4.4 Feeder & Transformer Tap Rules (NEC 240.21)

Idaho Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Orientation, NEC Navigation & Idaho Regulations

1.1 Idaho Journeyman Exam Format, PSI Logistics & Rapid NEC Navigation 1.2 Idaho Electrical Licensing Laws (Title 54, Ch. 10) & IDAPA 24.39.10 Requirements 1.3 Idaho Permits, Inspection Procedures & State-Specific NEC Amendments 1.4 NEC Article 90 Scope, Code Arrangement & Article 110 General Requirements

2 Chapter 2: Electrical Theory & Essential Math Calculations

2.1 Ohm's Law, Joule's Law & DC Circuit Calculations 2.2 Single-Phase & Three-Phase AC Fundamentals and Power Factor 2.3 DC & AC Voltage Drop Calculations and Conductor Sizing 2.4 NEC Article 100 Essential Definitions for Journeymen

3 Chapter 3: Conductors, Raceways & Box Sizing Calculations

3.1 Conductor Ampacity, Insulation Types & Terminal Temperature Ratings 3.2 Ambient Temperature Correction & Raceway Conductor Bundling Derating 3.3 Outlet & Junction Box Volume Fill Calculations (NEC 314.16) 3.4 Conduit Fill Calculations & Large Pull Box Sizing (NEC 314.28)

4 Chapter 4: Branch Circuits & Overcurrent Protection

4.1 Branch Circuit Ratings, Multiwire Circuits & Receptacle Placement 4.2 GFCI & AFCI Protection Mandates and Idaho Code Clarifications 4.3 Overcurrent Protective Devices, Standard Ratings & Small Conductor Rules 4.4 Feeder & Transformer Tap Rules (NEC 240.21)

5 Chapter 5: Feeders, Services & Outside Branch Circuits

5.1 Feeder Conductor Sizing, Neutral Calculations & Voltage Drop 5.2 Outside Branch Circuits, Feeders & Overhead/Underground Clearances 5.3 Service Drop, Service Lateral & Service-Entrance Sizing 5.4 Service Disconnecting Means, Emergency Disconnects & Surge Protection

6 Chapter 6: Load Calculations: Dwellings & Commercial

6.1 General Lighting, Small Appliance & Laundry Load Calculations 6.2 Standard Method Single-Family Dwelling Service Calculations (NEC 220 Part III) 6.3 Optional Method Single-Family & Multifamily Calculations (NEC 220 Part IV) 6.4 Commercial & Industrial Feeder/Service Calculations

7 Chapter 7: Grounding and Bonding: Systems & Electrodes

7.1 Grounding vs. Bonding Fundamentals & System Grounding 7.2 Grounding Electrodes & Grounding Electrode Conductor (GEC) Sizing 7.3 Main Bonding Jumpers, System Bonding Jumpers & Supply-Side Bonding

8 Chapter 8: Grounding and Bonding: Equipment & Enclosures

8.1 Equipment Grounding Conductors (EGC) Types, Installation & Sizing (Table 250.122) 8.2 Separately Derived Systems (SDS) Transformers & Generator Grounding 8.3 Service Enclosure Bonding, Concentric Knockouts & Effective Ground-Fault Path

9 Chapter 9: Wiring Methods, Cables & Conduits

9.1 General Requirements for Wiring Methods & Underground Installations (Article 300) 9.2 Nonmetallic-Sheathed (NM), Metal-Clad (MC) & Armored (AC) Cables 9.3 Metallic & Nonmetallic Raceway Systems (EMT, PVC, RMC, FMC) 9.4 Cabinets, Cutout Boxes & Outlet Box Installation Rules (Articles 312 & 314)

10 Chapter 10: Equipment for General Use: Devices, Luminaires & Appliances

10.1 Switches, Receptacles & Device Installation Standards (Articles 404 & 406) 10.2 Luminaire Clearances, Closet Rules & Lighting Track (Article 410) 10.3 Household Appliances & Fixed Electric Space Heating (Articles 422 & 424) 10.4 Generators, Transformer Overcurrent Protection & Panelboards

