2.4 NEC Article 100 Essential Definitions for Journeymen

Idaho Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Orientation, NEC Navigation & Idaho Regulations

1.1 Idaho Journeyman Exam Format, PSI Logistics & Rapid NEC Navigation 1.2 Idaho Electrical Licensing Laws (Title 54, Ch. 10) & IDAPA 24.39.10 Requirements 1.3 Idaho Permits, Inspection Procedures & State-Specific NEC Amendments 1.4 NEC Article 90 Scope, Code Arrangement & Article 110 General Requirements

2 Chapter 2: Electrical Theory & Essential Math Calculations

2.1 Ohm's Law, Joule's Law & DC Circuit Calculations 2.2 Single-Phase & Three-Phase AC Fundamentals and Power Factor 2.3 DC & AC Voltage Drop Calculations and Conductor Sizing 2.4 NEC Article 100 Essential Definitions for Journeymen

3 Chapter 3: Conductors, Raceways & Box Sizing Calculations

3.1 Conductor Ampacity, Insulation Types & Terminal Temperature Ratings 3.2 Ambient Temperature Correction & Raceway Conductor Bundling Derating 3.3 Outlet & Junction Box Volume Fill Calculations (NEC 314.16) 3.4 Conduit Fill Calculations & Large Pull Box Sizing (NEC 314.28)

4 Chapter 4: Branch Circuits & Overcurrent Protection

4.1 Branch Circuit Ratings, Multiwire Circuits & Receptacle Placement 4.2 GFCI & AFCI Protection Mandates and Idaho Code Clarifications 4.3 Overcurrent Protective Devices, Standard Ratings & Small Conductor Rules 4.4 Feeder & Transformer Tap Rules (NEC 240.21)

5 Chapter 5: Feeders, Services & Outside Branch Circuits

5.1 Feeder Conductor Sizing, Neutral Calculations & Voltage Drop 5.2 Outside Branch Circuits, Feeders & Overhead/Underground Clearances 5.3 Service Drop, Service Lateral & Service-Entrance Sizing 5.4 Service Disconnecting Means, Emergency Disconnects & Surge Protection

6 Chapter 6: Load Calculations: Dwellings & Commercial

6.1 General Lighting, Small Appliance & Laundry Load Calculations 6.2 Standard Method Single-Family Dwelling Service Calculations (NEC 220 Part III) 6.3 Optional Method Single-Family & Multifamily Calculations (NEC 220 Part IV) 6.4 Commercial & Industrial Feeder/Service Calculations

7 Chapter 7: Grounding and Bonding: Systems & Electrodes

7.1 Grounding vs. Bonding Fundamentals & System Grounding 7.2 Grounding Electrodes & Grounding Electrode Conductor (GEC) Sizing 7.3 Main Bonding Jumpers, System Bonding Jumpers & Supply-Side Bonding

8 Chapter 8: Grounding and Bonding: Equipment & Enclosures

8.1 Equipment Grounding Conductors (EGC) Types, Installation & Sizing (Table 250.122) 8.2 Separately Derived Systems (SDS) Transformers & Generator Grounding 8.3 Service Enclosure Bonding, Concentric Knockouts & Effective Ground-Fault Path

9 Chapter 9: Wiring Methods, Cables & Conduits

9.1 General Requirements for Wiring Methods & Underground Installations (Article 300) 9.2 Nonmetallic-Sheathed (NM), Metal-Clad (MC) & Armored (AC) Cables 9.3 Metallic & Nonmetallic Raceway Systems (EMT, PVC, RMC, FMC) 9.4 Cabinets, Cutout Boxes & Outlet Box Installation Rules (Articles 312 & 314)

10 Chapter 10: Equipment for General Use: Devices, Luminaires & Appliances

10.1 Switches, Receptacles & Device Installation Standards (Articles 404 & 406) 10.2 Luminaire Clearances, Closet Rules & Lighting Track (Article 410) 10.3 Household Appliances & Fixed Electric Space Heating (Articles 422 & 424) 10.4 Generators, Transformer Overcurrent Protection & Panelboards

11 Chapter 11: Motors, Motor Circuits & Controllers

11.1 Motor Nameplate vs. Table FLC & Branch Circuit Conductor Sizing 11.2 Branch Circuit Short-Circuit & Ground-Fault Protection (Table 430.52) 11.3 Motor Overload Protection Sizing & Selection (NEC 430 Part III) 11.4 Motor Disconnects, Controllers & Multimotor Feeder Calculations

12 Chapter 12: Special Occupancies & Hazardous Locations

12.1 Hazardous (Classified) Locations: Classes, Divisions, Zones & Seals 12.2 Commercial Garages, Repair Hangars & Fuel Dispensing Facilities 12.3 Health Care Facilities: Patient Care Spaces & Redundant Grounding (Article 517) 12.4 Agricultural Buildings, Marinas, Boatyards & RV Parks

13 Chapter 13: Special Equipment, Emergency Systems & Renewable Energy

13.1 Swimming Pools, Spas, Hot Tubs & Equipotential Bonding (Article 680) 13.2 Electric Vehicle Supply Equipment (EVSE) Installation & Sizing (Article 625) 13.3 Solar Photovoltaic (PV) Systems & Energy Storage Systems (Articles 690 & 706) 13.4 Emergency, Standby Power Systems & Fire Pumps (Articles 700, 701, 702 & 695) 13.5 Fire Alarm, Optical Fiber & Power-Limited Circuits (Articles 760, 770 & 800)

2.4 NEC Article 100 Essential Definitions for Journeymen

Key Takeaways Explain This Topic AI

Article 100 contains definitions essential to the proper application of the National Electrical Code. Terms defined apply throughout the entire code unless an article-specific definition modifies the scope.

