Study guide

6.1 Switches, Receptacles & Light Fixtures (0501)

ICC Commercial Electrical Inspector E2

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 Current Exam Facts 1.2 Exam Format, Scheduling & Logistics 1.3 Study Strategy & Timeline 1.4 NEC Navigation & Open-Book Tactics

2 General Requirements (Domain 01 — 10%)

2.1 Project Administration & Legal (0101) 2.2 Public Information: Terminology, Listing & Labeling (0102) 2.3 Conductors (0103) 2.4 Conductor Ampacity & Termination Workshop (0103)

3 Services (NEC Article 230 & 250)

3.1 Service Size, Rating & Installations (0201) 3.2 Service & Feeder Grounding & Bonding (0202) 3.3 Service Calculations, Clearances & Working Space (depth) 3.4 Service Conductor Installation, Raceways & Emergency Disconnects (0201) 3.5 Grounding Electrode Conductor Installation & Connections (0202) 3.6 Bonding of Metal Piping, Building Steel & Separately Derived Systems (0202)

4 Branch Circuits & Feeders (NEC Articles 210, 215, 220, 240)

4.1 Branch Circuit & Feeder Installation (0301) 4.2 Branch Circuit & Feeder Calculations (0302) 4.3 Branch Circuit Ratings & Overcurrent Protection (0303) 4.4 Equipment Grounding & Bonding (0304) 4.5 Feeder Installation & Buildings Supplied by a Feeder (0301) 4.6 Non-Dwelling Load Calculation Workshop (0302) 4.7 Transformer Secondary Conductors & Selective Coordination (0303) 4.8 Equipment Grounding Conductor Installation & Fault-Path Verification (0304)

5 Wiring Methods & Distribution Systems (NEC Chapters 3 & 4)

5.1 Branch Circuit Required Outlets (0401) 5.2 Boxes, Enclosures & Conduit Bodies (0402) 5.3 Panelboards & Switchboards (0403) 5.4 Raceways, Cables & Bus Ducts (0404) 5.5 Flexible Cords & Fixture Wires (0405) 5.6 Pull Boxes, Cabinets, Cutout Boxes & Accessibility (0402) 5.7 Panelboard Arrangement, Back-Fed Devices & Switchgear Inspection (0403) 5.8 Underground Raceways, Cover Depths & Cable Trays (0404)

6 General Use Equipment (NEC Chapter 4)

6.1 Switches, Receptacles & Light Fixtures (0501) 6.2 General Use Equipment & Appliances (0502) 6.3 Motors & Controllers (0503) 6.4 Transformers, Generators & Misc Equipment (0504)

7 Special Occupancies (NEC Chapter 5)

7.1 Hazardous Locations (0601) 7.2 Health Care Facilities (0602) 7.3 Miscellaneous Other Special Occupancies (0603) 7.4 Commercial Garages, Gas Stations & Bulk Stations (0604)

8 Special Equipment (NEC Chapter 6)

8.1 Swimming Pools, Fountains & Similar Installations (0701) 8.2 Miscellaneous Special Equipment (0702) 8.3 Pool Bonding, Underwater Luminaires & Spa Inspection Workshop (0701)

9 Special Systems (NEC Chapters 7 & 8)

9.1 Emergency Systems (0801) 9.2 Signaling Systems (0802) 9.3 Fire Alarm Systems (0803) 9.4 Communications Systems (0804)

6.1 Switches, Receptacles & Light Fixtures (0501)

Key Takeaways Explain This Topic AI

404.14 classifies general-use snap switches: an AC snap switch may carry resistive and inductive loads to its rating, tungsten-filament loads to its rating at 120 V, and motor loads not exceeding 80% of its rating; an AC-DC snap switch is limited to 50% of its rating on inductive loads and needs a T marking for tungsten loads.

Receptacle ratings must match the branch circuit: 210.21(B)(3) permits a 15 A receptacle on a 20 A multi-outlet circuit, but a single receptacle on an individual branch circuit must have an ampere rating not less than the circuit rating (210.21(B)(1)).

Tamper-resistant receptacles are required by 406.12 in dwelling units, hotel and motel guest rooms and guest suites, child care facilities, preschools and elementary education facilities, and several other listed occupancies.

Luminaires in damp or wet locations must be marked for the location (410.10), and outlet boxes supporting luminaires over 50 lb must be listed and marked for the weight (314.27(A)(2)).

Knife switches must be placed so gravity will not tend to close them (404.6(A)) and connected so the blade is de-energized when the switch is open (404.6(C)).

Last updated: August 2026

Switch Ratings and Types (NEC Article 404)

Switches are rated by current, voltage, and the type of load they can control. 404.14 sets what each class of general-use snap switch may control:

Switch class Permitted loads

404.14(A) Alternating-current general-use snap switch (marked "AC only") Resistive and inductive loads not exceeding the ampere rating at the applied voltage; tungsten-filament lamp loads not exceeding the ampere rating at 120 V ; motor loads not exceeding 80% of the ampere rating at the applied voltage

404.14(B) Alternating-current or direct-current general-use snap switch Resistive loads not exceeding the ampere rating; inductive loads not exceeding 50% of the ampere rating ; tungsten-filament lamp loads not exceeding the ampere rating only if the switch is marked "T"

404.14(C) CO/ALR snap switches Snap switches rated 20 A or less directly connected to aluminum conductors must be marked CO/ALR

404.14(E) Dimmer and electronic control switches May be used only to control permanently installed incandescent luminaires unless listed for the specific load type; they may not be used to control receptacles

Two traps live in this section. First, the tungsten "T" marking belongs to the AC-DC switch — an AC-only snap switch already handles tungsten loads to its rating at 120 V without a T mark. Second, an AC-only switch must not be used on a DC circuit, because it relies on the AC current zero-crossing to extinguish the arc. A switch must always have a current rating not less than the load it controls and a voltage rating not less than the circuit voltage.