11 Chapter 11: Motors, Motor Circuits & Controllers

11.1 Motor Nameplate vs. Table FLC & Branch Circuit Conductor Sizing 11.2 Branch Circuit Short-Circuit & Ground-Fault Protection (Table 430.52) 11.3 Motor Overload Protection Sizing & Selection (NEC 430 Part III) 11.4 Motor Disconnects, Controllers & Multimotor Feeder Calculations

12 Chapter 12: Special Occupancies & Hazardous Locations

12.1 Hazardous (Classified) Locations: Classes, Divisions, Zones & Seals 12.2 Commercial Garages, Repair Hangars & Fuel Dispensing Facilities 12.3 Health Care Facilities: Patient Care Spaces & Redundant Grounding (Article 517) 12.4 Agricultural Buildings, Marinas, Boatyards & RV Parks

13 Chapter 13: Special Equipment, Emergency Systems & Renewable Energy

13.1 Swimming Pools, Spas, Hot Tubs & Equipotential Bonding (Article 680) 13.2 Electric Vehicle Supply Equipment (EVSE) Installation & Sizing (Article 625) 13.3 Solar Photovoltaic (PV) Systems & Energy Storage Systems (Articles 690 & 706) 13.4 Emergency, Standby Power Systems & Fire Pumps (Articles 700, 701, 702 & 695) 13.5 Fire Alarm, Optical Fiber & Power-Limited Circuits (Articles 760, 770 & 800)

4.4 Feeder & Transformer Tap Rules (NEC 240.21)

Key Takeaways Explain This Topic AI

NEC 240.21 establishes the foundational rule that overcurrent protection must be installed at the point where a conductor receives its supply, with tap rules serving as strictly controlled safety exceptions; tap conductors are never permitted to tap another tap.

A tap conductor is defined as a conductor, other than a service conductor, that has overcurrent protection ahead of its point of supply exceeding the conductor ampacity listed in Table 310.16.

The 10-Foot Feeder Tap Rule (NEC 240.21(B)(1)) requires: length not over 10 ft, ampacity not less than computed load and not less than rating of termination device / OCPD supplied, enclosed in raceway, and terminating within the equipment enclosure.

The 25-Foot Feeder Tap Rule (NEC 240.21(B)(2)) requires: length not over 25 ft, ampacity not less than 1/3 the rating of the upstream feeder OCPD, enclosed/protected from physical damage, and terminating in a single circuit breaker or set of fuses.

Outside feeder taps (NEC 240.21(B)(5)) permit unlimited outdoor length terminating in a single OCPD, while transformer secondary taps (NEC 240.21(C)) follow specific primary-to-secondary transformation ratio rules.

Last updated: August 2026

Feeder & Transformer Tap Rules (NEC 240.21)

Under the general rule of NEC 240.21 , overcurrent protection must be provided in each ungrounded conductor at the exact point where the conductor receives its electrical supply. However, running a full-size feeder directly to every small disconnect or subpanel is economically and physically impractical in commercial and industrial facilities.

To accommodate practical electrical distribution, the Code provides specific, strictly regulated Tap Rules under NEC 240.21(B) (Feeder Taps) and NEC 240.21(C) (Transformer Secondary Taps). Mastery of these tap rules and their underlying safety mechanics is a cornerstone of the Idaho Journeyman Electrician examination.

1. Tap Conductor Definition & General Prohibitions +-----------------------------------------------------------------------------+

  • | WHAT IS A TAP CONDUCTOR? (NEC 240.2) |
  • | |
  • | "A conductor, other than a service conductor, that has overcurrent |
  • | protection ahead of its point of supply exceeding the value permitted |
  • | for similar conductors in Section 240.4." |
  • | |
  • | [FUNDAMENTAL TAP RULES] |
  • | 1. A tap conductor CANNOT supply another tap (NO TAPS FROM TAPS!). |
  • | 2. Tap conductors must be enclosed in raceway or approved cable from the |
  • | tap point to the termination enclosure. |
  • | 3. Tap conductors must terminate in a single OCPD or group of OCPDs as |
  • | specifically permitted by the individual tap section. |
  • | 4. The 'Next Higher Standard Device' rule (240.4(B)) CANNOT be applied to |
  • | tap conductor terminations! |
  • +-----------------------------------------------------------------------------+

Why Do Tap Rules Exist?