Accessibility distinguishes three strict legal tiers: 'Accessible (as applied to wiring methods)' (removable without damaging building finishes), 'Accessible (as applied to equipment)' (not guarded by locked doors or elevation), and 'Readily Accessible' (reached quickly without climbing, obstacles, portable ladders, or tools).

A 'Continuous Load' is defined as maximum current expected to continue for 3 hours or more, mandating a 125% multiplier for conductor ampacity and overcurrent device ratings under NEC 210.19(A) and 215.2(A).

A 'Device' is a unit of an electrical system intended to carry or control electric energy (switches, receptacles, circuit breakers), whereas 'Utilization Equipment' actually transforms electrical energy into light, heat, or mechanical power (motors, luminaires, heaters).

'Bonded (Bonding)' establishes electrical conductivity and continuity between metal parts to create an effective ground-fault current path, whereas 'Grounded (Grounding)' establishes an intentional connection to the earth.

Last updated: August 2026

2.4 NEC Article 100 Essential Definitions for Journeymen

In the National Electrical Code (NEC), precision of language is paramount. On the Idaho Journeyman Electrician exam, numerous questions test exact definitions located in NEC Article 100 . Misinterpreting a single legal term—such as confusing accessible with readily accessible , or overload with overcurrent —leads directly to incorrect code navigation and calculation errors.

1. The Accessibility Triad

The Code strictly differentiates three levels of access to wiring methods and electrical equipment: +-----------------------------------------------------------------------------+

  • | THE ACCESSIBILITY TRIAD |
  • | |
  • | TERM DEFINITION / CRITERIA REAL-WORLD EXAMPLE |
  • | ----------------------------------------------------------------------- |
  • | Accessible Capable of being removed or Junction box located |
  • | (Wiring Methods) exposed without damaging the above a drop ceiling |
  • | building structure or finish. with lay-in tiles. |
  • | |
  • | Accessible Admitting close approach; not Panelboard behind an |
  • | (Equipment) guarded by locked doors, unlocked door or in a |
  • | elevation, or other barriers. mechanical room. |
  • | |
  • | Readily Accessible Capable of being reached Main service breaker, |
  • | (Fast Access) QUICKLY without: receptacle, or GFCI |
  • | 1. Climbing over obstacles reset switch within |
  • | 2. Resorting to ladders normal reach (≤6'7"). |
  • | 3. Using portable tools |
  • +-----------------------------------------------------------------------------+

Important

Exam Trap: Tools & Drop Ceilings: A junction box installed above a drywall ceiling with no access panel is NOT accessible . A junction box above a lay-in acoustic tile ceiling is accessible as applied to wiring methods , but it is NOT readily accessible because reaching it requires standing on a portable ladder or stool.

2. Grounding, Bonding & Conductor Classifications

Article 100 defines the precise roles of conductors in grounding and fault-clearing paths: +-----------------------------------------------------------------------------+

  • | GROUNDING & BONDING DEFINITIONS IN ACTION |
  • | |
  • | +---------------------------------------------------------------------+ |
  • | | SERVICE PANEL | |
  • | | [Neutral Bus] <==== MAIN BONDING JUMPER ====> [Ground Bus / Encl] | |
  • | | | | | |
  • | +---------|----------------------------------------------|------------+ |
  • | | (Grounded Neutral) | (EGC) |
  • | v v |
  • | [White Conductor: Normal Current] [Bare/Green: Fault Current] |
  • | | | |
  • | v v |
  • | [UTILIZATION LOAD] ==========================> [METAL MOTOR FRAME] |
  • | (Bonded Enclosure) |
  • +-----------------------------------------------------------------------------+

Key Definitions:

Bonded (Bonding): Connected to establish electrical continuity and conductivity between metal parts to ensure an effective ground-fault current path.

Grounded (Grounding): Connected (intentionally or accidentally) to the earth or to some conducting body that extends the connection to the earth.

Grounded Conductor: A system or circuit conductor that is intentionally grounded (typically the white or gray neutral conductor ). It carries normal return current.

Equipment Grounding Conductor (EGC): The conductive path(s) installed to connect normally non-current-carrying metal parts of equipment, raceways, and enclosures together and to the system grounded conductor or grounding electrode conductor. Does NOT carry current under normal operating conditions.

Grounding Electrode Conductor (GEC): A conductor used to connect the system grounded conductor or equipment to a grounding electrode (such as a ground rod, metal water pipe, or concrete-encased electrode/Ufer).

