2.2 Approved Piping Materials, Joints & Connections

ICC Plumbing Plans Examiner P3

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Administration & Plan Review Workflow

1.1 ICC P3 Exam Overview: Format, References & Content Weights 1.2 Scope, Intent, and Administrative Authority 1.3 Construction Documents & Submittal Requirements 1.4 Inspections, Testing Protocols & Department Operations

2 Chapter 2: General Regulations, Materials & Pipe Protection

2.1 Piping Protection, Trenching & Bedding 2.2 Approved Piping Materials, Joints & Connections 2.3 Piping Hangers, Supports & Thermal Expansion

3 Chapter 3: Plumbing Fixtures, Occupant Load & Minimum Fixture Counts

3.1 Occupant Load Calculation & IPC Table 403.1 3.2 Separate Facilities, Urinal Substitution & Exceptions 3.3 Public Toilet Facilities & Customer Access Requirements 3.4 Multi-User, Single-User & Family/Assisted-Use Facilities

4 Chapter 4: Accessible Plumbing Facilities & Fixture Standards

4.1 ICC A117.1 Clearances & Accessible Fixture Dimensions 4.2 Accessible Showers, Bathtubs & Drinking Fountains 4.3 Fixture Construction, Flow Rates & Water Conservation

5 Chapter 5: Water Heaters, Fuel Gas Piping & Venting

5.1 Water Heater Design, Location & Clearances 5.2 Temperature & Pressure Relief Valves & Discharge Piping 5.3 Safety Controls, Drain Pans & Thermal Expansion 5.4 Fuel Gas Pipe Sizing: Demand, Tables & Length Methods (IFGC 402) 5.5 Gas Water Heater Venting & Combustion Air Calculations (IFGC 304 & 503) 5.6 Gas Piping Materials, Installation, Testing & Appliance Connections (IFGC 403–411, 624)

6 Chapter 6: Water Supply, Backflow Protection & Nonpotable Systems

6.1 Water Supply Fixture Units (WSFU) & Demand Estimation 6.2 Water Service & Distribution Pipe Sizing Calculations 6.3 Maximum Velocities, Water Hammer & Pressure Regulators 6.4 Backflow Prevention & Cross-Connection Control 6.5 Nonpotable Water Systems: Identification, Separation & Storage Tanks 6.6 Graywater Reuse, Rainwater Collection, Reclaimed Water & Subsurface Graywater

7 Chapter 7: Sanitary Drainage System Design & Sizing

7.1 Drainage Principles, Minimum Slope & Flow Velocities 7.2 Drainage Fixture Units (DFU) & System Load Assignment 7.3 Horizontal Branch & Building Drain/Sewer Sizing 7.4 Soil & Waste Stacks, Offsets & Multi-Story Systems

8 Chapter 8: Sanitary Cleanouts, Sumps & Sewage Ejectors

8.1 Cleanout Sizing, Spacing & Installation Requirements 8.2 Backwater Valves & Flood Protection 8.3 Sewage Ejectors, Sumps & Macerating Systems

9 Chapter 9: Venting Systems & Vent Sizing

9.1 Venting Fundamentals, Terminations & Flood Rim Rules 9.2 Fixture Vents, Individual & Common Vents, Trap-to-Vent Distances 9.3 Wet Venting, Circuit Venting & Combination Waste-Vent Systems 9.4 Vent Stacks, Stack Vents & Air Admittance Valves

10 Chapter 10: Traps, Interceptors & Special Waste Systems

10.1 Fixture Traps, Trap Seals & Design Requirements 10.2 Grease Interceptors: Sizing, Types & Plan Review 10.3 Oil Separators, Sand Interceptors & Indirect / Chemical Waste

11 Chapter 11: Storm Drainage Systems & Roof Drainage Design

11.1 Storm Drainage Hydraulics & 100-Year Rainfall Rates 11.2 Sizing Vertical Conductors, Leaders & Horizontal Storm Drains 11.3 Secondary (Emergency) Roof Drainage & Subsoil Systems

12 Chapter 12: Health Care Plumbing Systems

12.1 Health Care Plumbing Scope, Fixtures & Special Equipment 12.2 Health Care Water Supply Protection, Water Services & Medical Gas

2.2 Approved Piping Materials, Joints & Connections

Key Takeaways Explain This Topic AI

IPC Table 605.3 lists copper tubing Types K, L and M for water service; Type DWV copper is a drainage material only.

