Study guide
7.3 Horizontal Branch & Building Drain/Sewer Sizing
ICC Plumbing Plans Examiner P3
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Administration & Plan Review Workflow
1.1 ICC P3 Exam Overview: Format, References & Content Weights 1.2 Scope, Intent, and Administrative Authority 1.3 Construction Documents & Submittal Requirements 1.4 Inspections, Testing Protocols & Department Operations
2 Chapter 2: General Regulations, Materials & Pipe Protection
2.1 Piping Protection, Trenching & Bedding 2.2 Approved Piping Materials, Joints & Connections 2.3 Piping Hangers, Supports & Thermal Expansion
3 Chapter 3: Plumbing Fixtures, Occupant Load & Minimum Fixture Counts
3.1 Occupant Load Calculation & IPC Table 403.1 3.2 Separate Facilities, Urinal Substitution & Exceptions 3.3 Public Toilet Facilities & Customer Access Requirements 3.4 Multi-User, Single-User & Family/Assisted-Use Facilities
4 Chapter 4: Accessible Plumbing Facilities & Fixture Standards
4.1 ICC A117.1 Clearances & Accessible Fixture Dimensions 4.2 Accessible Showers, Bathtubs & Drinking Fountains 4.3 Fixture Construction, Flow Rates & Water Conservation
5 Chapter 5: Water Heaters, Fuel Gas Piping & Venting
5.1 Water Heater Design, Location & Clearances 5.2 Temperature & Pressure Relief Valves & Discharge Piping 5.3 Safety Controls, Drain Pans & Thermal Expansion 5.4 Fuel Gas Pipe Sizing: Demand, Tables & Length Methods (IFGC 402) 5.5 Gas Water Heater Venting & Combustion Air Calculations (IFGC 304 & 503) 5.6 Gas Piping Materials, Installation, Testing & Appliance Connections (IFGC 403–411, 624)
6 Chapter 6: Water Supply, Backflow Protection & Nonpotable Systems
6.1 Water Supply Fixture Units (WSFU) & Demand Estimation 6.2 Water Service & Distribution Pipe Sizing Calculations 6.3 Maximum Velocities, Water Hammer & Pressure Regulators 6.4 Backflow Prevention & Cross-Connection Control 6.5 Nonpotable Water Systems: Identification, Separation & Storage Tanks 6.6 Graywater Reuse, Rainwater Collection, Reclaimed Water & Subsurface Graywater
7 Chapter 7: Sanitary Drainage System Design & Sizing
7.1 Drainage Principles, Minimum Slope & Flow Velocities 7.2 Drainage Fixture Units (DFU) & System Load Assignment 7.3 Horizontal Branch & Building Drain/Sewer Sizing 7.4 Soil & Waste Stacks, Offsets & Multi-Story Systems
8 Chapter 8: Sanitary Cleanouts, Sumps & Sewage Ejectors
8.1 Cleanout Sizing, Spacing & Installation Requirements 8.2 Backwater Valves & Flood Protection 8.3 Sewage Ejectors, Sumps & Macerating Systems
9 Chapter 9: Venting Systems & Vent Sizing
9.1 Venting Fundamentals, Terminations & Flood Rim Rules 9.2 Fixture Vents, Individual & Common Vents, Trap-to-Vent Distances 9.3 Wet Venting, Circuit Venting & Combination Waste-Vent Systems 9.4 Vent Stacks, Stack Vents & Air Admittance Valves
10 Chapter 10: Traps, Interceptors & Special Waste Systems
10.1 Fixture Traps, Trap Seals & Design Requirements 10.2 Grease Interceptors: Sizing, Types & Plan Review 10.3 Oil Separators, Sand Interceptors & Indirect / Chemical Waste
11 Chapter 11: Storm Drainage Systems & Roof Drainage Design
11.1 Storm Drainage Hydraulics & 100-Year Rainfall Rates 11.2 Sizing Vertical Conductors, Leaders & Horizontal Storm Drains 11.3 Secondary (Emergency) Roof Drainage & Subsoil Systems
12 Chapter 12: Health Care Plumbing Systems
12.1 Health Care Plumbing Scope, Fixtures & Special Equipment 12.2 Health Care Water Supply Protection, Water Services & Medical Gas
7.3 Horizontal Branch & Building Drain/Sewer Sizing
Key Takeaways Explain This Topic AI
IPC Table 710.1(1) sizes building drains and sewers by slope: a 4-inch drain carries 180 DFU at 1/8 inch and 216 DFU at 1/4 inch per foot.
IPC Table 710.1(2) sizes horizontal fixture branches regardless of slope: 2-inch carries 6 DFU, 3-inch 20 DFU and 4-inch 160 DFU.
A building drain serving a water closet must be at least 3 inches in diameter (IPC Table 710.1(1) footnote a).
