Study guide
5.4 Commercial & Multifamily Load Calculations
ICC Electrical Plans Examiner E3
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: General Administration, Plan Review & Code Navigation
1.1 Scope, Administration & the Plans Examiner's Role 1.2 Key Definitions & Core Terminology for Plan Examiners 1.3 Electrical Plan Symbols, Single-Line Diagrams & Schedules
2 Chapter 2: Services & Service Equipment
2.1 Service Clearances & Approvals 2.2 Service Conductors & Sizing 2.3 Service Disconnecting Means & Equipment 2.4 Service Overcurrent Protection & Surge Protection
3 Chapter 3: Grounding and Bonding
3.1 Grounding vs. Bonding Fundamentals 3.2 Grounding Electrode System (GES) & Conductors 3.3 Equipment Grounding & Bonding 3.4 Separately Derived Systems & Transformers
4 Chapter 4: Branch Circuits & Receptacle Layouts
4.1 Branch Circuit Ratings, Loads & Multi-Wire Circuits 4.2 Required Branch Circuits & GFCI/AFCI Protection 4.3 Receptacle Outlets & Spacing Rules
5 Chapter 5: Feeder Sizing & Load Calculations
5.1 Feeder Sizing & Voltage Drop Calculations 5.2 Dwelling Unit Load Calculations (Standard Method) 5.3 Dwelling Unit Load Calculations (Optional Method) 5.4 Commercial & Multifamily Load Calculations
6 Chapter 6: Overcurrent Protection & Fault Current Analysis
6.1 Overcurrent Protective Device Ratings & Rules 6.2 Feeder and Transformer Tap Rules 6.3 Short-Circuit Current Ratings, Series Ratings & Selective Coordination
7 Chapter 7: Wiring Methods, Raceways, Enclosures & Distribution Equipment
7.1 Underground Wiring & Physical Protection 7.2 Conductor Ampacity & Derating Adjustments 7.3 Box Fill & Pull Box Calculations 7.4 Raceway Sizing & Conduit Fill Rules 7.5 Panelboards, Switchboards & Distribution Equipment
8 Chapter 8: Equipment for General Use
8.1 Motor Circuit Sizing & Motor Controllers 8.2 Motor Overload & Short-Circuit Protection 8.3 Air Conditioning, Refrigeration & Heating 8.4 Transformers & Generators 8.5 Switches, Receptacles & Luminaires
9 Chapter 9: Special Occupancies
9.1 Hazardous (Classified) Locations Fundamentals 9.2 Commercial Garages, Repair Facilities & Fuel Dispensing 9.3 Health Care Facilities 9.4 Places of Assembly, Marinas & RV Parks 9.5 Mobile Homes, Manufactured Homes & Mobile Home Parks
10 Chapter 10: Special Equipment
10.1 Electric Signs & Outline Lighting 10.2 Swimming Pools, Spas & Hot Tubs 10.3 Fire Pumps 10.4 Solar PV, Energy Storage (ESS) & EVSE 10.5 Information Technology Equipment Rooms & Busways
11 Chapter 11: Special Systems & Electrical Safety
11.1 Emergency & Legally Required Standby Systems 11.2 Fire Alarm Systems & Power-Limited Circuits 11.3 Arc-Flash Hazard Warning & Electrical Safety
5.4 Commercial & Multifamily Load Calculations
Key Takeaways Explain This Topic AI
Non-dwelling general lighting loads come from 2023 NEC Table 220.42(A) by occupancy (office 1.3, retail 1.9, restaurant 1.5, warehouse 1.2, manufacturing 2.2 VA/sq ft), and the Note to that table states the 125% continuous multiplier is already included, so it must not be applied a second time.
Commercial show window lighting must be calculated at not less than 200 VA per linear foot of show window under NEC 220.14(G) and 220.46(A); general receptacle loads (180 VA per strap) qualify for Table 220.47 demand factors: first 10 kVA at 100%, and remainder over 10 kVA at 50%.
Commercial kitchen and cooking equipment loads are calculated using NEC Table 220.56 demand factors (1-2 units @ 100%, 3 units @ 90%, 4 units @ 80%, 5 units @ 70%, 6+ units @ 65%), but the feeder demand can never be less than the sum of the largest two cooking units.
