Study guide
2.1 Ohm's Law, Joule's Law & DC Circuit Calculations
Idaho Journeyman Electrician Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Orientation, NEC Navigation & Idaho Regulations
1.1 Idaho Journeyman Exam Format, PSI Logistics & Rapid NEC Navigation 1.2 Idaho Electrical Licensing Laws (Title 54, Ch. 10) & IDAPA 24.39.10 Requirements 1.3 Idaho Permits, Inspection Procedures & State-Specific NEC Amendments 1.4 NEC Article 90 Scope, Code Arrangement & Article 110 General Requirements
2 Chapter 2: Electrical Theory & Essential Math Calculations
2.1 Ohm's Law, Joule's Law & DC Circuit Calculations 2.2 Single-Phase & Three-Phase AC Fundamentals and Power Factor 2.3 DC & AC Voltage Drop Calculations and Conductor Sizing 2.4 NEC Article 100 Essential Definitions for Journeymen
3 Chapter 3: Conductors, Raceways & Box Sizing Calculations
3.1 Conductor Ampacity, Insulation Types & Terminal Temperature Ratings 3.2 Ambient Temperature Correction & Raceway Conductor Bundling Derating 3.3 Outlet & Junction Box Volume Fill Calculations (NEC 314.16) 3.4 Conduit Fill Calculations & Large Pull Box Sizing (NEC 314.28)
4 Chapter 4: Branch Circuits & Overcurrent Protection
4.1 Branch Circuit Ratings, Multiwire Circuits & Receptacle Placement 4.2 GFCI & AFCI Protection Mandates and Idaho Code Clarifications 4.3 Overcurrent Protective Devices, Standard Ratings & Small Conductor Rules 4.4 Feeder & Transformer Tap Rules (NEC 240.21)
5 Chapter 5: Feeders, Services & Outside Branch Circuits
5.1 Feeder Conductor Sizing, Neutral Calculations & Voltage Drop 5.2 Outside Branch Circuits, Feeders & Overhead/Underground Clearances 5.3 Service Drop, Service Lateral & Service-Entrance Sizing 5.4 Service Disconnecting Means, Emergency Disconnects & Surge Protection
6 Chapter 6: Load Calculations: Dwellings & Commercial
6.1 General Lighting, Small Appliance & Laundry Load Calculations 6.2 Standard Method Single-Family Dwelling Service Calculations (NEC 220 Part III) 6.3 Optional Method Single-Family & Multifamily Calculations (NEC 220 Part IV) 6.4 Commercial & Industrial Feeder/Service Calculations
7 Chapter 7: Grounding and Bonding: Systems & Electrodes
7.1 Grounding vs. Bonding Fundamentals & System Grounding 7.2 Grounding Electrodes & Grounding Electrode Conductor (GEC) Sizing 7.3 Main Bonding Jumpers, System Bonding Jumpers & Supply-Side Bonding
8 Chapter 8: Grounding and Bonding: Equipment & Enclosures
8.1 Equipment Grounding Conductors (EGC) Types, Installation & Sizing (Table 250.122) 8.2 Separately Derived Systems (SDS) Transformers & Generator Grounding 8.3 Service Enclosure Bonding, Concentric Knockouts & Effective Ground-Fault Path
9 Chapter 9: Wiring Methods, Cables & Conduits
9.1 General Requirements for Wiring Methods & Underground Installations (Article 300) 9.2 Nonmetallic-Sheathed (NM), Metal-Clad (MC) & Armored (AC) Cables 9.3 Metallic & Nonmetallic Raceway Systems (EMT, PVC, RMC, FMC) 9.4 Cabinets, Cutout Boxes & Outlet Box Installation Rules (Articles 312 & 314)
10 Chapter 10: Equipment for General Use: Devices, Luminaires & Appliances
10.1 Switches, Receptacles & Device Installation Standards (Articles 404 & 406) 10.2 Luminaire Clearances, Closet Rules & Lighting Track (Article 410) 10.3 Household Appliances & Fixed Electric Space Heating (Articles 422 & 424) 10.4 Generators, Transformer Overcurrent Protection & Panelboards
11 Chapter 11: Motors, Motor Circuits & Controllers
11.1 Motor Nameplate vs. Table FLC & Branch Circuit Conductor Sizing 11.2 Branch Circuit Short-Circuit & Ground-Fault Protection (Table 430.52) 11.3 Motor Overload Protection Sizing & Selection (NEC 430 Part III) 11.4 Motor Disconnects, Controllers & Multimotor Feeder Calculations
12 Chapter 12: Special Occupancies & Hazardous Locations