When a small conductor is tapped off a large feeder (e.g., a 10 AWG wire tapped off a 400A feeder), the 400A upstream breaker cannot protect the 10 AWG wire from sustained thermal overloads. The tap rules ensure safety by:

Limiting Length: Minimizing the physical exposure distance of the undersized conductor.

Mandating Mechanical Protection: Requiring raceways or metal enclosures to prevent physical damage and short circuits.

Mandating Downstream OCPD: Ensuring that a downstream overcurrent device limits maximum current to the conductor's rated ampacity before an overload can occur.

2. Feeder Tap Rules (NEC 240.21(B)) +-----------------------------------------------------------------------------+

  • | THE 10-FT VS. 25-FT FEEDER TAP RULES |
  • | |
  • | [10-FOOT FEEDER TAP (NEC 240.21(B)(1))] |
  • | * Max Length: 10 Feet (3.0 m) |
  • | * Minimum Ampacity: Not less than the computed load on the circuit AND |
  • | not less than the rating of the device/panelboard supplied. |
  • | * Enclosure: Enclosed in raceway, cable tray, or metal cabinet. |
  • | * Extent: Cannot extend beyond switchboard, panelboard, or control devices|
  • | |
  • | [25-FOOT FEEDER TAP (NEC 240.21(B)(2)) - THE 1/3 RULE] |
  • | * Max Length: 25 Feet (7.5 m) |
  • | * Minimum Ampacity: At least 1/3 (33.3%) of the upstream feeder OCPD! |
  • | * Protection: Enclosed in raceway or protected from physical damage. |
  • | * Termination: Must terminate in a SINGLE circuit breaker or set of fuses!|
  • +-----------------------------------------------------------------------------+
  • A. 10-Foot Feeder Tap Rule (NEC 240.21(B)(1))

Conductors are permitted to be tapped from a feeder without overcurrent protection at the tap point where ALL of the following conditions are satisfied:

The length of the tap conductors does not exceed 10 feet (3.0 m) .

The ampacity of the tap conductors is:

Not less than the combined computed loads on the circuits supplied by the tap conductors, AND

Not less than the rating of the equipment containing an overcurrent device supplied by the tap conductors, or not less than the rating of the overcurrent protective device at the termination.

The tap conductors do not extend beyond the switchboard, switchgear, panelboard, disconnecting means, or control devices they supply.

Except at the point of connection to the feeder, the tap conductors are enclosed in a raceway, which extends from the tap to the enclosure of an enclosed switchboard, switchgear, a panelboard, or control devices, or to the back of an open switchboard.

For field installations where the tap conductors leave the enclosure or vault in which the tap is made, the rating of the overcurrent device on the line side of the tap conductors cannot exceed 10 times the tap conductor's ampacity .

B. 25-Foot Feeder Tap Rule (NEC 240.21(B)(2))

Conductors are permitted to be tapped from a feeder without overcurrent protection at the point of supply where ALL of the following conditions are met:

The length of the tap conductors does not exceed 25 feet (7.5 m) .

The ampacity of the tap conductors is not less than 1/3 of the rating of the overcurrent device protecting the feeder conductors .

The tap conductors are suitably protected from physical damage by being enclosed in an approved raceway or by other approved means.

The tap conductors terminate in a single circuit breaker or a single set of fuses that limits the load to the ampacity of the tap conductors.

C. Outside Feeder Taps of Unlimited Length (NEC 240.21(B)(5))

Feeder conductors installed outside of a building or structure are permitted to be tapped without overcurrent protection at the tap point if:

The conductors are suitably protected from physical damage.

The conductors terminate at a single circuit breaker or a single set of fuses that limits the load to the ampacity of the conductors.

The overcurrent device for the conductors is an integral part of a disconnecting means or located immediately adjacent thereto.