IPC 605.2.1 requires drinking-water pipe, fittings and faucets to meet NSF 372 with a weighted average lead content of 0.25 percent or less.

IPC 605.21.3 and 705.10.2 require a purple ASTM F656 primer before non-purple ASTM D2564 cement on PVC water and DWV joints.

Under IPC 705.16.4, different plastics join with an approved adapter, except one ASTM D3138 ABS-to-PVC joint where the building drain meets the building sewer.

IPC 405.9 allows slip joints only on the trap inlet, trap outlet and within the trap seal, with a 12-inch access opening where they are concealed.

Last updated: October 2026

2.2 Approved Piping Materials, Joints & Connections

A central responsibility of the plumbing plans examiner is verifying that all specified piping materials, fittings, and joining methods appear in the material tables of Chapter 6 (Water Supply and Distribution: Tables 605.3, 605.4 and 605.5) and Chapter 7 (Sanitary Drainage: Tables 702.1 through 702.4), and that the joints follow Sections 605 and 705. Specifying unlisted materials or incompatible joints leads to catastrophic mechanical failures, potable water contamination, and property damage.

Material Identification and Certification (IPC Section 303)

Under IPC 303.1, each length of pipe and each pipe fitting, trap, fixture, material and device must bear the manufacturer's identification and any markings the referenced standard requires. Plastic pipe, fittings and components must be third-party certified as conforming to NSF 14 (IPC 303.3). Under IPC 303.4, products required to comply with a referenced standard must be listed by a third-party certification agency, and IPC 303.5 requires cast-iron soil pipe, fittings and couplings to be third-party listed and labeled. The marking and certification are what let an examiner confirm that the specified product matches a standard listed in the code's material tables.

  • Metallic Water & Drainage Piping Systems
  • 1. Copper Tubing (ASTM B88 & ASTM B306)

Copper tubing is color-coded by wall thickness, which determines its allowable operating pressures and mechanical durability:

Type K (Green Marking) : Heaviest wall. Often specified for underground water services and high-pressure risers, and available in annealed coils or hard-drawn lengths.

Type L (Blue Marking) : Medium wall. A common specification for interior commercial hot and cold water distribution.

Type M (Red Marking) : Thinnest pressure-rated wall. IPC Table 605.3 lists Types K, WK, L, WL, M and WM copper tubing for water service , and Table 605.4 lists them for water distribution. A rule against Type M underground is a local amendment or project specification, not a model-code requirement.

Type DWV (Yellow Marking - ASTM B306) : Thin wall for drainage, waste and vent piping (IPC Table 702.1). It is not listed in Tables 605.3 or 605.4, so it may not be used for water service or distribution.

2. Cast Iron Soil Pipe (ASTM A74 & CISPI 301)

Cast iron remains the premier material for sanitary drainage and acoustic dampening in commercial, healthcare, and multi-family construction:

Hub-and-Spigot Pipe (ASTM A74) : Available in Service Weight ( SV ) and Extra Heavy ( XH ). Spigot ends seat into hub bells fitted with compression elastomeric gaskets conforming to ASTM C564 (or historically lead and oakum, now rare in new construction).

Hubless (No-Hub) Pipe (CISPI 301) : Smooth-ended pipe joined by elastomeric neoprene sleeves wrapped in corrugated stainless steel shields with band clamps conforming to CISPI 310 (standard 2-band) or ASTM C1277 / ASTM C1540 (heavy-duty 4-band and 6-band couplings for high-vibration or high-rise installations).

3. Other Metallic Materials

Ductile Iron Water Pipe (AWWA C151/A21.51, AWWA C115/A21.15) : Listed in Table 605.3 for water service. It is usually cement-mortar lined and joined with push-on or mechanical joints.

Galvanized Steel Pipe (ASTM A53) : Listed for water service and distribution, but rarely specified today because of internal scaling. Joints to copper need a copper-alloy, dielectric or insulating fitting (IPC 605.23.1).

Stainless Steel (Types 304/304L and 316/316L; ASTM A269, A312, A778) : Listed in Tables 605.3 and 605.4 and used for high-purity water, chemical waste and press-connect systems.

