3.2 Separate Facilities, Urinal Substitution & Exceptions

ICC Plumbing Plans Examiner P3

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Administration & Plan Review Workflow

1.1 ICC P3 Exam Overview: Format, References & Content Weights 1.2 Scope, Intent, and Administrative Authority 1.3 Construction Documents & Submittal Requirements 1.4 Inspections, Testing Protocols & Department Operations

2 Chapter 2: General Regulations, Materials & Pipe Protection

2.1 Piping Protection, Trenching & Bedding 2.2 Approved Piping Materials, Joints & Connections 2.3 Piping Hangers, Supports & Thermal Expansion

3 Chapter 3: Plumbing Fixtures, Occupant Load & Minimum Fixture Counts

3.1 Occupant Load Calculation & IPC Table 403.1 3.2 Separate Facilities, Urinal Substitution & Exceptions 3.3 Public Toilet Facilities & Customer Access Requirements 3.4 Multi-User, Single-User & Family/Assisted-Use Facilities

4 Chapter 4: Accessible Plumbing Facilities & Fixture Standards

4.1 ICC A117.1 Clearances & Accessible Fixture Dimensions 4.2 Accessible Showers, Bathtubs & Drinking Fountains 4.3 Fixture Construction, Flow Rates & Water Conservation

5 Chapter 5: Water Heaters, Fuel Gas Piping & Venting

5.1 Water Heater Design, Location & Clearances 5.2 Temperature & Pressure Relief Valves & Discharge Piping 5.3 Safety Controls, Drain Pans & Thermal Expansion 5.4 Fuel Gas Pipe Sizing: Demand, Tables & Length Methods (IFGC 402) 5.5 Gas Water Heater Venting & Combustion Air Calculations (IFGC 304 & 503) 5.6 Gas Piping Materials, Installation, Testing & Appliance Connections (IFGC 403–411, 624)

6 Chapter 6: Water Supply, Backflow Protection & Nonpotable Systems

6.1 Water Supply Fixture Units (WSFU) & Demand Estimation 6.2 Water Service & Distribution Pipe Sizing Calculations 6.3 Maximum Velocities, Water Hammer & Pressure Regulators 6.4 Backflow Prevention & Cross-Connection Control 6.5 Nonpotable Water Systems: Identification, Separation & Storage Tanks 6.6 Graywater Reuse, Rainwater Collection, Reclaimed Water & Subsurface Graywater

7 Chapter 7: Sanitary Drainage System Design & Sizing

7.1 Drainage Principles, Minimum Slope & Flow Velocities 7.2 Drainage Fixture Units (DFU) & System Load Assignment 7.3 Horizontal Branch & Building Drain/Sewer Sizing 7.4 Soil & Waste Stacks, Offsets & Multi-Story Systems

8 Chapter 8: Sanitary Cleanouts, Sumps & Sewage Ejectors

8.1 Cleanout Sizing, Spacing & Installation Requirements 8.2 Backwater Valves & Flood Protection 8.3 Sewage Ejectors, Sumps & Macerating Systems

9 Chapter 9: Venting Systems & Vent Sizing

9.1 Venting Fundamentals, Terminations & Flood Rim Rules 9.2 Fixture Vents, Individual & Common Vents, Trap-to-Vent Distances 9.3 Wet Venting, Circuit Venting & Combination Waste-Vent Systems 9.4 Vent Stacks, Stack Vents & Air Admittance Valves

10 Chapter 10: Traps, Interceptors & Special Waste Systems

10.1 Fixture Traps, Trap Seals & Design Requirements 10.2 Grease Interceptors: Sizing, Types & Plan Review 10.3 Oil Separators, Sand Interceptors & Indirect / Chemical Waste

11 Chapter 11: Storm Drainage Systems & Roof Drainage Design

11.1 Storm Drainage Hydraulics & 100-Year Rainfall Rates 11.2 Sizing Vertical Conductors, Leaders & Horizontal Storm Drains 11.3 Secondary (Emergency) Roof Drainage & Subsoil Systems

12 Chapter 12: Health Care Plumbing Systems

12.1 Health Care Plumbing Scope, Fixtures & Special Equipment 12.2 Health Care Water Supply Protection, Water Services & Medical Gas

3.2 Separate Facilities, Urinal Substitution & Exceptions

Key Takeaways Explain This Topic AI

IPC 403.2 requires separate facilities for each sex, with six exceptions in the 2024 edition including occupant loads of 15 or fewer.

Separate facilities are not required in mercantile occupancies of 100 or fewer or business occupancies of 25 or fewer (IPC 403.2 Exceptions 3 and 4).

Under IPC 424.2, urinals may replace up to 67 percent of required male water closets in assembly and educational occupancies.

In all other occupancies, IPC 424.2 limits urinal substitution to 50 percent of the required male water closets in each toilet room.

IPC 405.3.5 urinal partitions are at least 30 inches apart and project the greater of 18 inches or 6 inches past the lip, to at least 60 inches high.