12.1 Hazardous (Classified) Locations: Classes, Divisions, Zones & Seals 12.2 Commercial Garages, Repair Hangars & Fuel Dispensing Facilities 12.3 Health Care Facilities: Patient Care Spaces & Redundant Grounding (Article 517) 12.4 Agricultural Buildings, Marinas, Boatyards & RV Parks
13 Chapter 13: Special Equipment, Emergency Systems & Renewable Energy
13.1 Swimming Pools, Spas, Hot Tubs & Equipotential Bonding (Article 680) 13.2 Electric Vehicle Supply Equipment (EVSE) Installation & Sizing (Article 625) 13.3 Solar Photovoltaic (PV) Systems & Energy Storage Systems (Articles 690 & 706) 13.4 Emergency, Standby Power Systems & Fire Pumps (Articles 700, 701, 702 & 695) 13.5 Fire Alarm, Optical Fiber & Power-Limited Circuits (Articles 760, 770 & 800)
2.1 Ohm's Law, Joule's Law & DC Circuit Calculations
Key Takeaways Explain This Topic AI
Ohm's Law defines the proportional relationship between electromotive force (E in volts), current (I in amperes), and resistance (R in ohms): E = I * R, I = E / R, and R = E / I.
Joule's Law defines electrical power (P in watts) as the rate of energy dissipation: P = E * I, P = I² * R, and P = E² / R. Derating a resistive heating load from 240V to 208V reduces power output by 24.9% (operating at 75.1% rated wattage).
In a DC series circuit, current is identical through all components (I_total = I1 = I2 = ...), total resistance is the algebraic sum of all resistances (R_total = R1 + R2 + ...), and the sum of component voltage drops equals source voltage (Kirchhoff's Voltage Law).
In a DC parallel circuit, voltage is identical across all parallel branches (E_total = E1 = E2 = ...), total current is the sum of branch currents (Kirchhoff's Current Law), and total equivalent resistance is always lower than the smallest branch resistance.
Solving complex series-parallel combination circuits requires a systematic reduction method: simplify parallel banks to equivalent series resistances (using product-over-sum or reciprocal formulas), calculate total circuit current, and expand back out to solve branch-specific currents and voltage drops.
Last updated: August 2026
2.1 Ohm's Law, Joule's Law & DC Circuit Calculations
Electrical theory forms the foundation of all National Electrical Code (NEC) rules, overcurrent protection sizing, equipment ratings, and branch-circuit calculations. On the Idaho Journeyman Electrician examination, candidates are expected to manipulate electrical equations quickly, solve multi-resistor network problems, and evaluate electrical power transformations without relying on guesswork.
1. Fundamental Electrical Quantities & Units
All electrical circuits govern the interaction of four fundamental physical quantities: +-----------------------------------------------------------------------------+
- | CORE ELECTRICAL QUANTITIES & SYMBOLS |
- | |
- | QUANTITY SYMBOL (FORMULA) UNIT (SYMBOL) PHYSICAL ANALOGY |
- | ----------------------------------------------------------------------- |
- | Electromotive E (or V) Volt (V) Water Pressure |
- | Force (Voltage) (PSI) |
- | |
- | Current I Ampere (A) Water Flow Rate |
- | (Intensity) (Gallons / Minute) |
- | |
- | Resistance R Ohm (Ω) Pipe Friction / |
- | Restriction |
- | |
- | Electrical P Watt (W) Mechanical Work |
- | Power Rate (Horsepower) |
- +-----------------------------------------------------------------------------+
- Detailed Parameter Definitions
Electromotive Force / Voltage (E or V): The potential difference or electrical pressure required to force one ampere of current through a resistance of one ohm. In electrical calculations, E stands for Electromotive Force (often denoted as V for Voltage ).
Current (I): The rate of electron flow past a given point in a conductor. One ampere represents the movement of one coulomb of electrical charge (6.242 x 10^18 electrons) per second.
