5.4 Fuel Gas Pipe Sizing: Demand, Tables & Length Methods (IFGC 402)

ICC Plumbing Plans Examiner P3

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Administration & Plan Review Workflow

1.1 ICC P3 Exam Overview: Format, References & Content Weights 1.2 Scope, Intent, and Administrative Authority 1.3 Construction Documents & Submittal Requirements 1.4 Inspections, Testing Protocols & Department Operations

2 Chapter 2: General Regulations, Materials & Pipe Protection

2.1 Piping Protection, Trenching & Bedding 2.2 Approved Piping Materials, Joints & Connections 2.3 Piping Hangers, Supports & Thermal Expansion

3 Chapter 3: Plumbing Fixtures, Occupant Load & Minimum Fixture Counts

3.1 Occupant Load Calculation & IPC Table 403.1 3.2 Separate Facilities, Urinal Substitution & Exceptions 3.3 Public Toilet Facilities & Customer Access Requirements 3.4 Multi-User, Single-User & Family/Assisted-Use Facilities

4 Chapter 4: Accessible Plumbing Facilities & Fixture Standards

4.1 ICC A117.1 Clearances & Accessible Fixture Dimensions 4.2 Accessible Showers, Bathtubs & Drinking Fountains 4.3 Fixture Construction, Flow Rates & Water Conservation

5 Chapter 5: Water Heaters, Fuel Gas Piping & Venting

5.1 Water Heater Design, Location & Clearances 5.2 Temperature & Pressure Relief Valves & Discharge Piping 5.3 Safety Controls, Drain Pans & Thermal Expansion 5.4 Fuel Gas Pipe Sizing: Demand, Tables & Length Methods (IFGC 402) 5.5 Gas Water Heater Venting & Combustion Air Calculations (IFGC 304 & 503) 5.6 Gas Piping Materials, Installation, Testing & Appliance Connections (IFGC 403–411, 624)

6 Chapter 6: Water Supply, Backflow Protection & Nonpotable Systems

6.1 Water Supply Fixture Units (WSFU) & Demand Estimation 6.2 Water Service & Distribution Pipe Sizing Calculations 6.3 Maximum Velocities, Water Hammer & Pressure Regulators 6.4 Backflow Prevention & Cross-Connection Control 6.5 Nonpotable Water Systems: Identification, Separation & Storage Tanks 6.6 Graywater Reuse, Rainwater Collection, Reclaimed Water & Subsurface Graywater

7 Chapter 7: Sanitary Drainage System Design & Sizing

7.1 Drainage Principles, Minimum Slope & Flow Velocities 7.2 Drainage Fixture Units (DFU) & System Load Assignment 7.3 Horizontal Branch & Building Drain/Sewer Sizing 7.4 Soil & Waste Stacks, Offsets & Multi-Story Systems

8 Chapter 8: Sanitary Cleanouts, Sumps & Sewage Ejectors

8.1 Cleanout Sizing, Spacing & Installation Requirements 8.2 Backwater Valves & Flood Protection 8.3 Sewage Ejectors, Sumps & Macerating Systems

9 Chapter 9: Venting Systems & Vent Sizing

9.1 Venting Fundamentals, Terminations & Flood Rim Rules 9.2 Fixture Vents, Individual & Common Vents, Trap-to-Vent Distances 9.3 Wet Venting, Circuit Venting & Combination Waste-Vent Systems 9.4 Vent Stacks, Stack Vents & Air Admittance Valves

10 Chapter 10: Traps, Interceptors & Special Waste Systems

10.1 Fixture Traps, Trap Seals & Design Requirements 10.2 Grease Interceptors: Sizing, Types & Plan Review 10.3 Oil Separators, Sand Interceptors & Indirect / Chemical Waste

11 Chapter 11: Storm Drainage Systems & Roof Drainage Design

11.1 Storm Drainage Hydraulics & 100-Year Rainfall Rates 11.2 Sizing Vertical Conductors, Leaders & Horizontal Storm Drains 11.3 Secondary (Emergency) Roof Drainage & Subsoil Systems

12 Chapter 12: Health Care Plumbing Systems

12.1 Health Care Plumbing Scope, Fixtures & Special Equipment 12.2 Health Care Water Supply Protection, Water Services & Medical Gas

5.4 Fuel Gas Pipe Sizing: Demand, Tables & Length Methods (IFGC 402)

Key Takeaways Explain This Topic AI

IFGC 402.2 sizes gas piping on the total connected hourly load, assuming every appliance runs at full input at once.

IFGC 402.2 requires the gas flow rate to be adjusted for altitude where the installation is above 2,000 feet.

IFGC 402.4.1 sizes every section with the longest length from the point of delivery to the most remote outlet.

IFGC 402.4.2 lets branches use the length from the point of delivery to the most remote outlet on each branch.

IFGC 402.7 limits gas piping inside buildings to 5 psig unless joints are welded or brazed or another listed condition applies.

Last updated: October 2026

Fuel Gas Pipe Sizing: Demand, Tables & Length Methods (IFGC 402)

The ICC P3 outline lists "Piping, Combustion Air & Venting (fuel gas sizing)" at 7 percent , the largest share of the Water Heaters domain, and names the 2024 IFGC as a reference. Replacing a 40,000 Btu/h tank water heater with a 199,000 Btu/h tankless unit can make the existing gas piping too small. This section covers the sizing rules a plans examiner checks.