Multifamily building services can be calculated using the Standard Method (Part III) or the Optional Method under NEC 220.84 for buildings with 3 or more units having electric cooking and electric heating/cooling, applying Table 220.84 demand factors (e.g., 20 units @ 38%, 24 units @ 35%, 40 units @ 28%).
Common house loads in multifamily buildings (hallway/exterior lighting, elevators, clubhouse, common laundry, fire pumps) CANNOT use Table 220.84 dwelling demand factors and must be calculated separately under Part III at 100% non-continuous plus 125% continuous.
Last updated: August 2026
5.4 Commercial & Multifamily Load Calculations
Quick Reference: Commercial and multifamily electrical installations exhibit distinct demand profiles compared to single-family dwellings. In commercial buildings, lighting operates continuously, show windows demand dedicated linear-foot capacity, and commercial kitchens incorporate heavy cooking arrays subject to NEC Table 220.56 . In multifamily apartment complexes, plans examiners must distinguish between tenant dwelling unit diversity under NEC 220.84 and un-discounted common House Loads .
1. Commercial General Lighting Calculations (NEC 220.42 & Table 220.42(A))
In commercial occupancies, general lighting loads are determined on a unit-per-area basis using NEC Table 220.42(A) based on gross floor area calculated from outside building dimensions. +-----------------------------------------------------------------------------+
- | NEC TABLE 220.42(A) NON-DWELLING LIGHTING UNIT LOADS |
- +------------------------------------+----------------------------------------+
- | Occupancy Classification | Unit Load (VA/sq ft) |
- +------------------------------------+----------------------------------------+
- | Office (banks are office-type) | 1.3 VA / sq ft |
- | Retail (stores, barber/beauty) | 1.9 VA / sq ft |
- | Restaurant (clubs are restaurants) | 1.5 VA / sq ft |
- | Warehouse | 1.2 VA / sq ft |
- | School / university | 1.5 VA / sq ft (was 3 in the 2020 NEC) |
- | Hospital / health care clinic | 1.6 VA / sq ft |
- | Hotels and motels | 1.7 VA / sq ft |
- | Manufacturing facility | 2.2 VA / sq ft |
- | Parking garage | 0.3 VA / sq ft |
- +------------------------------------+----------------------------------------+
The occupancy names in Table 220.42(A) are energy-code names, so the table carries lettered notes that redirect familiar building types: armories and auditoriums are gymnasium-type, lodge rooms follow hotels and motels, industrial commercial loft buildings are manufacturing-type, banks are office-type , commercial storage garages are parking-garage-type, clubs are restaurant-type, and barber shops, beauty parlors, and stores are retail-type. A plans examiner who cannot find "bank" or "store" as its own row is expected to work the notes rather than guess.
Warning
The single biggest trap in commercial lighting calculations: do NOT apply 125% twice. The Note to Table 220.42(A) states that the 125 percent multiplier for a continuous load specified in 210.20(A) is already included in the unit loads in this table. Applying another 1.25 1.25 1.25 multiplier to a Table 220.42(A) result double-counts the continuous-load factor and oversizes the feeder by 25 percent. This changed with the 2020 NEC, when the table was rebuilt from ASHRAE 90.1 / IECC lighting power densities; pre-2020 tables (offices at 3.5 VA/sq ft, stores at 3 VA/sq ft) did not include the multiplier. On an open-book exam the note is printed directly beneath the table — read it before you multiply. Minimum Feeder Lighting Load (VA) = Floor Area × Table 220.42(A) Unit Load \text{Minimum Feeder Lighting Load (VA)} = \text{Floor Area} \times \text{Table 220.42(A) Unit Load} Minimum Feeder Lighting Load (VA) = Floor Area × Table 220.42(A) Unit Load
The 125% continuous multiplier of NEC 215.2(A)(1) and NEC 210.20(A) still applies in full to continuous lighting loads that are not taken from Table 220.42(A) — most importantly show-window lighting under 220.46(A), sign loads under 220.14(F), and any design that uses the actual connected lighting load because it exceeds the table minimum.
Note
2023 NEC Energy Code Lighting Exception (NEC 220.42(B)): Where the building is designed and constructed in compliance with a jurisdiction-adopted energy conservation code (such as ASHRAE 90.1 or IECC) that includes maximum Lighting Power Density (LPD) values and automated lighting controls, the feeder calculation is permitted to use the actual lighting load specified by the energy code, provided the power system is monitored with continuous power reporting equipment.
