5.4 Crawl Spaces, Masonry Veneer, Sunrooms & Heated Garages (R402.2.10–R402.2.12)
ICC Residential Energy Inspector/Plans Examiner Exam 79
Track your progress as you read
Finished sections get a check mark.
1 Exam Overview, Scope & Construction Documents
1.1 Current Exam 79 Facts, References & Open-Book Rules 1.2 Residential Scope, Mixed Occupancy & When the IECC Applies (R101, R102) 1.3 Construction Documents & Plan-Review Adequacy (R103)
2 Climate Zones, Materials Identification & Inspections
2.1 Climate Zones, Moisture Regimes & County Lookup (R301) 2.2 Design Conditions, Insulation Marks & Fenestration Labels (R302, R303) 2.3 Inspection Sequence & the Permanent Energy Certificate (R105, R401.3)
3 Compliance Paths, UA Tradeoff & Additional Efficiency
3.1 R401.2 Application: Prescriptive, Performance, ERI & Tropical Options 3.2 Additional Energy Efficiency Packages (R401.2.5, R408) 3.3 Total UA Alternative & Fenestration Tradeoff Caps (R402.1.5, R402.5)
4 Building Thermal Envelope Criteria
4.1 Building Thermal Envelope, Conditioned Space & Low-Energy Exceptions (R402.1) 4.2 Insulation Minimum R-Values — Table R402.1.3 4.3 Maximum Assembly U-Factors — Table R402.1.2 & R-Value Computation (R402.1.2, R402.1.4)
5 Specific Insulation Assemblies
5.1 Ceilings With and Without Attics, Eave Baffles & Access Hatches (R402.2.1–R402.2.4) 5.2 Wood-Frame, Mass & Steel-Frame Walls (R402.2.5–R402.2.6) 5.3 Floors, Basement Walls & Slab-on-Grade Insulation (R402.2.7–R402.2.9) 5.4 Crawl Spaces, Masonry Veneer, Sunrooms & Heated Garages (R402.2.10–R402.2.12)
6 Fenestration, Glazing & Doors
6.1 Fenestration U-Factor, SHGC & NFRC Labels (R402.3, R303.1.3) 6.2 Area-Weighted Averages, Dynamic Glazing & Exemptions (R402.3.1–R402.3.4) 6.3 Fenestration Air Leakage, Opaque Doors & Replacement Units (R402.4.3, R503.1.1.1)
7 Air Leakage Testing, Air Barrier & Moisture
7.1 Table R402.4.1.1: Ceilings, Walls, Rim Joists & Floors 7.2 Table R402.4.1.1: Openings, Penetrations, Tubs, Garages & Boxes 7.3 Blower-Door Testing, ACH50 Limits & Dwelling-Unit Alternatives (R402.4.1.2–R402.4.1.3) 7.4 Fireplaces, Recessed Luminaires, Air-Sealed Boxes, Combustion Rooms & Vapor Retarders (R402.4.2–R402.4.6, R402.1.1)
8 HVAC Controls, Sizing & Ventilation
8.1 Thermostats, Heat-Pump Supplementary Heat & Boiler Reset (R403.1, R403.2) 8.2 Equipment Sizing, Efficiency Ratings & Multi-Family Systems (R403.7, R403.8) 8.3 Mechanical Ventilation, HRV/ERV, Fan Efficacy & Airflow Testing (R403.6)
9 Duct Insulation, Sealing & Leakage Testing
9.1 Duct Insulation, Location & Buried Ducts (R403.3.1–R403.3.3) 9.2 Duct Sealing, Air Handlers & Framing-Cavity Ban (R403.3.4, R403.3.7) 9.3 Duct Testing Protocols & Leakage Limits (R403.3.5–R403.3.6)
10 Service Water Heating, Piping & Lighting
10.1 Service Water Heating Equipment, Circulation & Heat Trace (R403.5, R403.5.1) 10.2 Hot-Water Pipe Insulation, Mechanical Piping & Drain-Water Heat Recovery (R403.4, R403.5.2–R403.5.3) 10.3 High-Efficacy Lighting & Lighting Controls (R404)
11 Simulated Performance, ERI & Tropical Option
11.1 Simulated Performance Alternative (R405) 11.2 Energy Rating Index Alternative (R406) 11.3 Tropical Climate Region Option (R407)
12 Additions, Alterations, Repairs & Change of Occupancy
12.1 Additions & Change in Space Conditioning (R501, R502) 12.2 Alterations, Replacement Fenestration & Repairs (R503, R504) 12.3 Change of Occupancy, Historic Buildings & Maintenance (R505, R501.3, R501.6)
5.4 Crawl Spaces, Masonry Veneer, Sunrooms & Heated Garages (R402.2.10–R402.2.12)
Key Takeaways Explain This Topic AI
Crawl space walls are insulated to Table R402.1.3 unless the crawl is vented to the outdoors and the floor overhead is insulated to the table and Section R402.2.7.