  • Plastic Water & Drainage Piping Systems
  • 1. Polyvinyl Chloride (PVC-DWV)

Solid Wall PVC (ASTM D2665) : High-rigidity thermoplastic drainage, waste, and vent pipe. Universally approved for sanitary drainage above and below ground.

Cellular Core PVC (ASTM F891) : Co-extruded pipe featuring solid outer and inner skins with a foamed cellular plastic core. Highly cost-effective and lightweight, but plans examiners must verify local municipal amendments, as many commercial jurisdictions restrict cellular core pipe in fire-resistance-rated assemblies or multi-story buildings.

2. Acrylonitrile Butadiene Styrene (ABS-DWV)

Solid Wall ABS (ASTM D2661) & Cellular Core ABS (ASTM F628) : Black rigid plastic used exclusively for DWV systems. Has high impact resistance at freezing temperatures.

3. Cross-Linked Polyethylene (PEX - ASTM F876/F877)

PEX is the predominant material for residential and light-commercial water distribution:

Ratings : Standard hydrostatic ratings of 160 psi 160\text{ psi} 160 psi at 73.4 ∘ F 73.4^\circ\text{F} 73. 4 ∘ F , 100 psi 100\text{ psi} 100 psi at 180 ∘ F 180^\circ\text{F} 18 0 ∘ F , and 80 psi 80\text{ psi} 80 psi at 200 ∘ F 200^\circ\text{F} 20 0 ∘ F .

Manufacturing Classifications : PEX-a (peroxide method, > 85 % >85\% > 85% cross-linking, highest flexibility and thermal shape memory), PEX-b (silane method, 65 – 70 % 65\text{--}70\% 65 – 70% cross-linking), and PEX-c (electronic beam radiation, 70 – 75 % 70\text{--}75\% 70 – 75% cross-linking).

Fittings Standards : ASTM F1807 (metal insert with copper crimp rings), ASTM F2159 (plastic insert), ASTM F1960 (cold expansion with PEX reinforcing rings / ProPEX), and ASTM F2080 (cold expansion with compression sleeve).

4. Chlorinated Polyvinyl Chloride (CPVC - ASTM D2846 / ASTM F441 / ASTM F442)

Approved for hot and cold water distribution with a typical rating of 100 psi 100\text{ psi} 100 psi at 180 ∘ F 180^\circ\text{F} 18 0 ∘ F . Schedule 40 and 80 CPVC is used in commercial applications.

Lead content (IPC 605.2 and 605.2.1). Pipe, fittings, valves and faucets in the water supply system may contain not more than 8 percent lead. Products that supply water for drinking or cooking must comply with NSF 372 and have a weighted average lead content of 0.25 percent or less .

Code-Approved Joining Methods & Standards +--------------------------------------------------------------------------+

  • | SUMMARY OF PERMITTED JOINTS BY MATERIAL |
  • +----------------------+---------------------------+-----------------------+
  • | Material | Approved Joint Method | Standard Specification|
  • +----------------------+---------------------------+-----------------------+
  • | PVC-DWV | Solvent Cement & Primer | ASTM D2564 / F656 |
  • | ABS-DWV | Solvent Cement (NO Primer)| ASTM D2235 |
  • | Copper Tubing | Solder (Lead-Free <=0.2%) | ASTM B32 / ASTM B813 |
  • | Copper Tubing | Brazing (Melting >1000°F) | AWS A5.8 (BCuP series)|
  • | Copper Tubing | Press-Connect (EPDM seal) | ASME B16.51 |
  • | Copper / CPVC / PEX | Push-Fit | ASSE 1061 |
  • | Cast Iron (Hubless) | Shielded Coupling | CISPI 310 / ASTM C1277|
  • | Ductile Iron | Push-On / Mechanical | AWWA C111 / C606 |
  • +----------------------+---------------------------+-----------------------+
  • Solvent Welding Requirements & The Dissimilar Plastics Rule

PVC Primer Requirement (IPC Sections 605.21.3 and 705.10.2) : For PVC water piping and PVC DWV piping, joint surfaces must be clean and dry, a purple primer conforming to ASTM F656 must be applied, and then a solvent cement that is not purple and conforms to ASTM D2564 (or a listed CSA standard) is applied to all joint surfaces while the primer is wet. Joints follow ASTM D2855. The 2024 IPC text for these sections contains no exception that omits the primer, so a plan note calling for "one-step" cement without primer on PVC should be questioned.

