6.6 Graywater Reuse, Rainwater Collection, Reclaimed Water & Subsurface Graywater

ICC Plumbing Plans Examiner P3

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Administration & Plan Review Workflow

1.1 ICC P3 Exam Overview: Format, References & Content Weights 1.2 Scope, Intent, and Administrative Authority 1.3 Construction Documents & Submittal Requirements 1.4 Inspections, Testing Protocols & Department Operations

2 Chapter 2: General Regulations, Materials & Pipe Protection

2.1 Piping Protection, Trenching & Bedding 2.2 Approved Piping Materials, Joints & Connections 2.3 Piping Hangers, Supports & Thermal Expansion

3 Chapter 3: Plumbing Fixtures, Occupant Load & Minimum Fixture Counts

3.1 Occupant Load Calculation & IPC Table 403.1 3.2 Separate Facilities, Urinal Substitution & Exceptions 3.3 Public Toilet Facilities & Customer Access Requirements 3.4 Multi-User, Single-User & Family/Assisted-Use Facilities

4 Chapter 4: Accessible Plumbing Facilities & Fixture Standards

4.1 ICC A117.1 Clearances & Accessible Fixture Dimensions 4.2 Accessible Showers, Bathtubs & Drinking Fountains 4.3 Fixture Construction, Flow Rates & Water Conservation

5 Chapter 5: Water Heaters, Fuel Gas Piping & Venting

5.1 Water Heater Design, Location & Clearances 5.2 Temperature & Pressure Relief Valves & Discharge Piping 5.3 Safety Controls, Drain Pans & Thermal Expansion 5.4 Fuel Gas Pipe Sizing: Demand, Tables & Length Methods (IFGC 402) 5.5 Gas Water Heater Venting & Combustion Air Calculations (IFGC 304 & 503) 5.6 Gas Piping Materials, Installation, Testing & Appliance Connections (IFGC 403–411, 624)

6 Chapter 6: Water Supply, Backflow Protection & Nonpotable Systems

6.1 Water Supply Fixture Units (WSFU) & Demand Estimation 6.2 Water Service & Distribution Pipe Sizing Calculations 6.3 Maximum Velocities, Water Hammer & Pressure Regulators 6.4 Backflow Prevention & Cross-Connection Control 6.5 Nonpotable Water Systems: Identification, Separation & Storage Tanks 6.6 Graywater Reuse, Rainwater Collection, Reclaimed Water & Subsurface Graywater

7 Chapter 7: Sanitary Drainage System Design & Sizing

7.1 Drainage Principles, Minimum Slope & Flow Velocities 7.2 Drainage Fixture Units (DFU) & System Load Assignment 7.3 Horizontal Branch & Building Drain/Sewer Sizing 7.4 Soil & Waste Stacks, Offsets & Multi-Story Systems

8 Chapter 8: Sanitary Cleanouts, Sumps & Sewage Ejectors

8.1 Cleanout Sizing, Spacing & Installation Requirements 8.2 Backwater Valves & Flood Protection 8.3 Sewage Ejectors, Sumps & Macerating Systems

9 Chapter 9: Venting Systems & Vent Sizing

9.1 Venting Fundamentals, Terminations & Flood Rim Rules 9.2 Fixture Vents, Individual & Common Vents, Trap-to-Vent Distances 9.3 Wet Venting, Circuit Venting & Combination Waste-Vent Systems 9.4 Vent Stacks, Stack Vents & Air Admittance Valves

10 Chapter 10: Traps, Interceptors & Special Waste Systems

10.1 Fixture Traps, Trap Seals & Design Requirements 10.2 Grease Interceptors: Sizing, Types & Plan Review 10.3 Oil Separators, Sand Interceptors & Indirect / Chemical Waste

11 Chapter 11: Storm Drainage Systems & Roof Drainage Design

11.1 Storm Drainage Hydraulics & 100-Year Rainfall Rates 11.2 Sizing Vertical Conductors, Leaders & Horizontal Storm Drains 11.3 Secondary (Emergency) Roof Drainage & Subsoil Systems

12 Chapter 12: Health Care Plumbing Systems

12.1 Health Care Plumbing Scope, Fixtures & Special Equipment 12.2 Health Care Water Supply Protection, Water Services & Medical Gas

6.6 Graywater Reuse, Rainwater Collection, Reclaimed Water & Subsurface Graywater

Key Takeaways Explain This Topic AI

IPC 1302.2 limits on-site reuse sources to bathtubs, showers, lavatories, clothes washers and laundry trays, unless other sources are approved.