Resistance (R): The opposition offered by a material to the flow of electrical current, measured in Ohms (Ω). Conductor resistance depends directly on material resistivity (ρ), length (L), cross-sectional area (A), and operating temperature.
Power (P): The rate at which electrical energy is converted into another form of energy (such as heat, light, or mechanical motion), measured in Watts (W) or Joules per second. In mechanical power conversions, 1 Horsepower (HP) = 746 Watts .
2. Ohm's Law & The Ohm's Circle
Formulated by Georg Simon Ohm in 1827, Ohm's Law states that the current flowing through a conductor between two points is directly proportional to the voltage across the two points and inversely proportional to the resistance between them. +-------------------+
- | E |
- | (Voltage) |
- +---------+---------+
- | I | R |
- | (Amps) | (Ohms) |
- +---------+---------+
- E = I x R | I = E / R | R = E / I
- Step-by-Step Ohm's Law Applications
- Example 1.1: Determining Conductor Operating Current
A 240 V single-phase electric water heater element has an internal cold resistance of 12 Ω. What is the continuous current draw when energized at rated voltage?
- Given: E = 240 V, R = 12 Ω
- I = E / R = (240 V) / (12 Ω) = 20.0 A
- Example 1.2: Calculating Unknown Component Resistance
A 120 V industrial solenoid valve draws 2.5 A when energized. What is the DC resistance of the solenoid coil?
- Given: E = 120 V, I = 2.5 A
- R = E / I = (120 V) / (2.5 A) = 48.0 Ω
- 3. Joule's Law & The 12-Formula Power Wheel
Joule's Law (The Power Law) establishes that the electrical power dissipated in a circuit is directly proportional to the product of voltage and current. By substituting Ohm's Law expressions (E = I x R and I = E / R) into the base power equation P = E x I, electricians derive the complete 12-formula wheel. +-----------------------------------------------------------------------------+
- | THE 12 ELECTRICAL FORMULA MATRIX |
- | |
- | TO FIND: FORMULA 1 FORMULA 2 FORMULA 3 |
- | ----------------------------------------------------------------------- |
- | Voltage (E) E = I * R E = P / I E = √(P * R) |
- | |
- | Current (I) I = E / R I = P / E I = √(P / R) |
- | |
- | Resistance (R) R = E / I R = E² / P R = P / I² |
- | |
- | Power (P) P = E * I P = I² * R P = E² / R |
- +-----------------------------------------------------------------------------+
Important
The Voltage Derating Trap on Resistive Loads (High-Yield Exam Concept): When a purely resistive heating appliance rated for 240 V is connected to a 208 V supply (common in commercial facilities fed by 208Y/120V systems), the resistance of the heating element remains constant, but the power output drops with the square of the voltage:
P_actual = P_rated x (V_applied / V_rated)^2 = P_rated x (208 / 240)^2 = P_rated x (0.8667)^2 = P_rated x 0.7511
A 4,800 W, 240 V heater operated on 208 V will only produce 4,800 x 0.7511 = 3,605.3 W (a 24.9% loss of heating capacity!).
Worked Example: Heat Dissipation in a Bad Connection
An improper, loose wire-nut splice has developed a contact resistance of 0.75 Ω. If a continuous commercial branch-circuit load of 16 A passes through this high-resistance terminal, calculate the thermal power dissipated at the splice.
Given: I = 16 A, R = 0.75 Ω
P = I^2 x R = (16 A)^2 x 0.75 Ω = 256 x 0.75 = 192.0 Watts (Note: 192 Watts concentrated inside an enclosed junction box is equivalent to two 100W incandescent bulbs, rapidly melting conductor insulation and causing electrical fires).