Loading diagram... Commercial vs. Multifamily Calculation Decision Framework
- 2. Show Windows & Commercial Receptacle Demand (NEC 220.46, Table 220.47)
- 1. Show Window Lighting (NEC 220.14(G) & 220.46(A))
In retail occupancies, show window lighting branch circuits and feeders must be calculated at not less than 200 VA 200\text{ VA} 200 VA per linear foot ( 660 VA/m 660\text{ VA/m} 660 VA/m ) of show window, measured horizontally along its base. Because show window lighting operates continuously, feeders must be sized for 200 VA/ft × 1.25 = 250 VA/ft 200\text{ VA/ft} \times 1.25 = \mathbf{250\text{ VA/ft}} 200 VA/ft × 1.25 = 250 VA/ft .
2. Commercial Receptacle Loads & Demand Factors (NEC Table 220.47)
In commercial buildings, general-use convenience receptacle outlets are calculated at 180 VA 180\text{ VA} 180 VA per strap/yoke (single, duplex, or triplex receptacle on a single mounting strap per NEC 220.14(I)). For multioutlet assemblies (e.g., plug-mold / raceway), NEC 220.14(H) requires 180 VA 180\text{ VA} 180 VA per 5 ft 5\text{ ft} 5 ft (general use) or 180 VA 180\text{ VA} 180 VA per 1 ft 1\text{ ft} 1 ft (simultaneous heavy commercial use).
Feeder and service demand factors for commercial receptacles are established in NEC Table 220.47 :
- Portion of Receptacle Load Demand Factor (Table 220.47)
- First 10 kVA (10,000 VA) or less 100% ( 1.00 1.00 1.00 )
Remainder over 10 kVA (10,000 VA) 50% ( 0.50 0.50 0.50 ) Net Commercial Receptacle Load = 10 , 000 VA + [ ( Gross Receptacle VA − 10 , 000 VA ) × 0.50 ] \text{Net Commercial Receptacle Load} = 10,000\text{ VA} + \left[ (\text{Gross Receptacle VA} - 10,000\text{ VA}) \times 0.50 \right] Net Commercial Receptacle Load = 10 , 000 VA + [ ( Gross Receptacle VA − 10 , 000 VA ) × 0.50 ]
3. Commercial Kitchen & Cooking Equipment (NEC Table 220.56)
In commercial kitchens (restaurants, school cafeterias, hospital dietary centers, hotel kitchens), cooking equipment, dishwashers with booster heaters, water heaters dedicated to kitchen sanitization, fryers, griddles, steam tables, and food warmers exhibit operational diversity governed by NEC Table 220.56 . +-----------------------------------------------------------------------------+
- | NEC TABLE 220.56 COMMERCIAL KITCHEN EQUIPMENT DEMAND |
- +-------------------------------------+---------------------------------------+
- | Number of Units of Equipment | Demand Factor (%) |
- +-------------------------------------+---------------------------------------+
- | 1 to 2 units | 100% |
- | 3 units | 90% |
- | 4 units | 80% |
- | 5 units | 70% |
- | 6 or more units | 65% |
- +-------------------------------------+---------------------------------------+
The Mandatory "Never Less Than Two Largest" Rule:
Under the footnote to NEC Table 220.56, in no case shall the calculated feeder or service demand load be less than the sum of the ratings of the two largest units of commercial cooking equipment.
Caution
Plan Review Calculation Check — Table 220.56 Safety Floor: Suppose a commercial kitchen has 6 pieces of equipment: two 15 kW 15\text{ kW} 15 kW fryers, one 3 kW 3\text{ kW} 3 kW warmer, one 2 kW 2\text{ kW} 2 kW heat lamp, one 2 kW 2\text{ kW} 2 kW toaster, and one 1 kW 1\text{ kW} 1 kW slicer (total = 34 kW = 34\text{ kW} = 34 kW ). Applying the 6-unit factor of 65 % 65\% 65% gives 34 kW × 0.65 = 22.1 kW 34\text{ kW} \times 0.65 = 22.1\text{ kW} 34 kW × 0.65 = 22.1 kW . However, the sum of the two largest units is 15 kW + 15 kW = 30.0 kW 15\text{ kW} + 15\text{ kW} = \mathbf{30.0\text{ kW}} 15 kW + 15 kW = 30.0 kW . The plans examiner must enforce the 30.0 kW 30.0\text{ kW} 30.0 kW floor!