IPC 1302.2.1 prohibits collecting kitchen sink, dishwasher, water softener, reverse osmosis reject and wet-hood scrubber wastewater for on-site reuse.

IPC 1302.6 limits untreated graywater storage to 24 hours, and IPC 1302.6.1 requires NSF 350 treatment for flushing.

IPC 1303.5.1 requires rainwater gutters and downspouts to slope at least 1/8 inch per foot, except siphonic systems.

IPC 1403.2 requires subsurface graywater distribution pipe of at least 3 inches, sloped 2 to 4 inches per 100 feet.

Last updated: October 2026

Graywater Reuse, Rainwater Collection, Reclaimed Water & Subsurface Graywater

Section 6.5 covered the rules common to all nonpotable systems. This section covers the three source-specific systems in IPC Sections 1302 through 1304 , plus Chapter 14 subsurface graywater soil absorption systems. On the P3 exam, expect questions on allowed and prohibited sources, required valves, rainwater collection devices, pressure limits and absorption area calculations.

On-Site Nonpotable Water Reuse Systems (IPC 1302)

Governing standard (1302.1): ASTM E2635 and Section 1302 govern on-site reuse systems, where the jurisdiction permits them.

Sources (1302.2 and 1302.2.1)

  • Allowed Sources (1302.2) Prohibited Sources (1302.2.1)
  • Bathtubs Wastewater containing urine or fecal matter
  • Showers Kitchen sink wastewater
  • Lavatories Dishwasher wastewater
  • Clothes washers Water softener discharge
  • Laundry trays Reverse osmosis reject water
  • Other nonpotable sources, where approved Wet-hood scrubber wastewater

Wastewater containing urine or feces discharges to the sanitary drainage system per Chapter 7.

Collection, Treatment and Valves

Traps (1302.3): Fixtures that discharge to a reuse system have traps per Section 1002.4.

Collection pipe (1302.4): DWV piping materials per Section 702, installed per 704, jointed per 705 and sized per 710 , like a sanitary drain.

Filtration (1302.5): Filters have access, a pressure gauge or other service indicator, and shutoff valves immediately upstream and downstream .

Retention limit (1302.6): Water containing untreated graywater may be held in collection reservoirs for not more than 24 hours .

Flushing use (1302.6.1): Graywater used to flush water closets and urinals is disinfected and treated by a system complying with NSF 350 .

Bypass valve (1302.8.1): One three-way diverter valve listed to NSF 50 (or another approved device) is installed upstream of each tank or drain field. It diverts untreated water to the sanitary sewer for servicing and goes downstream of fixture traps and vent connections . Two shutoff valves may not serve as the bypass.

Backwater valves (1302.8.2): One or more backwater valves (per Section 714) go on each overflow and tank drain pipe.

Pressure (1302.10): Where pump pressure exceeds 80 psi static , a PRV reduces the distribution pressure to 80 psi or less.

Tank setbacks (Table 1302.7.1): 2 feet from the critical root zone of protected trees; 5 feet from lot lines, seepage pits, septic tanks and the water service; 10 feet from a public water main; and 50 feet from streams, lakes and water wells. Tank outlets are at least 4 inches above the tank bottom and do not skim the surface (1302.7.2). ON-SITE GRAYWATER REUSE SYSTEM — PLAN REVIEW FLOW (IPC 1302)

  • Showers / tubs / lavs / washers ──► Trap + vent (DWV, Sections 702–710)
  • │
  • ▼
  • ┌── 3-way diverter valve, NSF 50 (1302.8.1) ──┐
  • │ │
  • ▼ ▼
  • Filter (gauge + isolation valves) Sanitary sewer
  • │ (bypass for service)
  • ▼
  • Storage tank (≤24 h untreated, 1302.6) ── overflow/drain + backwater valve
  • │
  • ▼
  • NSF 350 treatment for WC/urinal flushing (1302.6.1)
  • │
  • ▼
  • Pump ──► PRV if >80 psi ──► PURPLE distribution (608.9)
  • Nonpotable Rainwater Collection (IPC 1303)

Collection surfaces (1303.2): Rainwater is collected only from above-ground impervious roofing of approved materials and, where approved, from vehicular parking or pedestrian walking surfaces.

Debris excluders (1303.3): Downspouts and leaders connect to a debris excluder that removes leaves, sticks and needles before the tank.

First-flush diverters (1303.4): These operate automatically , not with manual valves. Diverted water does not drain onto the roof, and the diverter has access for service.

Gutter slope (1303.5.1): Gutters and downspouts slope at least 1/8 inch per foot with no pooling. Siphonic systems installed per the manufacturer are exempt.

