3.5 Grounding Electrode Conductor Installation & Connections (0202)
ICC Commercial Electrical Inspector E2
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 Current Exam Facts 1.2 Exam Format, Scheduling & Logistics 1.3 Study Strategy & Timeline 1.4 NEC Navigation & Open-Book Tactics
2 General Requirements (Domain 01 — 10%)
2.1 Project Administration & Legal (0101) 2.2 Public Information: Terminology, Listing & Labeling (0102) 2.3 Conductors (0103) 2.4 Conductor Ampacity & Termination Workshop (0103)
3 Services (NEC Article 230 & 250)
3.1 Service Size, Rating & Installations (0201) 3.2 Service & Feeder Grounding & Bonding (0202) 3.3 Service Calculations, Clearances & Working Space (depth) 3.4 Service Conductor Installation, Raceways & Emergency Disconnects (0201) 3.5 Grounding Electrode Conductor Installation & Connections (0202) 3.6 Bonding of Metal Piping, Building Steel & Separately Derived Systems (0202)
4 Branch Circuits & Feeders (NEC Articles 210, 215, 220, 240)
4.1 Branch Circuit & Feeder Installation (0301) 4.2 Branch Circuit & Feeder Calculations (0302) 4.3 Branch Circuit Ratings & Overcurrent Protection (0303) 4.4 Equipment Grounding & Bonding (0304) 4.5 Feeder Installation & Buildings Supplied by a Feeder (0301) 4.6 Non-Dwelling Load Calculation Workshop (0302) 4.7 Transformer Secondary Conductors & Selective Coordination (0303) 4.8 Equipment Grounding Conductor Installation & Fault-Path Verification (0304)
5 Wiring Methods & Distribution Systems (NEC Chapters 3 & 4)
5.1 Branch Circuit Required Outlets (0401) 5.2 Boxes, Enclosures & Conduit Bodies (0402) 5.3 Panelboards & Switchboards (0403) 5.4 Raceways, Cables & Bus Ducts (0404) 5.5 Flexible Cords & Fixture Wires (0405) 5.6 Pull Boxes, Cabinets, Cutout Boxes & Accessibility (0402) 5.7 Panelboard Arrangement, Back-Fed Devices & Switchgear Inspection (0403) 5.8 Underground Raceways, Cover Depths & Cable Trays (0404)
6 General Use Equipment (NEC Chapter 4)
6.1 Switches, Receptacles & Light Fixtures (0501) 6.2 General Use Equipment & Appliances (0502) 6.3 Motors & Controllers (0503) 6.4 Transformers, Generators & Misc Equipment (0504)
7 Special Occupancies (NEC Chapter 5)
7.1 Hazardous Locations (0601) 7.2 Health Care Facilities (0602) 7.3 Miscellaneous Other Special Occupancies (0603) 7.4 Commercial Garages, Gas Stations & Bulk Stations (0604)
8 Special Equipment (NEC Chapter 6)
8.1 Swimming Pools, Fountains & Similar Installations (0701) 8.2 Miscellaneous Special Equipment (0702) 8.3 Pool Bonding, Underwater Luminaires & Spa Inspection Workshop (0701)
9 Special Systems (NEC Chapters 7 & 8)
9.1 Emergency Systems (0801) 9.2 Signaling Systems (0802) 9.3 Fire Alarm Systems (0803) 9.4 Communications Systems (0804)
3.5 Grounding Electrode Conductor Installation & Connections (0202)
Key Takeaways Explain This Topic AI
250.64(A) permits bare, covered, or insulated aluminum grounding electrode conductors only where not in contact with masonry or earth, and prohibits them within 18 in. of the earth.
250.64(B) requires a grounding electrode conductor 6 AWG or larger to be protected where exposed to physical damage, and a 6 AWG copper conductor may be run along a building surface without protection where free from damage; smaller than 6 AWG must be in a raceway or armor.
250.64(C) requires the grounding electrode conductor to be installed in one continuous length without a splice, except by irreversible compression connectors listed for the purpose, exothermic welding, busbar sections, or bolted busbar connections.
250.64(E) requires ferrous metal enclosures and raceways for grounding electrode conductors to be electrically continuous and bonded at both ends, so the raceway does not act as a choke on fault current.
250.68(A) requires the connection to the electrode to be accessible, except that an encased or buried connection — such as at a concrete-encased electrode or a driven rod below grade — is permitted to be inaccessible.
Last updated: August 2026
Sizing Is the Easy Half
Section 3.2 covered Table 250.66 and the three caps that modify it. On the job, the grounding electrode conductor (GEC) is far more often written up for how it was installed than for what size it is . This section is the installation half of sub-topic 0202.