4. DC Series Circuits
A series circuit provides only one continuous path for electric current to flow through all connected loads. +-----------------------------------------------------------------------------+
- | DC SERIES CIRCUIT |
- | |
- | +--------------[ R1 = 10 Ω ]--------------+ |
- | | | |
- | | v |
- | +----+----+ [ R2 = 15 Ω ] |
- | | E_source| | |
- | | = 120 V | v |
- | +----+----+ [ R3 = 25 Ω ] |
- | | | |
- | +-----------------------------------------+ |
- +-----------------------------------------------------------------------------+
Fundamental Series Rules:
Current is Constant: The current is identical at every point in the circuit:
I_total = I_1 = I_2 = I_3 = ... = I_n
Total Resistance is Additive: The total resistance is the direct algebraic sum of individual load resistances:
R_total = R_1 + R_2 + R_3 + ... + R_n
Kirchhoff's Voltage Law (KVL): The sum of all individual voltage drops across series components equals the total applied source voltage:
E_total = V_1 + V_2 + V_3 + ... + V_n
Individual Voltage Drops: Calculated via Ohm's Law: V_n = I_total x R_n.
Total Power is Additive: Total power equals the sum of power consumed by individual components:
- P_total = P_1 + P_2 + P_3 + ... + P_n = E_total x I_total
- Step-by-Step Series Problem Solution
Using the circuit illustrated above (E_source = 120 V, R_1 = 10 Ω, R_2 = 15 Ω, R_3 = 25 Ω):
- Step 1: Calculate Total Circuit Resistance (R_T): R_T = 10 Ω + 15 Ω + 25 Ω = 50.0 Ω
- Step 2: Calculate Total Circuit Current (I_T): I_T = E_T / R_T = (120 V) / (50 Ω) = 2.40 A
- Step 3: Calculate Voltage Drop Across Each Resistor: V_1 = I_T x R_1 = 2.40 A x 10 Ω = 24.0 V
- V_2 = I_T x R_2 = 2.40 A x 15 Ω = 36.0 V
- V_3 = I_T x R_3 = 2.40 A x 25 Ω = 60.0 V
- Check KVL: 24 V + 36 V + 60 V = 120.0 V (Matches Source)
- Step 4: Calculate Individual and Total Power Dissipated: P_1 = (2.4 A)^2 x 10 Ω = 57.6 W
- P_2 = (2.4 A)^2 x 15 Ω = 86.4 W
- P_3 = (2.4 A)^2 x 25 Ω = 144.0 W
- P_T = 57.6 + 86.4 + 144.0 = 288.0 W (Check: P_T = 120 V x 2.4 A = 288.0 W)
- 5. DC Parallel Circuits
A parallel circuit provides two or more independent branches for current to travel across a common voltage supply. +-----------------------------------------------------------------------------+
- | DC PARALLEL CIRCUIT |
- | |
- | +----------------+----------------+ |
- | | | | |
- | v (I1) v (I2) v (I3) |
- | [ R1 = 20 Ω ] [ R2 = 30 Ω ] [ R3 = 60 Ω ] |
- | | | | |
- | +--------+----------------+----------------+ |
- | | |
- | +----+----+ |
- | | E_source| = 120 V |
- | +----+----+ |
- | | |
- | +------------------------------------------+ |
- +-----------------------------------------------------------------------------+
Fundamental Parallel Rules:
Voltage is Constant Across All Branches: E_total = E_1 = E_2 = E_3 = ... = E_n
Kirchhoff's Current Law (KCL): The total current entering a junction must equal the sum of currents leaving that junction:
I_total = I_1 + I_2 + I_3 + ... + I_n
Equivalent Resistance Calculation: The total equivalent resistance is always strictly LESS than the resistance of the smallest individual branch.