ABS Cementing (IPC 705.2.2) : ABS joints use solvent cement conforming to ASTM D2235 (or CSA B181.1) applied to clean, dry joint surfaces. The code does not call for a primer on ABS.

The Dissimilar Plastics Rule : IPC 605.9 (water) and IPC 707.1 (drainage) prohibit solvent-cement joints between different types of plastic pipe . Under IPC 705.16.4, joints between different types of plastic drainage pipe must use an approved adapter fitting . The only exception is a single joint between ABS and PVC at the end of the building drain and the beginning of the building sewer , made with transition solvent cement complying with ASTM D3138 . Mechanical joints between different drainage materials follow ASTM C1173, C1460 or C1461 (IPC 705.16).

Soldering, Brazing & Lead-Free Mandates

Lead-free solder and flux (IPC 605.12.3 and 605.13.6) : Water supply piping must be joined with lead-free solder and fluxes, where "lead free" means 0.2 percent lead or less . Solder and flux for drinking-water piping must also conform to NSF 61.

Lead in pipe and fittings (IPC 605.2.1) : Products supplying drinking or cooking water must comply with NSF 372, with a weighted average lead content of 0.25 percent or less . The federal Safe Drinking Water Act uses the same definitions.

Soldered Joints : Joints are made per ASTM B828, with tube ends reamed, flux conforming to ASTM B813 , and solder conforming to ASTM B32 .

Brazed Joints : Filler metals conforming to AWS A5.8 (typically BCuP phosphorus-copper alloys) melt above 840 ∘ F 840^\circ\text{F} 84 0 ∘ F ( 449 ∘ C 449^\circ\text{C} 44 9 ∘ C ), the point that separates brazing from soldering. Medical gas piping is brazed under NFPA 99, which the IPC references for those systems.

Code-Prohibited Joints & Piping Connections

The plans examiner must flag and reject the joints prohibited by IPC 605.9 (water supply) and IPC 707.1 (drainage):

  • Prohibited Joint Water Supply (605.9) Drainage (707.1)
  • Cement or concrete joints Prohibited Prohibited
  • Joints made with fittings not approved for the specific installation Prohibited Prohibited

Solvent-cement joints between different types of plastic pipe Prohibited Prohibited, except the single ABS-to-PVC D3138 joint allowed by 705.16.4

  • Saddle-type fittings Prohibited Prohibited
  • Mastic or hot-pour bituminous joints Not listed Prohibited
  • Joints between different diameter pipes made with elastomeric rolling O-rings Not listed Prohibited

Two related rules round out the list:

Saddle-Type Fittings : Saddle valves clamped onto a pipe to feed an ice maker or humidifier pierce the pipe wall and rely on a gasket. They are prohibited on both water and drainage piping.

Slip Joints (IPC 405.9 and 1002.2) : Slip joints must use an approved elastomeric gasket and may be installed only on the trap inlet, the trap outlet and within the trap seal . Where a fixture has concealed slip-joint connections, an access panel or utility space at least 12 inches in its smallest dimension (or another approved arrangement) must give access for inspection and repair.

Plan Examiner Checklist: Approved Materials & Joint Verification

Lead-Free Compliance : Do drinking-water valves, fittings and faucets comply with NSF 372 ( 0.25 % 0.25\% 0.25% weighted average lead), and does the solder specification call for lead-free solder and flux ( 0.2 % 0.2\% 0.2% lead or less)?

Material Listing : Does each specified pipe appear in the correct table: Table 605.3 for water service, Table 605.4 for distribution, and Tables 702.1 through 702.3 for drainage? Type DWV copper, for example, is not listed for water piping.

Primer & Solvent Specification : Are PVC-DWV joints specified with ASTM F656 purple primer and ASTM D2564 cement? Is solvent welding between dissimilar PVC and ABS avoided?

Cast Iron Couplings : In multi-story cast iron drainage stacks, are CISPI 310 or ASTM C1277/C1540 heavy-duty shielded couplings specified rather than unshielded rubber boots?

Prohibited Joints Check : Are saddle-type fittings, cement joints, unapproved fittings and solvent joints between different plastics absent, and are slip joints only at trap inlets and outlets, with access where concealed?