Last updated: October 2026

Separate Facilities, Urinal Substitution & Exceptions

The International Plumbing Code balances the need for gender-specific sanitation facilities with practical design considerations for smaller occupancies. While separate facilities for males and females represent the baseline code requirement, IPC Section 403.2 contains specific exceptions where a single unisex facility is code-compliant. Furthermore, where male facilities are provided, IPC Section 424.2 permits urinals to substitute for a defined percentage of required water closets to optimize water efficiency and reduce waiting times.

1. Mandatory Separate Facilities: The Baseline Rule

IPC Section 403.2 establishes the core standard:

IPC 403.2 Separate Facilities : Where plumbing fixtures are required, separate facilities shall be provided for each sex.

This rule applies to all commercial, industrial, assembly, and institutional occupancies unless one of the statutory code exceptions explicitly applies. When separate facilities are required, the fixtures provided in each room must satisfy the respective male and female fixture counts calculated from IPC Table 403.1.

2. Exceptions to Separate Facilities (IPC 403.2, 2024 Edition)

The 2024 IPC lists six exceptions where separate toilet facilities for each sex are not required:

  • Exception Where Separate Facilities Are Not Required
  • 1 Dwelling units and sleeping units

2 Structures or tenant spaces with a total occupant load of 15 or fewer , including both employees and customers

  • 3 Mercantile occupancies with a maximum occupant load of 100 or fewer
  • 4 Business occupancies with a maximum occupant load of 25 or fewer

5 Where single-user toilet rooms are provided in accordance with IPC 403.1.2 (they need not be designated by sex)

6 Where rooms with both water closets and lavatories are designed for use by all persons regardless of sex, and privacy is provided for water closets per IPC 405.3.4 and for urinals per IPC 405.3.5

Plan Review Notes

Exception 2 threshold : An office of 2 , 400 gross sq ft 2,400 \text{ gross sq ft} 2 , 400 gross sq ft has an occupant load of 2 , 400 / 150 = 16 2,400 / 150 = 16 2 , 400/150 = 16 . Exception 2 does not apply, but Exception 4 (business, 25 or fewer) does, so one toilet room usable by all persons is acceptable.

Exception 3 scope : The exception removes the requirement to separate the facilities by sex. It does not replace the Table 403.1 ratios, so the examiner still confirms the fixture count under IPC 403.1.1 and 403.1.2.

Exceptions 5 and 6 are the 2024 code's path for all-gender design. Single-user rooms are deducted proportionately from the gender ratios (IPC 403.1.2). A multiple-user all-gender room must give every water closet a compartment and every urinal partitions.

3. Urinal Substitution Rules & Ratios (IPC Section 424.2)

In male toilet facilities, urinals may be installed in place of some required water closets. Urinals use less water (IPC Table 604.4 caps urinals at 1.0 gallon per flushing cycle and water closets at 1.6 gallons per flushing cycle , and many specified products use far less) and move users through faster.

However, IPC Section 424.2 caps the percentage of required male water closets that urinals may replace. The 2024 edition applies the cap in each bathroom or toilet room :

  • Occupancy Classification Maximum Urinal Substitution Percentage Applicable Ratio
  • Assembly Occupancies (Group A) Up to 67% Up to 2 3 \frac{2}{3} 3 2 ​ of required male water closets
  • Educational Occupancies (Group E) Up to 67% Up to 2 3 \frac{2}{3} 3 2 ​ of required male water closets
  • All Other Occupancies (B, F, I, M, R, S) Up to 50% Up to 1 2 \frac{1}{2} 2 1 ​ of required male water closets
  • The Three Non-Negotiable Substitution Rules

The Percentage Is a Ceiling, So a Water Closet Remains : Urinals may replace not more than 67 or 50 percent of the required water closets, and the result is never rounded up. A room that requires one water closet cannot substitute a urinal at all, because one urinal would be 100 percent.

Example : If a small workshop requires 1 male water closet, 50 % × 1 = 0.5 50\% \times 1 = 0.5 50% × 1 = 0.5 , so zero urinals may substitute. The required fixture must remain a water closet.

Urinals Do Not Add Fixture Count : Urinal substitution allows urinals to replace required water closets, but the total number of fixtures (water closets plus urinals) must equal or exceed the minimum male fixture count calculated from Table 403.1.

Female Restroom Invariance : Urinals can never be credited toward or substituted for female water closets. The female fixture count remains entirely unaffected by urinal installations.

4. Clearances and Spatial Dimensions (IPC Section 405.3.1)

Plumbing fixtures must have sufficient physical clearance to allow proper maintenance, user access, and sanitary separation.

Urinal Clearances

Center-to-Center Spacing : Where partitions do not separate adjacent urinals, they must be at least 30 inches center to center.

Centerline to Side Wall / Partition : Not less than 15 inches from the centerline of the urinal to any side wall, partition, vanity or other obstruction.

Front Clearance : Not less than 21 inches of clearance in front of the urinal to any wall, fixture or door. (For accessible urinals, ICC A117.1 requires a clear floor space of at least 30 inches by 48 inches.)

Water Closet Clearances and Compartments

Centerline to Side Wall / Partition : Not less than 15 inches from the centerline of the water closet to any side wall, partition or vanity (an accessible children's water closet may be 12 inches from the wall on one side).