4. Multifamily Building Calculations: Standard vs. Optional Method (NEC 220.84)
When calculating the main electrical service for a multifamily apartment building, engineers may choose between the Standard Method (Part III) and the Multifamily Optional Method (NEC 220.84) .
Qualifying Conditions for NEC 220.84:
The building must contain three or more dwelling units .
Each dwelling unit must be equipped with electric cooking equipment . The Exception to this condition is not a gas-cooking allowance: where a multifamily building without electric cooking produces a larger Part III calculated load than the same building would produce under Part IV with electric cooking added at 8 kW per unit, the designer is permitted to use the lesser of the two results.
Each dwelling unit must be equipped with electric space heating and/or air conditioning .
No individual dwelling unit is supplied by more than one feeder. +-----------------------------------------------------------------------------+
- | NEC TABLE 220.84 MULTIFAMILY OPTIONAL DEMAND FACTORS |
- +-----------------------+---------------------+-------------------------------+|
- | Number of Units | Demand Factor (%) | Number of Units | Demand (%) ||
- +-----------------------+---------------------+-------------------------------+|
- | 3 to 5 units | 45% | 26 to 27 units | 34% ||
- | 6 to 7 units | 44% | 28 to 30 units | 33% ||
- | 8 to 10 units | 43% | 31 units | 32% ||
- | 11 units | 42% | 32 to 33 units | 31% ||
- | 12 to 13 units | 41% | 34 to 36 units | 30% ||
- | 14 to 15 units | 40% | 37 to 38 units | 29% ||
- | 16 to 17 units | 39% | 39 to 42 units | 28% ||
- | 18 to 20 units | 38% | 43 to 45 units | 27% ||
- | 21 units | 37% | 46 to 50 units | 26% ||
- | 22 to 23 units | 36% | 51 to 55 units | 25% ||
- | 24 to 25 units | 35% | 56 to 61 units | 24% ||
- | | | 62 and over | 23% ||
- +-----------------------+---------------------+-------------------------------+|
- +-----------------------------------------------------------------------------+
- Separation of Multifamily House Loads (NEC 220.84(B))
House loads (loads not located inside individual apartments) are strictly excluded from Table 220.84 demand factors. House loads include:
- Corridor, stairwell, lobby, and architectural egress lighting
- Parking lot and landscape lighting
- Common clubhouse, leasing office, and fitness center
- Common tenant laundry rooms (commercial coin-op dryers/washers)
- Elevators, fire pumps, booster pumps, and common HVAC central plants
Important
Plan Review Mandate: House loads must be calculated separately under NEC Article 220 Part III at 100 % 100\% 100% for non-continuous loads plus 125 % 125\% 125% for continuous loads, and then added directly to the calculated Table 220.84 dwelling unit demand.
- 5. Step-by-Step Worked Commercial & Multifamily Calculations
- Example 1: Commercial Restaurant / Retail Tenant Fit-Out
Parameters: A 4 , 000 sq ft 4,000\text{ sq ft} 4 , 000 sq ft commercial restaurant with a 30 ft 30\text{ ft} 30 ft show window. System is 208 Y / 120 V 208\text{Y}/120\text{V} 208 Y /120 V , 3-phase, 4-wire.
Restaurant floor area: 4 , 000 sq ft 4,000\text{ sq ft} 4 , 000 sq ft (Table 220.42(A) unit load = 1.5 VA/sq ft = 1.5\text{ VA/sq ft} = 1.5 VA/sq ft )
Show window: 30 linear feet 30\text{ linear feet} 30 linear feet
General Receptacles: 40 duplex receptacles ( 40 × 180 VA = 7 , 200 VA 40 \times 180\text{ VA} = 7,200\text{ VA} 40 × 180 VA = 7 , 200 VA )
Commercial Kitchen: (5) units totaling 42 kW 42\text{ kW} 42 kW (two largest units are 12 kW 12\text{ kW} 12 kW and 10 kW 10\text{ kW} 10 kW )
HVAC: 10 -ton 10\text{-ton} 10 -ton Rooftop AC unit ( 208 V 208\text{V} 208 V , 3-phase, 38 A FLA = 13 , 690 VA 38\text{ A FLA} = 13,690\text{ VA} 38 A FLA = 13 , 690 VA , largest motor)
Step 1: General Lighting (Table 220.42(A) — 125% already included) Lighting Load = 4 , 000 sq ft × 1.5 VA/sq ft = 6 , 000 VA \text{Lighting Load} = 4,000\text{ sq ft} \times 1.5\text{ VA/sq ft} = \mathbf{6,000\text{ VA}} Lighting Load = 4 , 000 sq ft × 1.5 VA/sq ft = 6 , 000 VA Do not multiply this by 1.25 1.25 1.25 again. The Note to Table 220.42(A) states that the 210.20(A) continuous-load multiplier is already built into the unit load.
