10.1 Switches, Receptacles & Device Installation Standards (Articles 404 & 406)
Idaho Journeyman Electrician Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Orientation, NEC Navigation & Idaho Regulations
1.1 Idaho Journeyman Exam Format, PSI Logistics & Rapid NEC Navigation 1.2 Idaho Electrical Licensing Laws (Title 54, Ch. 10) & IDAPA 24.39.10 Requirements 1.3 Idaho Permits, Inspection Procedures & State-Specific NEC Amendments 1.4 NEC Article 90 Scope, Code Arrangement & Article 110 General Requirements
2 Chapter 2: Electrical Theory & Essential Math Calculations
2.1 Ohm's Law, Joule's Law & DC Circuit Calculations 2.2 Single-Phase & Three-Phase AC Fundamentals and Power Factor 2.3 DC & AC Voltage Drop Calculations and Conductor Sizing 2.4 NEC Article 100 Essential Definitions for Journeymen
3 Chapter 3: Conductors, Raceways & Box Sizing Calculations
3.1 Conductor Ampacity, Insulation Types & Terminal Temperature Ratings 3.2 Ambient Temperature Correction & Raceway Conductor Bundling Derating 3.3 Outlet & Junction Box Volume Fill Calculations (NEC 314.16) 3.4 Conduit Fill Calculations & Large Pull Box Sizing (NEC 314.28)
4 Chapter 4: Branch Circuits & Overcurrent Protection
4.1 Branch Circuit Ratings, Multiwire Circuits & Receptacle Placement 4.2 GFCI & AFCI Protection Mandates and Idaho Code Clarifications 4.3 Overcurrent Protective Devices, Standard Ratings & Small Conductor Rules 4.4 Feeder & Transformer Tap Rules (NEC 240.21)
5 Chapter 5: Feeders, Services & Outside Branch Circuits
5.1 Feeder Conductor Sizing, Neutral Calculations & Voltage Drop 5.2 Outside Branch Circuits, Feeders & Overhead/Underground Clearances 5.3 Service Drop, Service Lateral & Service-Entrance Sizing 5.4 Service Disconnecting Means, Emergency Disconnects & Surge Protection
6 Chapter 6: Load Calculations: Dwellings & Commercial
6.1 General Lighting, Small Appliance & Laundry Load Calculations 6.2 Standard Method Single-Family Dwelling Service Calculations (NEC 220 Part III) 6.3 Optional Method Single-Family & Multifamily Calculations (NEC 220 Part IV) 6.4 Commercial & Industrial Feeder/Service Calculations
7 Chapter 7: Grounding and Bonding: Systems & Electrodes
7.1 Grounding vs. Bonding Fundamentals & System Grounding 7.2 Grounding Electrodes & Grounding Electrode Conductor (GEC) Sizing 7.3 Main Bonding Jumpers, System Bonding Jumpers & Supply-Side Bonding
8 Chapter 8: Grounding and Bonding: Equipment & Enclosures
8.1 Equipment Grounding Conductors (EGC) Types, Installation & Sizing (Table 250.122) 8.2 Separately Derived Systems (SDS) Transformers & Generator Grounding 8.3 Service Enclosure Bonding, Concentric Knockouts & Effective Ground-Fault Path
9 Chapter 9: Wiring Methods, Cables & Conduits
9.1 General Requirements for Wiring Methods & Underground Installations (Article 300) 9.2 Nonmetallic-Sheathed (NM), Metal-Clad (MC) & Armored (AC) Cables 9.3 Metallic & Nonmetallic Raceway Systems (EMT, PVC, RMC, FMC) 9.4 Cabinets, Cutout Boxes & Outlet Box Installation Rules (Articles 312 & 314)
10 Chapter 10: Equipment for General Use: Devices, Luminaires & Appliances
10.1 Switches, Receptacles & Device Installation Standards (Articles 404 & 406) 10.2 Luminaire Clearances, Closet Rules & Lighting Track (Article 410) 10.3 Household Appliances & Fixed Electric Space Heating (Articles 422 & 424) 10.4 Generators, Transformer Overcurrent Protection & Panelboards
11 Chapter 11: Motors, Motor Circuits & Controllers
11.1 Motor Nameplate vs. Table FLC & Branch Circuit Conductor Sizing 11.2 Branch Circuit Short-Circuit & Ground-Fault Protection (Table 430.52) 11.3 Motor Overload Protection Sizing & Selection (NEC 430 Part III) 11.4 Motor Disconnects, Controllers & Multimotor Feeder Calculations
12 Chapter 12: Special Occupancies & Hazardous Locations
12.1 Hazardous (Classified) Locations: Classes, Divisions, Zones & Seals 12.2 Commercial Garages, Repair Hangars & Fuel Dispensing Facilities 12.3 Health Care Facilities: Patient Care Spaces & Redundant Grounding (Article 517) 12.4 Agricultural Buildings, Marinas, Boatyards & RV Parks
13 Chapter 13: Special Equipment, Emergency Systems & Renewable Energy
13.1 Swimming Pools, Spas, Hot Tubs & Equipotential Bonding (Article 680) 13.2 Electric Vehicle Supply Equipment (EVSE) Installation & Sizing (Article 625) 13.3 Solar Photovoltaic (PV) Systems & Energy Storage Systems (Articles 690 & 706) 13.4 Emergency, Standby Power Systems & Fire Pumps (Articles 700, 701, 702 & 695) 13.5 Fire Alarm, Optical Fiber & Power-Limited Circuits (Articles 760, 770 & 800)
10.1 Switches, Receptacles & Device Installation Standards (Articles 404 & 406)
Key Takeaways Explain This Topic AI
NEC 404.2 mandates that switches must disconnect only ungrounded conductors, and NEC 404.2(C) requires a grounded neutral conductor at lighting switch locations for electronic controls, subject to raceway/framing exceptions.