The 2024 IPC drainage tables do not limit the number of water closets on 3-inch pipe; the limit is set by DFU capacity.
IPC Table 709.1 note e bars rating water closets and urinals at a lower DFU value for building drain and sewer loads unless testing confirms it.
Last updated: October 2026
Horizontal Branch & Building Drain/Sewer Sizing
Once drainage fixture units (DFU) are tabulated, the plans examiner verifies every horizontal drain against IPC Section 710 . The 2024 IPC uses two different tables , and choosing the right one is the first test:
Table 710.1(1), Building Drains and Sewers: Sizes the building drain , the building sewer and branches of the building drain . Capacity depends on slope .
Table 710.1(2), Horizontal Fixture Branches and Stacks: Sizes horizontal fixture branches (other than branches of the building drain) and soil and waste stacks . The horizontal branch column does not vary with slope.
The terms come from IPC Chapter 2:
Horizontal Branch Drain: A drain branch pipe extending laterally from a soil or waste stack or building drain, with or without vertical sections or branches, that receives the discharge from two or more fixture drains or branches and conducts it to the soil or waste stack or the building drain.
Building Drain: The lowest piping of the drainage system that receives discharge from soil, waste and other drainage pipes inside the building and extends 30 inches in developed length beyond the exterior walls , conveying the drainage to the building sewer.
Building Sewer: The part of the drainage system that extends from the end of the building drain to a public sewer, private sewer, individual sewage disposal system or other point of disposal. RESTROOM FIXTURES
- ┌───┐ ┌───┐ ┌───┐
- │WC │ │WC │ │LAV│
- └─┬─┘ └─┬─┘ └─┬─┘
- ──┴──────┴──────┴──────► HORIZONTAL FIXTURE BRANCH
- Table 710.1(2), branch column (no slope variable)
- │
- ▼ Stack: Table 710.1(2) stack columns
- ════════════════════════════════════════════════════════════════════
- │
- ──────────────────────────────────────────► BUILDING DRAIN (to 30" outside wall)
- Exterior Building Wall │ Table 710.1(1), by slope
- ══════════════════════════════╪════════════
- ▼
- ──────────────────────────────────────────► BUILDING SEWER (to public sewer)
- Table 710.1(1), by slope
- IPC Table 710.1(1): Building Drains and Sewers (2024)
Maximum DFU connected to any portion of the building drain or building sewer, including branches of the building drain:
- Pipe Diameter (inches) 1/16 inch per foot 1/8 inch per foot 1/4 inch per foot 1/2 inch per foot
- 1-1/4 — — 1 1
- 1-1/2 — — 3 3
- 2 — — 21 26
- 2-1/2 — — 24 31
- 3 — 36 42 50
- 4 — 180 216 250
- 5 — 390 480 575
- 6 — 700 840 1,000
- 8 1,400 1,600 1,920 2,300
- 10 2,500 2,900 3,500 4,200
- 12 3,900 4,600 5,600 6,700
- 15 7,000 8,300 10,000 12,000
Footnote a: The minimum size of any building drain serving a water closet is 3 inches .
IPC Table 710.1(2): Horizontal Fixture Branches (Branch Column)
- Pipe Diameter (inches) Total for Horizontal Branch (DFU)
- 1-1/2 3
- 2 6
- 2-1/2 12
- 3 20
- 4 160
- 5 360
- 6 620
- 8 1,400
- 10 2,500
- 12 3,900
- 15 7,000
The stack columns of the same table are covered in Section 7.4.
The Critical Difference: Horizontal Branches vs. Building Drains
A common plan review error is sizing a fixture branch from the building drain table. Compare a 2-inch pipe:
As a horizontal fixture branch (Table 710.1(2)): 6 DFU , regardless of slope.
As a building drain at 1/4 inch per foot (Table 710.1(1)): 21 DFU .
Why Fixture Branches Are Rated Lower
Fixture branches take discharge directly from traps as sudden surges, often from fixtures close together, so the pipe can momentarily fill and disturb trap seals. By the time flow reaches the building drain, discharges from many fixtures have merged into a steadier stream, and the larger, sloped drain carries more load at the same depth. Building drain capacity also rises with slope, which is why Table 710.1(1) has slope columns and the branch column does not.