Step 2: Show Window Lighting (Continuous 125 % 125\% 125% ) Show Window Load = 30 ft × 200 VA/ft × 1.25 = 7 , 500 VA \text{Show Window Load} = 30\text{ ft} \times 200\text{ VA/ft} \times 1.25 = \mathbf{7,500\text{ VA}} Show Window Load = 30 ft × 200 VA/ft × 1.25 = 7 , 500 VA
Step 3: General Receptacles (Table 220.47)
Gross receptacle load = 7 , 200 VA = 7,200\text{ VA} = 7 , 200 VA (less than 10 , 000 VA → 100 % 10,000\text{ VA} \rightarrow 100\% 10 , 000 VA → 100% ) = 7 , 200 VA = \mathbf{7,200\text{ VA}} = 7 , 200 VA
Step 4: Commercial Kitchen Equipment (Table 220.56)
5 units = 70 % = 70\% = 70% demand factor: 42 , 000 VA × 0.70 = 29 , 400 VA 42,000\text{ VA} \times 0.70 = 29,400\text{ VA} 42 , 000 VA × 0.70 = 29 , 400 VA
Check 2 largest units floor: 12 , 000 VA + 10 , 000 VA = 22 , 000 VA 12,000\text{ VA} + 10,000\text{ VA} = 22,000\text{ VA} 12 , 000 VA + 10 , 000 VA = 22 , 000 VA
Since 29 , 400 VA > 22 , 000 VA 29,400\text{ VA} > 22,000\text{ VA} 29 , 400 VA > 22 , 000 VA , use 29 , 400 VA 29,400\text{ VA} 29 , 400 VA .
- Step 5: HVAC & Largest Motor Adder (NEC 220.11(A))
- HVAC load = 13 , 690 VA = 13,690\text{ VA} = 13 , 690 VA
Largest motor adder: 13 , 690 VA × 0.25 = 3 , 423 VA 13,690\text{ VA} \times 0.25 = 3,423\text{ VA} 13 , 690 VA × 0.25 = 3 , 423 VA
Total HVAC = 13 , 690 + 3 , 423 = 17 , 113 VA = 13,690 + 3,423 = \mathbf{17,113\text{ VA}} = 13 , 690 + 3 , 423 = 17 , 113 VA
Step 6: Total 3-Phase Calculated Load & Service Sizing Total VA = 6 , 000 + 7 , 500 + 7 , 200 + 29 , 400 + 17 , 113 = 67 , 213 VA \text{Total VA} = 6,000 + 7,500 + 7,200 + 29,400 + 17,113 = \mathbf{67,213\text{ VA}} Total VA = 6 , 000 + 7 , 500 + 7 , 200 + 29 , 400 + 17 , 113 = 67 , 213 VA Service Current = 67 , 213 VA 3 × 208 V = 67 , 213 360.25 = 186.6 Amperes \text{Service Current} = \frac{67,213\text{ VA}}{\sqrt{3} \times 208\text{ V}} = \frac{67,213}{360.25} = \mathbf{186.6\text{ Amperes}} Service Current = 3 × 208 V 67 , 213 VA = 360.25 67 , 213 = 186.6 Amperes
Service Selection: Standard 200 A 200\text{ A} 200 A , 208Y/120V 3-phase commercial service ( 3 / 0 AWG Cu 3/0\text{ AWG Cu} 3/0 AWG Cu per Table 310.16 at 75°C).
Example 2: 20-Unit Multifamily Building (NEC 220.84 Optional Method)
Parameters: 20 identical apartments ( 900 sq ft 900\text{ sq ft} 900 sq ft each) supplied by a common 208 Y / 120 V 208\text{Y}/120\text{V} 208 Y /120 V 3-phase service.