Main Bonding Jumper (MBJ): The connection between the grounded circuit conductor (neutral) and the equipment grounding conductor at the service disconnect.

Neutral Conductor: The conductor connected to the neutral point of a system that is intended to carry current under normal conditions.

3. Circuit Topography: Branch Circuits vs. Feeders vs. Services +-----------------------------------------------------------------------------+

  • | CIRCUIT TOPOGRAPHY SPECTRUM |
  • | |
  • | [UTILITY POLE / TRANSFORMER] |
  • | | |
  • | v (Service Drop / Lateral) |
  • | [SERVICE POINT] (Boundary of utility ownership & premises wiring) |
  • | | |
  • | v (Service-Entrance Conductors) |
  • | [MAIN SERVICE DISCONNECT / OCPD] |
  • | | |
  • | v (FEEDER: Between Service Disconnect and Subpanel OCPD) |
  • | [DISTRIBUTION SUBPANEL / OCPD] |
  • | | |
  • | v (BRANCH CIRCUIT: Between Final OCPD and Outlets) |
  • | [OUTLETS: Receptacles, Switches, Luminaires, Hardwired Loads] |
  • +-----------------------------------------------------------------------------+

Definitional Rules:

Service Point: The point of connection between the facilities of the serving utility and the premises wiring.

Service Conductors: The conductors from the service point to the service disconnecting means.

Feeder: All circuit conductors between the service equipment, the source of a separately derived system, or other power supply source and the final branch-circuit overcurrent device .

Branch Circuit: The circuit conductors between the final overcurrent device protecting the circuit and the outlet(s).

4. Hardware Terms: Devices vs. Equipment vs. Utilization Equipment

Term Official Article 100 Definition What It Includes What It DOES NOT Include

Device A unit of an electrical system, other than a conductor, that carries or controls electric energy as its principal function . Switches, receptacles, circuit breakers, fuses, relays, contactors. Motors, lights, heaters, appliances (these consume power).

Utilization Equipment Equipment that utilizes electric energy for electronic, electromechanical, chemical, heating, lighting , or similar purposes. Motors, luminaires, water heaters, ranges, transformers powering loads. Wall switches, standard receptacles, disconnect switches.

Equipment A general term including fittings, devices, appliances, luminaires, apparatus, machinery, and like parts used as a part of, or in connection with, an electrical installation. Comprehensive umbrella term covering all electrical hardware. Non-electrical framing or structural lumber.

5. Overcurrent, Overload & Fault Classifications +-----------------------------------------------------------------------------+

  • | OVERCURRENT CLASSIFICATION TAXONOMY |
  • | |
  • | OVERCURRENT |
  • | (Any current in excess of rated equipment ampacity) |
  • | | |
  • | +--------------------+--------------------+ |
  • | | | |
  • | v v |
  • | OVERLOAD FAULT CONDITIONS |
  • | • Excessive operating demand • Direct insulation failure |
  • | • Persists over time • Massive instantaneous current |
  • | • Examples: Motor mechanical jam, • Types: |
  • | too many heaters on one circuit 1. Short Circuit (Phase-Phase) |
  • | • No insulation breakdown 2. Ground Fault (Phase-Ground) |
  • +-----------------------------------------------------------------------------+

Critical Code Distinctions:

Overcurrent: Any current in excess of the rated current of equipment or the ampacity of a conductor. It may result from overload, short circuit, or ground fault .

Overload: Operation of equipment in excess of normal, full-load rating, or of a conductor in excess of rated ampacity that, when it persists for a sufficient length of time, would cause damage or dangerous overheating. A fault, such as a short circuit or ground fault, is NOT an overload.

Short Circuit: An abnormal connection of relatively low impedance, whether made intentionally or accidentally, between two points of different potential (e.g., hot-to-hot or hot-to-neutral).

Ground Fault: An unintentional, electrically conductive connection between an ungrounded conductor of an electric circuit and the normally non-current-carrying conductors, metallic enclosures, metallic raceways, metallic equipment, or earth.

  • 6. Other High-Yield Article 100 Definitions
  • Continuous Load

Definition: A load where the maximum current is expected to continue for 3 hours or more .

Exam Application: Under NEC 210.19(A)(1) and 215.2(A)(1), branch circuit and feeder conductors/OCPDs must be sized for 125% of the continuous load plus 100% of noncontinuous loads.

In Sight From (Within Sight From / Within Sight)

Definition: Where specified that equipment shall be "in sight from," the specified equipment shall be visible and not more than 50 feet (15 m) distant from the other.

Exam Application: Motor disconnects, HVAC disconnects, and water heater servicing disconnects must be visible and within 50 ft.

Separately Derived System (SDS)

Definition: An electrical source, other than a service, having no direct connection(s) to circuit conductors of any other electrical source other than those established by grounding and bonding connections.

Common Examples: Distribution transformers (480V Delta to 208Y/120V Wye), standalone solar systems, or generators where the transfer switch switches the neutral conductor.

Ampacity

Definition: The maximum current, in amperes, that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.