Knife Switches (404.2)

The knife-switch rules live in 404.6 , not 404.2. 404.6(A) requires single-throw knife switches to be placed so that gravity will not tend to close them ; a switch approved for use in the inverted position must have a locking device that holds the blades open. 404.6(B) permits double-throw knife switches to be mounted with the throw either vertical or horizontal, and requires a locking device where the throw is vertical. 404.6(C) requires single-throw knife switches, molded-case switches, and switches with butt contacts to be connected so the blade is de-energized when the switch is in the open position — the connection that keeps a lineman from finding a live blade behind an "off" handle.

Receptacle Ratings and Configurations (NEC Article 406)

A receptacle is a contact device installed at an outlet for connection of an attachment plug. NEC 406.3 sets receptacle ratings and configurations. Receptacles shall not be connected to a circuit of higher voltage or current than their rating.

Common NEMA Configurations (non-locking)

  • Configuration Voltage Rating Typical Use
  • 5-15R 125 V 15 A General-purpose 2-pole, 3-wire grounding
  • 5-20R 125 V 20 A 20 A branch circuit (T-slot accepts 5-15P or 5-20P)
  • 6-15R 250 V 15 A 250 V loads (e.g., larger A/C)
  • 6-20R 250 V 20 A 250 V loads on 20 A circuits
  • 14-30R 125/250 V 30 A Electric clothes dryer
  • 14-50R 125/250 V 50 A Electric range / EV charging
  • L5-15R / L5-20R 125 V 15/20 A Locking, twist-lock
  • L6-20R / L6-30R 250 V 20/30 A Locking, 250 V
  • Receptacle Types and Required Locations

406.4(A) Grounding type — receptacles installed on 15 A and 20 A branch circuits shall be the grounding type.

406.12 Tamper-resistant — listed tamper-resistant receptacles are required for 125 V and 250 V, 15 A and 20 A receptacles in dwelling units , guest rooms and guest suites of hotels and motels , child care facilities , preschools and elementary education facilities , medical and dental offices and outpatient facilities , assembly occupancy gaming areas , dormitory units , and the other occupancies listed there. This is a commercial-inspector item as much as a residential one.

406.9(B) Weather-resistant and covers — receptacles in wet locations must be listed weather-resistant , and 15 A and 20 A receptacles in wet locations require an in-use (extra-duty) cover that remains weatherproof with an attachment plug inserted. In damp locations the cover need only be weatherproof when the plug is removed.

406.4(D) Non-grounding replacement — where a grounding means does not exist, a non-grounding-type receptacle may be replaced with another non-grounding receptacle, or with a GFCI-type receptacle marked "No Equipment Ground."

406.5 Mounting — receptacles must be mounted in identified boxes or assemblies. Where the box is set back from a noncombustible surface (permitted by 314.20 up to 1/4 in.), the receptacle must be installed so the mounting yoke is held rigidly at the finished surface, and receptacle faceplates must completely cover the opening (406.6).

Combination devices — a switch-and-receptacle device on one strap must satisfy Article 404 for the switch portion and Article 406 for the receptacle portion, including the TR, WR, and GFCI requirements for its location. For box-fill purposes the whole strap is still one yoke — worth two conductor allowances under 314.16(B)(4).

Luminaires and Light Fixtures (NEC Article 410)

A luminaire is a complete lighting unit consisting of a light source and parts to position, protect, and connect it.

410.10 Damp, wet, or corrosive locations — luminaires shall be identified for the location. A luminaire in a wet location shall be listed for wet locations; chain-mounted luminaires in damp locations shall have the chain grounded.

410.11 Luminaires near combustible material — luminaires must be constructed, installed, or equipped with shades or guards so that combustible material is not subjected to temperatures in excess of 90 °C (194 °F).

410.16 Luminaires in clothes closets — the storage space is defined dimensionally, and only listed luminaire types are permitted, with specific clearances from the storage space.

410.30 and 410.36 Supports — luminaires and lampholders must be securely supported. A luminaire installed in a suspended (dropped) ceiling must be securely fastened to the ceiling framing member by mechanical means such as bolts, screws, or rivets, and listed clips identified for that ceiling framing member are permitted; the framing members themselves must be securely fastened to each other and to the building structure. A luminaire weighing more than 50 lb (23 kg) must be supported independently of the outlet box unless the box is listed and marked for that weight (314.27(A)(2)).

410.62 Cord-connected luminaires — where a luminaire is cord-connected, the cord must be a listed flexible cord (not fixture wire), and the specific conditions in 410.62(C) apply to cord-connected lampholders and to luminaires supplied by a cord and plug.

Fixture Wires (Article 402)

Fixture wire (Article 402) is permitted only inside luminaires and similar equipment and for connecting luminaires to their branch-circuit conductors — it is not a branch-circuit wiring method (402.11). Common types include TF, TFF, TFN, TFFN, SF, SFF, and PF. Allowable ampacity comes from Table 402.5 (not Table 402.3, which lists types and insulations):

  • Size (AWG) Allowable ampacity
  • 18 6 A
  • 16 8 A
  • 14 17 A
  • 12 23 A
  • 10 28 A

402.6 makes 18 AWG the minimum fixture-wire size, and 240.5(B)(2) sets the branch-circuit ratings that a given fixture wire may be tapped from, including run-length limits for 18 AWG and 16 AWG.