Center-to-Center Spacing : Not less than 30 inches between centerlines of adjacent water closets not separated by partitions.

Front Clearance : Not less than 21 inches of clearance in front of the water closet.

Compartment Size : Water closet compartments must be at least 30 inches wide by 60 inches deep for floor-mounted water closets and 30 inches by 56 inches for wall-hung water closets.

Compartments Required (IPC 405.3.4) : Each public or employee water closet occupies a separate compartment with walls or partitions and a door. Exceptions include a single-occupant toilet room with a lockable door.

5. Privacy Partitions & Urinal Screens (IPC Section 405.3.5)

In public and employee multi-user restrooms, user privacy is a mandated sanitation standard, not merely an aesthetic choice. +-------------------------------------------------------------+

  • | URINAL PRIVACY SCREEN DIMENSIONS |
  • | |
  • | Finished Wall |
  • | | |
  • | |================== 18" Min. Projection =============>|
  • | | |
  • | | +---------------------------------------------+ |
  • | | | | |
  • | | | | |
  • | | | URINAL PRIVACY PARTITION | |
  • | | | | |
  • | | | | |
  • | | +---------------------------------------------+ |
  • | | | |
  • | | | 60" Min. Above Floor |
  • | | v |
  • | Finished Floor ========================================== |
  • | | <-- 12" Max. Bottom Clearance --> |
  • +-------------------------------------------------------------+
  • Technical Standards for Urinal Partitions (IPC 405.3.5)

When Required : Each urinal used by the public or employees must occupy a separate area with walls or partitions that provide privacy.

Spacing : The horizontal dimension between walls or partitions at each urinal must be at least 30 inches .

Outward Projection : Partitions extend from the wall surface at each side of the urinal at least 18 inches , or to a point at least 6 inches beyond the outermost front lip of the urinal measured from the finished back wall, whichever is greater .

Height : The partitions begin not more than 12 inches above the finished floor and extend not less than 60 inches above it.

Exceptions : Partitions are not required in a single-occupant or family/assisted-use toilet room with a lockable door. In child day care facilities with two or more urinals, one urinal may be without partitions.

  • 6. Worked Substitution Scenarios
  • Scenario A: High School Gymnasium (Group A-3)

Parameters : Calculated male occupant requirement = 9 Water Closets .

Occupancy Rule : Group A allows up to 67% (two-thirds) urinal substitution.

Calculation : Maximum Urinals = 9 × 2 3 = 6 urinals \text{Maximum Urinals} = 9 \times \frac{2}{3} = 6 \text{ urinals} Maximum Urinals = 9 × 3 2 ​ = 6 urinals

Resulting Fixture Mix :

Minimum Water Closets = 9 − 6 = 3 Water Closets 9 - 6 = \mathbf{3 \text{ Water Closets}} 9 − 6 = 3 Water Closets

Maximum Allowed Urinal Substitution = 6 Urinals \mathbf{6 \text{ Urinals}} 6 Urinals

Total Fixture Count = 3 + 6 = 9 fixtures 3 + 6 = 9 \text{ fixtures} 3 + 6 = 9 fixtures .

Plan Review Check : Ensure each urinal has partitions at least 30 inches apart that project the greater of 18 inches or 6 inches past the urinal lip and rise to at least 60 inches.

Scenario B: Corporate Headquarters (Group B)

Parameters : Calculated male occupant requirement = 4 Water Closets .

Occupancy Rule : Group B allows up to 50% urinal substitution.

Calculation : Maximum Urinals = 4 × 0.50 = 2 urinals \text{Maximum Urinals} = 4 \times 0.50 = 2 \text{ urinals} Maximum Urinals = 4 × 0.50 = 2 urinals

Resulting Fixture Mix :

Minimum Water Closets = 4 − 2 = 2 Water Closets 4 - 2 = \mathbf{2 \text{ Water Closets}} 4 − 2 = 2 Water Closets

Maximum Allowed Urinal Substitution = 2 Urinals \mathbf{2 \text{ Urinals}} 2 Urinals

Total Fixture Count = 2 + 2 = 4 fixtures 2 + 2 = 4 \text{ fixtures} 2 + 2 = 4 fixtures .

7. Plan Examiner Traps & Common Non-Compliance Issues

Over-Substitution in Group B : Applying the 67% Assembly ratio to an office or mercantile building. In Group B, substitution is capped at 50%.

Rounding Up the Substitution : When 2 water closets are required in a Group A occupancy, 2 × 0.67 = 1.34 2 \times 0.67 = 1.34 2 × 0.67 = 1.34 . Designers sometimes round this up to 2 urinals and provide no water closets. Because 424.2 sets a maximum, the allowance rounds down to 1 urinal, leaving 1 water closet.

Measuring Clearances to Rough Framing : Spacing must be verified to the finished wall surface . Measuring 15 inches to a gypsum stud line before tile and wallboard are installed results in a built clearance of only 14 inches, failing inspection.

Missing Urinal Partitions : Under IPC 405.3.5, every public or employee urinal needs partitions, even a single urinal next to a lavatory, unless the room is a single-occupant or family/assisted-use room with a lockable door.