Each unit connected load: Lighting ( 2 , 700 VA 2,700\text{ VA} 2 , 700 VA ), SABC ( 3 , 000 VA 3,000\text{ VA} 3 , 000 VA ), Range ( 9 , 000 VA 9,000\text{ VA} 9 , 000 VA ), Water Heater ( 4 , 500 VA 4,500\text{ VA} 4 , 500 VA ), Dishwasher/Disposer ( 2 , 000 VA 2,000\text{ VA} 2 , 000 VA ), A/C ( 3 , 500 VA 3,500\text{ VA} 3 , 500 VA ). Total per unit = 24 , 700 VA = \mathbf{24,700\text{ VA}} = 24 , 700 VA .
Common House Loads: Common lighting ( 4 , 000 VA 4,000\text{ VA} 4 , 000 VA continuous), Common laundry ( 8 , 000 VA 8,000\text{ VA} 8 , 000 VA non-continuous), Elevator ( 15 , 000 VA 15,000\text{ VA} 15 , 000 VA motor load).
Step 1: Calculate Total Dwelling Unit Connected Load Total Connected Dwelling Load = 20 units × 24 , 700 VA = 494 , 000 VA \text{Total Connected Dwelling Load} = 20\text{ units} \times 24,700\text{ VA} = \mathbf{494,000\text{ VA}} Total Connected Dwelling Load = 20 units × 24 , 700 VA = 494 , 000 VA
Step 2: Apply NEC Table 220.84 Demand Factor
For 20 dwelling units, Table 220.84 falls in the 18-to-20-unit tier at a 38 % 38\% 38% demand factor . Net Dwelling Unit Demand = 494 , 000 VA × 0.38 = 187 , 720 VA \text{Net Dwelling Unit Demand} = 494,000\text{ VA} \times 0.38 = \mathbf{187,720\text{ VA}} Net Dwelling Unit Demand = 494 , 000 VA × 0.38 = 187 , 720 VA
Step 3: Calculate Common House Loads (Part III)
Continuous Lighting = 4 , 000 VA × 1.25 = 5 , 000 VA = 4,000\text{ VA} \times 1.25 = 5,000\text{ VA} = 4 , 000 VA × 1.25 = 5 , 000 VA
Common Laundry = 8 , 000 VA = 8,000\text{ VA} = 8 , 000 VA
Elevator + 25% motor adder = 15 , 000 × 1.25 = 18 , 750 VA = 15,000 \times 1.25 = 18,750\text{ VA} = 15 , 000 × 1.25 = 18 , 750 VA
Total House Load: 5 , 000 + 8 , 000 + 18 , 750 = 31 , 750 VA 5,000 + 8,000 + 18,750 = \mathbf{31,750\text{ VA}} 5 , 000 + 8 , 000 + 18 , 750 = 31 , 750 VA
Step 4: Total Building Service Sizing Total Service Load = 187 , 720 VA + 31 , 750 VA = 219 , 470 VA \text{Total Service Load} = 187,720\text{ VA} + 31,750\text{ VA} = \mathbf{219,470\text{ VA}} Total Service Load = 187 , 720 VA + 31 , 750 VA = 219 , 470 VA Service Current = 219 , 470 VA 3 × 208 V = 219 , 470 360.25 = 609.2 Amperes \text{Service Current} = \frac{219,470\text{ VA}}{\sqrt{3} \times 208\text{ V}} = \frac{219,470}{360.25} = \mathbf{609.2\text{ Amperes}} Service Current = 3 × 208 V 219 , 470 VA = 360.25 219 , 470 = 609.2 Amperes
Service Selection: Standard 700 A 700\text{ A} 700 A or 800 A 800\text{ A} 800 A 208Y/120V 3-phase switchboard.
6. Plans Examiner Verification Checklist & Common Traps
Continuous Lighting Multiplier: Verify the designer did NOT apply 125% on top of a Table 220.42(A) unit load - the multiplier is already in the table. Confirm 125% IS applied to show-window, sign, and actual-connected-load lighting.
Show Window Linear Footage: Confirm 200 VA/linear ft (and 250 VA/ft continuous) is provided for retail display windows.
Table 220.47 Receptacle Demand: Verify commercial receptacle demand (1st 10 kVA @ 100%, rem @ 50%) is applied only to general convenience receptacles and not dedicated equipment.
Commercial Kitchen Two-Unit Floor: Check Table 220.56 calculations to ensure the total is never less than the two largest kitchen appliances.
Multifamily House Load Isolation: Confirm house loads are never factored through Table 220.84 and are calculated under Part III at 100%/125%.