Gutter size (1303.5.2): Gutters are sized per Section 1106.6 and local rainfall rates.

Roof washer drainage (1303.6): Water from roof washers and debris excluders may not go to the sanitary sewer . These devices self-drain between rain events and do not drain onto the roof.

Tank setbacks (Table 1303.10.1): 2 feet from the critical root zone of protected trees, and 5 feet from lot lines, seepage pits and septic tanks.

Backwater valves (1303.11.1): Required on each overflow and tank drain pipe.

Fire protection use (1303.1.1): Storage and distribution for fire protection systems follow the International Fire Code .

Gutter test (1303.15.1): At least 1 gallon of water is poured into the gutter end opposite the outlet. The gutter must not leak or hold standing water.

Raw water quality (1303.15.9): ASTM E2727 is used to judge whether site conditions require treatment.

Reclaimed Water Systems (IPC 1304)

Reclaimed water is treated wastewater delivered by a wastewater treatment facility .

Pressure (1304.2): A PRV is required where supply pressure exceeds 80 psi static .

Design (1304.3): The system follows accepted engineering practice. Distribution piping meets Section 605 for nonpotable water and is identified as purple per 608.9. The exception is outdoor irrigation piping downstream of the backflow preventer.

Subsurface Graywater Soil Absorption Systems (IPC Chapter 14)

These systems send graywater from an on-site reuse system into the soil for subsurface irrigation. No disinfection (1401.5) or dye (1401.6) is required.

Graywater flow (Equation 14-1): C = A × B C = A \times B C = A × B , where:

A A A is the number of occupants. For homes, use 2 for the first bedroom plus 1 for each additional bedroom.

B B B is the residential flow: 25 gpd per occupant for showers, bathtubs and lavatories, plus 15 gpd per occupant for clothes washers or laundry trays.

C C C is the estimated graywater discharge in gallons per day.

Design loading rates (Table 1403.1.1):

  • Percolation Rate (min/inch) Design Loading Factor (gal/sq ft/day)
  • 0 to less than 10 1.2
  • 10 to less than 30 0.8
  • 30 to less than 45 0.72
  • 45 to 60 0.4

Worked example: A three-bedroom house connects the showers, lavatories and clothes washer.

  • A = 2 + 1 + 1 = 4 A = 2 + 1 + 1 = 4 A = 2 + 1 + 1 = 4 occupants
  • B = 25 + 15 = 40 B = 25 + 15 = 40 B = 25 + 15 = 40 gpd per occupant
  • C = 4 × 40 = 160 C = 4 \times 40 = 160 C = 4 × 40 = 160 gpd

Percolation at 20 min/inch gives a factor of 0.8, so the area is 160 / 0.8 = 200 sq ft 160 / 0.8 = 200\text{ sq ft} 160/0.8 = 200 sq ft .

With 2-foot-wide trenches, that is 100 feet of trench, which is at the 100-foot limit for a single trench.

Installation rules:

Percolation tests (1402.2.1): At least three in each system area.

Absorption field setbacks (Table 1402.3): 2 feet from buildings and 100 feet from water wells.

Seepage trenches (1403.1.2): 1 to 5 feet wide, spaced at least 2 feet apart, and no more than 100 feet in developed length each.

Aggregate (1403.1.5): At least 6 inches of ½- to 2½-inch aggregate below the pipe and 2 inches over it, a cover, and 9 inches of soil backfill. Building paper may not be used.

Distribution pipe (1403.2): At least 3 inches , with its top at least 8 inches below the original surface, sloped 2 to 4 inches per 100 feet . Materials are PE (ASTM F405) or PVC (ASTM D2729 or F1488).

Plan Reviewer Verification Checklist: Source-Specific Systems

Graywater Sources: Only allowed sources connect, and no kitchen, dishwasher, softener or RO reject water (1302.2).

Bypass and Backwater Valves: An NSF 50 three-way diverter is installed downstream of traps and vents, and backwater valves are on the overflow and drain (1302.8).

Treatment: Untreated storage is limited to 24 hours, with NSF 350 treatment for flushing (1302.6).

Rainwater Devices: Debris excluder, automatic first-flush diverter, 1/8-inch-per-foot gutters, and no roof washer drainage to the sewer (1303).

Pressure: A PRV is shown where pumped or reclaimed pressure exceeds 80 psi (1302.10, 1303.13 and 1304.2).

Soil Absorption: Area equals C divided by the Table 1403.1.1 factor; trenches are 100 feet or shorter; distribution pipe is at least 3 inches (Chapter 14).