The disconnecting means is installed at a readily accessible location either outside of a building or structure, or inside nearest the point of entrance of the conductors.

3. Transformer Secondary Tap Rules (NEC 240.21(C))

Under NEC 240.21(C) , secondary conductors connected to a transformer are considered tap conductors because primary overcurrent devices generally cannot protect secondary conductors against overcurrent due to phase transformation and winding ratios (especially in 3-phase delta-wye transformations). +-----------------------------------------------------------------------------+

  • | TRANSFORMER SECONDARY TAPS (NEC 240.21(C)) |
  • | |
  • | [WHY PRIMARY OCPD CANNOT PROTECT SECONDARY CONDUCTORS] |
  • | * In a 480V Delta to 208Y/120V Wye Transformer, a 100A primary OCPD |
  • | corresponds to 231A on the secondary (Ratio = 480 / 208 = 2.31). |
  • | * A single-phase line-to-neutral secondary fault draws only ~58% of |
  • | balanced 3-phase current on the primary, leaving the primary breaker |
  • | unable to trip before secondary wires burn up! |
  • | |
  • | [10-FOOT SECONDARY TAP (NEC 240.21(C)(2))] |
  • | * Length: Max 10 Feet. |
  • | * Ampacity: Primary-to-secondary ratio equivalent + terminates in single |
  • | OCPD or panelboard with main OCPD matching tap ampacity. |
  • | |
  • | [25-FOOT INDUSTRIAL SECONDARY TAP (NEC 240.21(C)(3))] |
  • | * Length: Max 25 Feet in industrial installations with qualified personnel.|
  • | * Secondary conductor ampacity must be at least 1/3 of secondary FLC. |
  • +-----------------------------------------------------------------------------+
  • Transformer Secondary Tap Code Requirements Summary

Secondary Tap Type Max Length Minimum Conductor Ampacity Rule Termination Requirement Code Citation

10-Foot Secondary Tap 10 Feet (3.0 m) Ampacity not less than computed load AND not less than rating of device supplied / OCPD rating. Single OCPD or panelboard main breaker; enclosed in raceway. NEC 240.21(C)(2)

25-Foot Secondary Tap (Industrial) 25 Feet (7.5 m) Secondary ampacity >= rated full-load current of transformer secondary divided by 3 (1/3 FLC). Single OCPD; qualified maintenance supervision only. NEC 240.21(C)(3)

Outside Secondary Tap Unlimited (Outside) Sized to carry computed load; protected from physical damage. Single OCPD at building point of entrance. NEC 240.21(C)(4)

25-Foot Secondary Tap (Non-Industrial) 25 Feet (7.5 m) Primary OCPD rating x Primary/Secondary Voltage Ratio <= 3 x Secondary Ampacity. Single OCPD limiting load to conductor ampacity. NEC 240.21(C)(6)

4. Master Comparison: 10-Foot vs. 25-Foot Feeder Tap Sizing Rules

  • Design Feature 10-Foot Feeder Tap (240.21(B)(1)) 25-Foot Feeder Tap (240.21(B)(2))
  • Maximum Physical Length 10 Feet (3.0 meters) 25 Feet (7.5 meters)

Minimum Conductor Ampacity Not less than computed load AND not less than rating of termination device / OCPD. Not less than 1/3 (33.3%) of upstream feeder OCPD rating.

Upstream OCPD Ratio Cap Feeder OCPD <= 10 x tap conductor ampacity (if leaving vault/enclosure). Upstream OCPD <= 3 x tap conductor ampacity (1/3 rule).

Raceway / Enclosure Must be enclosed in raceway for entire length outside enclosures. Must be protected from physical damage (raceway or approved cable).

Termination Requirement Switchboard, panelboard, or control device with OCPD matching tap size. Single circuit breaker or single set of fuses limiting load to tap ampacity.

Round-Up Rule (240.4(B)) PROHIBITED (OCPD cannot exceed tap ampacity). PROHIBITED (OCPD cannot exceed tap ampacity).