Step 1: Determine the Demand (IFGC 402.1 and 402.2)

Supply requirement (402.1): Piping supplies enough gas for the maximum demand , and delivers gas to each appliance inlet at no less than the minimum supply pressure the appliance requires.

Maximum demand (402.2): The flow is the sum of the maximum inputs of the appliances served. Pipe is sized on the total connected hourly load , assuming all appliances can run at full capacity at once. A diversity factor may be used only where it can be established .

Altitude (402.2): The flow is adjusted for altitude where the installation is above 2,000 feet .

Converting Btu/h to cubic feet per hour (cfh): The sizing tables are in cfh. Divide the appliance input by the gas heating value, which the supplier provides. Designers commonly assume about 1,000 Btu per cubic foot for natural gas, so a 40,000 Btu/h water heater needs about 40 cfh.

Step 2: Choose a Sizing Method (IFGC 402.3)

Gas piping is sized by one of these:

Tables or equations in Section 402.4 or 402.5.

Sizing tables in a listed piping system's installation instructions, such as CSST manufacturer tables.

Engineering methods.

Tables 402.4(1) through 402.4(37) cover Schedule 40 steel, copper tubing, CSST, polyethylene and other materials for natural gas and propane at several inlet pressures and pressure drops. The low-pressure equation (Equation 4-1) applies below 1-1/2 psi, and the high-pressure equation (Equation 4-2) applies at 1-1/2 psi and above. Both require pipe with smooth inside walls.

Reading Table 402.4(1): Schedule 40 Metallic Pipe

Natural gas, inlet pressure less than 2 psi, 0.3-inch w.c. pressure drop, specific gravity 0.60. Capacity in cfh.

  • Length (ft) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in
  • 10 131 273 514 1,060 1,580 3,050
  • 20 90 188 353 726 1,090 2,090
  • 30 72 151 284 583 873 1,680
  • 40 62 129 243 499 747 1,440
  • 50 55 114 215 442 662 1,280
  • 60 50 104 195 400 600 1,160
  • 80 42 89 167 343 514 989
  • 100 38 79 148 304 455 877

Table 402.4(2) covers the same pipe at a 0.5-inch w.c. pressure drop, where capacities are higher. For example, 1-inch pipe at 60 feet carries 257 cfh instead of 195 cfh. The designer must still show the appliance gets its minimum inlet pressure ( 402.6 ).

Step 3: Determine the Length (IFGC 402.4.1–402.4.3)

Longest length method (402.4.1): Every section is sized using the longest length from the point of delivery to the most remote outlet , together with the load carried by that section.

Branch length method (402.4.2): Sections on the longest run use the longest length. Each branch not already sized uses the length from the point of delivery to the most remote outlet on that branch .

Hybrid pressure (402.4.3): Higher-pressure piping is sized with the length to the most remote line pressure regulator . Piping downstream of the regulator is sized with the length from the regulator to its most remote outlet.

  • Worked Example: Single-Family Gas Piping METER ──A (10 ft)── T1 ──B (20 ft)── T2 ──C (30 ft)── FURNACE 100 cfh
  • │ │
  • 20 ft│ 10 ft│
  • ▼ ▼
  • RANGE 65 cfh WATER HEATER 40 cfh
  • Meter to furnace = 60 ft (longest) Meter to range = 30 ft
  • Meter to water heater = 40 ft

Longest length method (use the 60-foot row for every section):

  • Section Load (cfh) Size from 60-ft Row Why
  • A (meter to T1) 205 1-1/4 in 1 in carries only 195 cfh; 1-1/4 in carries 400
  • B (T1 to T2) 140 1 in 3/4 in carries only 104 cfh; 1 in carries 195
  • C (to furnace) 100 3/4 in 3/4 in carries 104 cfh
  • Water heater branch 40 1/2 in 1/2 in carries 50 cfh
  • Range branch 65 3/4 in 1/2 in carries only 50 cfh

Branch length method: Sections A, B and C are unchanged. The range branch uses its own 30-foot length: 1/2-inch pipe carries 72 cfh at 30 feet, so it can be 1/2 inch . The water heater branch uses 40 feet, where 1/2-inch pipe carries 62 cfh, so it stays 1/2 inch . The branch length method can reduce branch sizes but never undersizes the main.

Maximum Operating Pressure Inside Buildings (IFGC 402.7)

Gas piping inside buildings may not exceed 5 psig unless one of these applies:

Joints are welded or brazed , or flanged with welded or brazed pipe-to-flange connections.

Fittings are listed to ANSI LC-4/CSA 6.32 (press-connect).

Piping is in a ventilated chase or otherwise enclosed.

Piping is in areas used only for industrial processing or heating, research, warehousing, or boiler or mechanical rooms .

The installation is temporary during construction or serves agricultural appliances.

The system is LP-gas above 20 psi complying with NFPA 58.

Plan Reviewer Verification Checklist: Gas Pipe Sizing

Load Schedule: Every appliance input is listed in Btu/h and converted to cfh, and the total connected load is shown (402.2).

Altitude: The flow is adjusted for sites above 2,000 feet (402.2).

Method Stated: The table number, pressure drop and length method are identified (402.3 and 402.4).

Lengths: The longest run is measured to the most remote outlet, and branch lengths are measured from the point of delivery (402.4.1 and 402.4.2).

Inlet Pressure: Each appliance receives at least its listed minimum inlet pressure (402.6).

Pressure Limit: Interior piping above 5 psig meets a 402.7 condition.