Crawl wall insulation must be permanently fastened, extend from the floor to finished grade, then continue vertically or horizontally at least 24 inches.
Unvented crawl spaces require a continuous Class I vapor retarder over exposed earth, with joints overlapped 6 inches and sealed or taped, and edges turned up at least 6 inches on the stem walls and attached.
Insulation is not required on the horizontal portion of a foundation that supports a masonry veneer.
Thermally isolated sunrooms and heated garages that enclose conditioned space may use ceiling R-19 in Climate Zones 0–4 or R-24 in Climate Zones 5–8 and wall R-13 in all climate zones; walls separating that space from the rest of the dwelling still meet the full envelope requirements.
Last updated: September 2026
Crawl Spaces, Masonry Veneer, Sunrooms, and Heated Garages
Quick Answer: Insulate crawl space walls to Table R402.1.3 unless the crawl is vented to the outdoors and the floor overhead meets the table and R402.2.7. Fasten crawl-wall insulation permanently, run it from the floor to finished grade, then continue vertically or horizontally at least 24 inches. Unvented crawls also need a continuous Class I vapor retarder on exposed earth, overlapped 6 inches and turned 6 inches up the stem wall. Masonry veneer ledges skip insulation on that horizontal step. Thermally isolated sunrooms and heated garages that enclose conditioned space may use ceiling R-19 (Climate Zones 0–4) or R-24 (Climate Zones 5–8) and wall R-13; the wall between that space and the house still takes the full envelope.
R402.2.10 through R402.2.12 close the envelope chapter’s specialty assemblies. Exam 79 items often pair a vented versus unvented crawl with a sunroom that is “just a three-season room” until the drawings show a heat run. The definitions of sunroom and thermal isolation in Chapter 2 [RE] decide which R-value table actually applies.
Crawl space walls (R402.2.10)
Crawl space walls shall be insulated in accordance with Table R402.1.3 .
- Climate zone Crawl space wall R-value
- 0–2 0
- 3 5ci or 13
- 4 except Marine 10ci or 13
- 5 through 8 15ci or 19 or 13+5ci
Exception: Crawl space walls associated with a crawl space that is vented to the outdoors and whose floor overhead is insulated in accordance with Table R402.1.3 and Section R402.2.7 do not take the crawl-wall R-value. Both halves of the exception are required. A vented crawl with no floor insulation, or with floor batts sagging away from the subfloor in violation of R402.2.7, still needs crawl-wall insulation (or a repaired floor). An unvented, conditioned, or “encapsulated” crawl is not this exception; those walls stay on the table.
Choosing the exception moves the thermal envelope to the floor. Choosing wall insulation moves the envelope to the stem wall and usually implies an unvented crawl with ground cover. Mixing the two—vents open, walls insulated, floor empty, or vents closed, floor insulated, walls empty—leaves a hole in the envelope.
Installation (R402.2.10.1)
Where crawl space wall insulation is installed, it shall be permanently fastened to the wall and shall extend downward from the floor to the finished grade elevation and then vertically or horizontally for not less than an additional 24 inches (610 mm) .
A 30-inch crawl with grade 24 inches below the floor needs insulation down those 24 inches plus another 24 inches turned out on the interior grade or continued down the wall if the wall goes deeper. Loose batts leaned against the concrete without fasteners fail “permanently fastened.” Foam boards with only a few dabs of adhesive that will release in a damp crawl also fail the fastening test at inspection.
Unvented crawl ground cover
Exposed earth in unvented crawl space foundations shall be covered with a continuous Class I vapor retarder in accordance with the IBC or IRC as applicable. Joints shall overlap by 6 inches (153 mm) and be sealed or taped . Edges shall extend not less than 6 inches (153 mm) up the stem walls and shall be attached to the stem walls.
Class I means a permeance of 0.1 perm or less in the referenced IRC/IBC vapor-retarder classification (polyethylene sheeting is the usual product). A Class II kraft facing on a batt is not the ground cover. Unsealed laps, a sheet that stops at the mud sill, or a vapor retarder that is not attached to the stem wall fail R402.2.10.1 even if the R-value on the wall is correct.
Masonry veneer (R402.2.11)
Insulation shall not be required on the horizontal portion of a foundation that supports a masonry veneer . The brick or stone ledge is a shelf. The code does not demand a wedge of foam on that shelf. Vertical foundation walls still follow basement, crawl, or slab-edge rules as applicable. Inspectors should not fail a job because the brick ledge itself is bare, and they should not skip the vertical edge insulation just because veneer is present.
Sunrooms and heated garages (R402.2.12)
Sunrooms enclosing conditioned space and heated garages shall meet the insulation requirements of this code.
Chapter 2 [RE] defines a sunroom as a one-story structure attached to a dwelling with a glazing area in excess of 40% of the gross area of the structure’s exterior walls and roof. A heated garage is a garage provided with space heating. Conditioned space is space enclosed within the building thermal envelope and directly or indirectly heated or cooled—including space that shares openings with conditioned rooms, is separated only by uninsulated assemblies, or contains uninsulated ducts, piping, or other heating or cooling sources.