Tapping Another Tap STRICTLY PROHIBITED STRICTLY PROHIBITED

  • 5. Worked Step-by-Step Examination Tap Sizing Calculations
  • Example 1: 10-Foot Feeder Tap Sizing

Question: A 400-ampere, 480V, 3-phase feeder supplies a large industrial distribution trough. An electrician wishes to install an 8-foot raceway tap to supply a 100-ampere, 3-phase enclosed circuit breaker disconnect serving a pump controller. The computed continuous load on the pump is 68A (68A x 1.25 = 85A). What is the minimum size copper THHN conductor (75°C terminals) required for this 10-foot tap? +-----------------------------------------------------------------------------+

  • | 10-FOOT TAP SCHEMATIC DIAGRAM |
  • | |
  • | [400A Main Feeder Breaker] |
  • | | |
  • | v (400A Feeder Conductor) |
  • | +------------------------------------+ |
  • | | Feeder Wireway / Trough | |
  • | +------------------------------------+ |
  • | | |
  • | | <--- 8-foot Tap Conductor in EMT |
  • | v |
  • | [100A Enclosed Disconnect Breaker] |
  • +-----------------------------------------------------------------------------+

Step-by-Step Solution:

Verify Tap Length (NEC 240.21(B)(1)): Length is 8 feet (<= 10 feet). Condition met.

Determine Minimum Required Ampacity:

Must not be less than computed load: 85 Amperes.

Must not be less than the rating of the termination device / OCPD: The disconnect contains a 100A circuit breaker .

Therefore, minimum tap ampacity is 100 Amperes .

Check 10-to-1 Upstream Ratio Rule:

Feeder OCPD (400A) <= 10 x 100A = 1000A. Condition met.

Select Conductor from Table 310.16 (75°C Column):

  • 4 AWG Cu = 85 A (Insufficient for 100A termination)
  • 3 AWG Cu = 100 A (Complies exactly with 100A requirement)

Conclusion: Minimum size conductor is 3 AWG Copper THHN .

Example 2: 25-Foot Feeder Tap Sizing (The 1/3 Rule)

Question: A 600-ampere, 208Y/120V feeder protected by a 600A circuit breaker passes through a commercial building. An electrician intends to tap this feeder with a 22-foot run of copper THHN conductors in EMT to supply a new lighting subpanel containing a single 200A main circuit breaker. What is the minimum size copper conductor required for the tap?

Step-by-Step Solution:

Verify Tap Length (NEC 240.21(B)(2)): Length is 22 feet (<= 25 feet). Condition met.

Apply the 1/3 Feeder OCPD Rule (NEC 240.21(B)(2)(1)):

Minimum Tap Ampacity = Feeder OCPD Rating / 3 = 600 A / 3 = 200.0 Amperes

Check Termination OCPD:

Tap terminates in a single 200A main circuit breaker.

Conductor ampacity must be at least 200A.

Select Conductor from Table 310.16 (75°C Column):

  • 2/0 AWG Cu = 175 A (Insufficient)
  • 3/0 AWG Cu = 200 A (Exactly meets the 200A requirement)

Conclusion: Minimum conductor size is 3/0 AWG Copper THHN .

Example 3: Exam Trap - Violating the 1/3 Rule on 25-Foot Taps

Question: A contractor installs an 18-foot tap consisting of 1 AWG THHN copper conductors (130A ampacity at 75°C) from a 450A feeder breaker, terminating in a 125A fused safety switch. Does this installation comply with NEC 240.21(B)(2)?

Step-by-Step Solution:

Check Tap Length: 18 feet (<= 25 ft). Valid.

Calculate 1/3 of Upstream Feeder OCPD:

Minimum Required Ampacity = 450 A / 3 = 150 Amperes

Compare with Conductor Ampacity:

1 AWG Copper has an allowable ampacity of only 130 Amperes at 75°C.

130 A < 150 A (VIOLATION of the 1/3 rule).

Conclusion: NON-COMPLIANT. Even though the tap terminates in a 125A switch, the conductor itself must have an ampacity of at least 150A (requiring minimum 1/0 AWG Cu at 150A) to satisfy the 1/3 rule.