General Reciprocal Formula (Any Number of Resistors): 1 / R_total = 1 / R_1 + 1 / R_2 + 1 / R_3 + ... + 1 / R_n => R_total = (1) / (1 / R_1 + 1 / R_2 + ... + 1 / R_n)
Product-Over-Sum Formula (Exactly Two Parallel Resistors): R_total = (R_1 x R_2) / (R_1 + R_2)
Equal-Value Resistor Shortcut: If N identical resistors of resistance R are connected in parallel:
- R_total = R / N
- Step-by-Step Parallel Problem Solution
Using the parallel circuit above (E_source = 120 V, R_1 = 20 Ω, R_2 = 30 Ω, R_3 = 60 Ω):
Step 1: Calculate Total Equivalent Resistance (R_T): 1 / R_T = 1 / 20 + 1 / 30 + 1 / 60 = 3 / 60 + 2 / 60 + 1 / 60 = 6 / 60 = (1) / (10 Ω)
- R_T = 10.0 Ω
- Step 2: Calculate Individual Branch Currents (I_1, I_2, I_3): I_1 = E / R_1 = (120 V) / (20 Ω) = 6.0 A
- I_2 = E / R_2 = (120 V) / (30 Ω) = 4.0 A
- I_3 = E / R_3 = (120 V) / (60 Ω) = 2.0 A
- Step 3: Calculate Total Circuit Current (I_T): I_T = I_1 + I_2 + I_3 = 6.0 A + 4.0 A + 2.0 A = 12.0 A
- Verification via Ohm's Law: I_T = E_T / R_T = (120 V) / (10 Ω) = 12.0 A
- Step 4: Total Power Dissipated: P_T = E_T x I_T = 120 V x 12 A = 1,440.0 W
- 6. Series-Parallel Combination Circuits
Combination circuits contain both series and parallel elements connected together. Solving these requires systematic block reduction. +-----------------------------------------------------------------------------+
- | SERIES-PARALLEL COMBINATION |
- | |
- | +--------[ R1 = 8 Ω ]---------+ |
- | | | |
- | | Node A | |
- | | +-------+ | |
- | | | | | |
- | | v v | |
- | +----+----+ [R2=12Ω] [R3=24Ω] | |
- | | E=120 V | | | | |
- | +----+----+ +-------+ | |
- | | Node B | |
- | | | | |
- | +-------[ R4 = 4 Ω ]----------+ |
- +-----------------------------------------------------------------------------+
Systematic 5-Step Reduction Method:
Identify Parallel Sub-Banks: Locate resistors connected between identical node pairs.
Calculate Equivalent Parallel Resistance (R_p): Replace the parallel branch with a single equivalent resistor.
Combine Series Elements (R_T): Add all remaining series resistors and equivalent parallel blocks.
Calculate Total Circuit Current (I_T): I_T = E_source / R_T.
Work Backwards for Local Values: Determine voltage drops across series elements, subtract to find the remaining voltage across the parallel bank, and calculate individual branch currents.
Complete Worked Solution:
Step 1: Simplify the Parallel Bank (R_2 and R_3): R_p(2-3) = (R_2 x R_3) / (R_2 + R_3) = (12 x 24) / (12 + 24) = 288 / 36 = 8.0 Ω
- Step 2: Calculate Total Series Resistance (R_T): R_T = R_1 + R_p(2-3) + R_4 = 8 Ω + 8 Ω + 4 Ω = 20.0 Ω
- Step 3: Calculate Total Circuit Current (I_T): I_T = E_source / R_T = (120 V) / (20 Ω) = 6.0 A
- Step 4: Calculate Series Voltage Drops: V_R1 = I_T x R_1 = 6.0 A x 8 Ω = 48.0 V
- V_R4 = I_T x R_4 = 6.0 A x 4 Ω = 24.0 V
Step 5: Calculate Voltage Across Parallel Bank (Node A to Node B): V_NodeAB = E_source - (V_R1 + V_R4) = 120 V - (48 V + 24 V) = 120 - 72 = 48.0 V
(Or: V_NodeAB = I_T x R_p(2-3) = 6.0 A x 8.0 Ω = 48.0 V)
Step 6: Calculate Individual Branch Currents through R_2 and R_3: I_R2 = V_NodeAB / R_2 = (48 V) / (12 Ω) = 4.0 A
- I_R3 = V_NodeAB / R_3 = (48 V) / (24 Ω) = 2.0 A
- Check KCL: I_R2 + I_R3 = 4.0 A + 2.0 A = 6.0 A = I_T
- 7. Quick Circuit Comparison Reference
Electrical Property Series Circuit Parallel Circuit Combination Circuit
Current (I) Same through all loads (I_T = I_1 = I_2) Splits across branches (I_T = Sum I_n) Main line carries I_T; splits in parallel banks
Voltage (E) Divides across loads (E_T = Sum V_n) Same across all branches (E_T = E_1 = E_2) Drops occur across series parts; same across shared nodes
Total Resistance (R_T) R_T = R_1 + R_2 + ... (Increases) 1/R_T = 1/R_1 + 1/R_2 + ... (Decreases) Combine step-by-step using reduction rules
Component Failure Open circuit stops all current flow Open branch leaves other branches active Depends on whether open occurs in main trunk or sub-branch