If a sunroom or heated garage encloses conditioned space and is not thermally isolated, its ceiling, walls, and (where applicable) floors use the same Table R402.1.3 values as the dwelling. A “sunroom” with a duct, a baseboard, or an uninsulated opening to the family room is inside the envelope.
Thermal isolation exception
Thermal isolation (Chapter 2 [RE]) is physical and space-conditioning separation from conditioned spaces. The conditioned spaces shall be controlled as separate zones for heating and cooling or conditioned by separate equipment .
For sunrooms and heated garages provided thermal isolation and enclosed conditioned space , the following exceptions to the insulation requirements apply:
Minimum ceiling insulation R-values: R-19 in Climate Zones 0 through 4 , and R-24 in Climate Zones 5 through 8 .
Minimum wall insulation R-value: R-13 in all climate zones.
Walls separating a sunroom or heated garage with thermal isolation from conditioned space shall comply with the building thermal envelope requirements of this code. The shared wall, shared ceiling, or shared floor is still a full Table R402.1.3 (or U-factor) assembly. The reduced R-19 / R-24 / R-13 numbers apply to the sunroom or garage envelope that faces the outdoors, not to the wall that protects the house.
Fenestration for these spaces is in R402.3.5 (taught with Chapter 6), not here: thermally isolated sunrooms and heated garages in Climate Zones 2 through 8 may use fenestration U-0.45 and skylight U-0.70, while new fenestration in the separating wall still meets the dwelling table. Do not import those U-factors into an R402.2.12 insulation answer.
Condition Ceiling R Exterior wall R Wall toward the dwelling
Sunroom or heated garage enclosing conditioned space, no thermal isolation Table R402.1.3 (R-30 / R-49 / R-60 by zone) Table R402.1.3 wood, mass, or steel Not a separate assembly; it is interior
Same space with thermal isolation R-19 in CZ 0–4; R-24 in CZ 5–8 R-13 in all climate zones Full envelope (for example CZ5 wood R-30 or R-20+5ci or R-13+10ci or R-0+20ci)
Heated attached or detached private garages also appear in the R402.4.1.2 testing exception: field verification of Table R402.4.1.1 may substitute for a blower-door number when those garages are thermally isolated per R402.2.12 and R402.3.5. That testing trade is Chapter 7 material; the insulation prerequisite is this section.
Field scenario: thermally isolated sunroom
A Climate Zone 6 two-story adds a 12-foot by 16-foot sunroom with glazing over 40% of its exterior walls and roof. The sunroom has its own ductless mini-split. A weatherstripped, labeled exterior-grade door and an insulated wood-frame wall separate the sunroom from the dining room. The dining-room thermostat does not control the mini-split.
That is thermal isolation plus enclosed conditioned space. The sunroom’s exterior ceiling may be R-24 and its exterior walls R-13 under R402.2.12. The separating wall toward the dining room must still meet Climate Zone 6 wood-frame options ( R-30 or R-20+5ci or R-13+10ci or R-0+20ci ), not R-13. If the contractor leaves a 4-foot cased opening with no door, thermal isolation fails: the sunroom is then simply more conditioned space, and the sunroom ceiling jumps to Table R402.1.3 R-60 (or the R402.2.1 attic trade if it has a qualifying attic).
A heated garage with a unit heater, a tight fire-rated door to the mudroom, and no shared uninsulated ducts can use the same reduced garage-envelope R-values, while the house-to-garage wall stays a full envelope assembly and still needs the air-sealing required of garage separation.
Masonry-veneer-plus-crawl combinations
A Climate Zone 4 house on a vented crawl with brick veneer often shows three details on one foundation sheet:
Floor overhead insulated to R-19 in permanent contact with the subfloor (vented-crawl exception + R402.2.7).
No crawl-wall insulation, because the exception applies.
A bare brick ledge under R402.2.11, which does not excuse skipping slab-edge or stem insulation on a different part of the same building if that part is a slab-on-grade wing.
Read the assembly in front of you. Veneer, crawl, and slab rules do not override each other; they occupy different surfaces.
Plan-review checklist
Crawl: vented or unvented; floor R-value and R402.2.7 method versus wall R-value, fastening, and 24-inch turn; Class I ground sheet with 6-inch laps and 6-inch stem attachment if unvented.
Veneer: horizontal ledge may be uninsulated; vertical walls still follow their section.
Sunroom / heated garage: confirm Chapter 2 sunroom glazing percentage if claimed; confirm thermal isolation (physical separation plus separate zone or equipment); apply R-19/R-24 and R-13 only to that enclosure; keep the shared wall on the full table.
Independent ExamFinch study material for ICC Exam 79 covers 2021 IECC residential Sections R402.2.10 through R402.2.12. It is not an ICC or IECC publication; match the first-printing text in the bound book you bring to the open-book exam.