Material and Where Aluminum May Not Go — 250.64(A)
A GEC may be copper, aluminum, copper-clad aluminum, or stainless steel , and may be solid or stranded, bare, covered, or insulated. But aluminum and copper-clad aluminum carry two restrictions:
They shall not be used where in direct contact with masonry or the earth , or where subject to corrosive conditions .
Where used outdoors, they shall not be terminated within 18 in. (450 mm) of the earth .
That second rule is the one field inspectors use: an aluminum GEC clamped to a ground rod at grade is a violation on its face, because the termination sits at the earth. Bare aluminum GECs installed in a concrete slab or run along a masonry foundation wall fail the first rule.
Physical Protection — 250.64(B)
The protection requirement is written by conductor size, and the thresholds are worth memorizing:
GEC size Protection required
4 AWG and larger Protected if exposed to physical damage ; a 4 AWG or larger conductor may be run along the surface of the building without metal covering where not exposed to physical damage
6 AWG May be run along the surface of the building without metal covering or protection where free from exposure to physical damage and securely fastened ; otherwise, in RMC, IMC, PVC, RTRC, EMT, or cable armor
Smaller than 6 AWG Shall be in RMC, IMC, PVC, RTRC, EMT, or cable armor — no exposed run is permitted
The practical takeaway: a 6 AWG copper GEC stapled up a basement wall to a driven rod is acceptable; a 8 AWG doing the same thing is not.
Continuous Without a Splice — 250.64(C)
The GEC must be installed in one continuous length without a splice or joint . Four things are permitted anyway:
Irreversible compression-type connectors listed as grounding and bonding equipment, or exothermic welding .
Sections of busbar connected together.
Bolted, riveted, or welded connections of structural metal frames of buildings.
Where a service consists of more than one enclosure as permitted by 230.71, the GEC may be run to a busbar and tapped to each enclosure — the busbar must be not smaller than 1/4 in. × 2 in., securely fastened, installed where accessible, and each tap connection must be made by a listed connector or by exothermic welding.
A wire nut, a split-bolt, or a mechanical lug in the middle of a GEC run is not on that list. That is a very common write-up.
The Ferrous Raceway Trap — 250.64(E)
Where a GEC is installed in a ferrous metal raceway, enclosure, or cable armor , that metal enclosure must be electrically continuous from the point of attachment to cabinets or equipment to the grounding electrode , and must be securely fastened to the ground clamp or fitting . Any ferrous raceway that is not physically continuous must be made continuous by bonding each end to the grounding electrode conductor .
The physics is worth understanding rather than memorizing. A steel conduit surrounding a single current-carrying conductor acts as a magnetic choke: the alternating flux from the GEC current induces opposing currents in the steel and dramatically raises the impedance of the path. Bonding both ends of the raceway to the GEC puts the steel in parallel with the conductor instead of in series with the flux, and the choking effect disappears. A GEC pulled through a steel sleeve that is bonded at neither end can have several times its expected impedance — the conductor is the right size and the installation still does not work.
Where the raceway is nonferrous — PVC or aluminum — the bonding requirement does not apply, which is why PVC is the common choice for a GEC sleeve.
Connections to the Electrode — 250.68 and 250.70
250.68(A) Accessibility. The connection of a grounding electrode conductor or bonding jumper to a grounding electrode must be accessible . Two exceptions: an encased or buried connection to a concrete-encased, driven, or buried electrode need not be accessible, and exothermic or irreversible compression connections to fireproofed structural metal need not be accessible.
250.68(B) Effective grounding path. The connection must be made in a manner that the installation of equipment — such as a water meter or a filter — will not likely be disconnected during normal use , which is why a bonding jumper around the water meter is required.
250.68(C)(1) Interior metal water pipe. Interior metal water piping located not more than 5 ft (1.52 m) from the point of entrance to the building may be used as a conductor to interconnect electrodes. In industrial, commercial, and institutional buildings where conditions of maintenance and supervision ensure qualified persons service the installation, the entire length of interior metal water pipe may be used if it is exposed.
250.70 Methods of connection. The connection must be by listed lugs, pressure connectors, clamps, or other listed means , and the fitting must be listed for the materials of the electrode and the conductor. Not more than one conductor may terminate on a single clamp unless the clamp is listed for multiple conductors. Solder shall not be used. A ground clamp used on a buried or direct-contact electrode must be listed for direct soil burial or concrete encasement .
Three-item field check. Walk the GEC from the service to the electrode and ask: is it continuous, is it protected for its size, and is every ferrous sleeve bonded at both ends? Those three questions catch the overwhelming majority of GEC defects.