Show window 3,000 Continuous
- Track lighting 1,800 Continuous
- Sign 1,200 Continuous
- Continuous subtotal 12,000 × 1.25 = 15,000 VA
- Receptacles (after 220.44) 7,200 Non-continuous
- Kitchen equipment (after 220.56) 25,200 Non-continuous
- Non-continuous subtotal 32,400
- Total for sizing 47,400 VA
- Step 6 — Amperes, device, and conductor
- I = 47,400 ÷ (1.732 × 208) = 47,400 ÷ 360.3 = 131.6 A
Overcurrent device : the next standard rating at or above 131.6 A per 240.6(A) is 150 A .
Conductors : ampacity of at least 131.6 A. From Table 310.16, 1/0 AWG copper at 75 °C is 150 A — comfortably above the calculated load and matched to the 150 A device.
Terminations : the equipment is rated over 100 A, so 110.14(C) puts us in the 75 °C column, which is the column already used.
Sanity check the answer. 47,400 VA in a 3,000 ft² restaurant is about 16 VA/ft², which is a believable number for food service. If a calculation lands at 4 VA/ft² for a restaurant or 40 VA/ft² for an office, a demand factor was applied where none belonged or a unit load came out of the wrong row.