Water Closet Rules for Small Drains
The 2024 IPC controls water closets on small drains through minimum sizes , not through a count of water closets: ┌────────────────────────────────────────────────────────────────────────┐
- │ WATER CLOSETS ON 3-INCH PIPE (2024 IPC) │
- ├───────────────────────────────────┬────────────────────────────────────┤
- │ HORIZONTAL FIXTURE BRANCH │ BUILDING DRAIN / SEWER │
- │ Table 710.1(2): 20 DFU max │ Table 710.1(1): 36 / 42 / 50 DFU │
- │ (any slope) │ at 1/8, 1/4, 1/2 inch per foot │
- │ │ Footnote a: building drain serving│
- │ A 3-inch branch with three │ a water closet is at least 3 in. │
- │ water closets (12 DFU) complies │ No separate count limit on water │
- │ on DFU │ closets in the 2024 tables │
- └───────────────────────────────────┴────────────────────────────────────┘
- Rule 1: Size by DFU
A 3-inch horizontal fixture branch may carry up to 20 DFU . Three public 1.6-gpf water closets (3 × 4 = 12 DFU) plus three lavatories (3 DFU) total 15 DFU, which a 3-inch branch carries. Older code editions and other model codes (such as the UPC) limit the number of water closets on 3-inch pipe; that limit does not appear in the 2024 IPC tables. Check local amendments before applying it.
Rule 2: Minimum Pipe Sizes Tied to Water Closets
Building drain (Table 710.1(1) footnote a): Any building drain serving a water closet must be at least 3 inches .
Water closet connections (IPC 425.4 and 704.2): A 4-by-3-inch closet bend is acceptable. Where a 3-inch bend is used, a 4-by-3-inch flange receives the fixture horn, and that is not treated as a reduction in the direction of flow.
Trap size (Table 709.1 note d): The trap must be consistent with the water closet's outlet size.
Rule 3: Building Sewers and Local Rules
Table 710.1(1) sizes building sewers by DFU and slope, so a 3-inch sewer is acceptable under the IPC when the load fits. Many utilities require a 4-inch minimum lateral for maintenance; that is a local or utility rule. Sewers 8 inches and larger also need manholes rather than cleanouts (IPC 708.1.2 and 708.1.8).
Worked Sizing Review: Single-Story Office Building
Scenario: A single-story office building has three fixture branches discharging to one building drain. All piping is sloped at 1/4 inch per foot . Branch A (Men's Restroom): Branch B (Women's Restroom): Branch C (Break Area):
- 2 public 1.6-gpf WCs (8 DFU) - 3 public 1.6-gpf WCs (12 DFU) - 2 sinks (4 DFU)
- 2 urinals, 1 gpf (4 DFU) - 3 lavatories (3 DFU) - 1 service sink (2 DFU)
- 2 lavatories (2 DFU) Subtotal = 15 DFU - 1 drinking fountain (1/2)
- Subtotal = 14 DFU Subtotal = 6.5 DFU
- │ │ │
- ▼ ▼ ▼
- ┌─────────────────────────────────────────────────────────────────────────────┐
- │ BUILDING DRAIN (Sloped at 1/4 inch per foot) │
- └─────────────────────────────────────────────────────────────────────────────┘
- Step-by-Step Plans Examination
Branch A (Men's Restroom), shown as 3 inches:
Load: 8 + 4 + 2 = 14 DFU 8 + 4 + 2 = 14\text{ DFU} 8 + 4 + 2 = 14 DFU (urinals using 1 gpf or less are 2 DFU each on a fixture branch).
Table 710.1(2): a 3-inch horizontal branch carries 20 DFU. Approved. A 2-inch branch (6 DFU) would be too small.
Branch B (Women's Restroom), shown as 3 inches:
Load: 12 + 3 = 15 DFU 12 + 3 = 15\text{ DFU} 12 + 3 = 15 DFU .
Table 710.1(2): 15 DFU does not exceed 20 DFU. Approved. Three water closets on a 3-inch branch are acceptable under the 2024 tables.
Branch C (Break Area), shown as 2 inches:
Load: 4 + 2 + 0.5 = 6.5 DFU 4 + 2 + 0.5 = 6.5\text{ DFU} 4 + 2 + 0.5 = 6.5 DFU .
Table 710.1(2): a 2-inch horizontal branch carries only 6 DFU. Rejected. Upsize to 2-1/2 inches (12 DFU) or 3 inches.
Building Drain, shown as 3 inches at 1/4 inch per foot:
Fixture-branch loads total 14 + 15 + 6.5 = 35.5 DFU 14 + 15 + 6.5 = 35.5\text{ DFU} 14 + 15 + 6.5 = 35.5 DFU .
For building drains and sewers, Table 709.1 note e does not allow the lower urinal rating unless testing confirms it, so the two urinals count at 4 DFU each: 35.5 + 4 = 39.5 DFU 35.5 + 4 = 39.5\text{ DFU} 35.5 + 4 = 39.5 DFU .
Table 710.1(1): a 3-inch building drain at 1/4 inch per foot carries 42 DFU, and footnote a's 3-inch minimum is met. Approved.
Check the slope: At 1/8 inch per foot, the same 3-inch drain would carry only 36 DFU and would have to be 4 inches (180 DFU).