Knife switches must be mounted vertically under NEC 404.6(A) so gravity will not close contacts, with supply line conductors connected to upper stationary contacts to de-energize blades when open.
NEC 406.12 mandates Tamper-Resistant (TR) receptacles in all dwelling units, guest rooms, child care facilities, preschools, pediatric clinics, dormitories, assisted living spaces, and airport concourses.
NEC 406.9 requires Weather-Resistant (WR) receptacles in damp and wet locations, and mandates listed Extra-Duty while-in-use outlet box hoods for all 15A/20A, 120V/250V receptacles in wet locations.
Under NEC 406.4(D), existing ungrounded 2-wire receptacles can be replaced with GFCI receptacles marked 'No Equipment Ground' or downstream receptacles marked 'GFCI Protected' and 'No Equipment Ground'.
Last updated: August 2026
10.1 Switches, Receptacles & Device Installation Standards (Articles 404 & 406)
Switches and receptacles represent the primary human-interactive interfaces of any electrical installation. Consequently, NEC Article 404 (Switches) and NEC Article 406 (Receptacles, Cord Connectors, and Attachment Plugs) establish rigorous safety mandates designed to prevent electric shock, arc flash, mechanical failure, and fire hazards.
For the Idaho Journeyman Electrician examination, candidates must possess master-level proficiency in switch wiring rules, neutral conductor mandates at switch boxes, knife switch physical orientation, Tamper-Resistant (TR) and Weather-Resistant (WR) receptacle requirements, Extra-Duty while-in-use enclosure standards, controlled receptacle markings, and retrofit receptacle replacement protocols under NEC 406.4(D) .
1. Switch Installation Standards (NEC Article 404)
NEC Article 404 governs all switching devices—including snap switches, knife switches, dimmers, circuit breakers used as switches, and electronic lighting controls. +-----------------------------------------------------------------------------+
- | NEC ARTICLE 404 SWITCH SAFETY MANDATES |
- | |
- | [404.2(A) SWITCHING UNGROUNDED CONDUCTORS] |
- | * Switches MUST disconnect ONLY ungrounded (hot) conductors. |
- | * The neutral / grounded conductor must NEVER be switched alone! |
- | |
- | [404.2(C) GROUNDED CONDUCTOR AT SWITCH LOCATIONS] |
- | * A grounded (neutral) conductor MUST be provided at every switch point |
- | controlling lighting loads for electronic controls / occupancy sensors. |
- | |
- | [404.6(A) KNIFE SWITCH ORIENTATION] |
- | * MUST be mounted vertically so GRAVITY will NOT close contacts. |
- | * Supply / Line MUST connect to upper jaws; Load connects to blades. |
- +-----------------------------------------------------------------------------+
- Switching of Ungrounded vs. Grounded Conductors (NEC 404.2)
Ungrounded Conductors Only (404.2(A)): Three-way and four-way switches must be wired so that all switching occurs strictly in the ungrounded phase conductors. Wiring between switches and lampholders must never permit the grounded neutral conductor to be switched.
Grounded Conductors (404.2(B)): A switch or circuit breaker must never disconnect the grounded (neutral) conductor of a circuit unless the device simultaneously disconnects all ungrounded phase conductors, or where the grounded conductor is disconnected via an approved multipole switch.
Mandatory Grounded Conductor at Switch Locations (NEC 404.2(C))
To eliminate the unsafe practice of electronic occupancy sensors and smart switches dumping low-level leakage current onto the equipment grounding conductor (EGC), NEC 404.2(C) mandates that the grounded conductor (neutral) of the lighting circuit must be installed at all switch points controlling lighting loads.
Exceptions to NEC 404.2(C) (Neutral Not Required at Switch Box):
Raceway System: Where conductors enter through a raceway system (e.g., EMT, PVC) that allows a neutral conductor to be easily pulled into the box in the future without damaging the building finish.
Accessible Framing / Cable Routing: Where the switch box is accessible from an unfinished attic, crawlspace, or framed wall cavity where additional cables can be run without removing wallboard or paneling.
Snap Switches with Integral Controls: Locations where lighting is controlled solely by automatic building automation systems not requiring local device power.
Multiple Switch Ganging: Where multiple switches control lights in the same room, a neutral conductor is required in only one gang of a multi-gang box.
Non-Lighting Loads: Where switches control dedicated motors, fans, or receptacle outlets rather than lighting luminaires. +-----------------------------------------------------------------------------+
- | THREE-WAY & FOUR-WAY SWITCH WIRING LOGIC |
- | |
- | 120V Line (Hot) Switched Leg |
- | --------[Common] Travelers [Common]--------> |
- | \ +=======================+ / (Lamp) |
- | O==========| T1 T1 |==========O |
- | 3-Way SW 1 O==========| T2 T2 |==========O 3-Way SW 2 |
- | +=======================+ |
- | 4-Way Switch (Middle) |
- | |
- | * 3-Way Switches: 3 Terminals (1 Common + 2 Travelers) + Ground Terminal |
- | * 4-Way Switches: 4 Terminals (2 In Travelers + 2 Out Travelers) + Ground |
- +-----------------------------------------------------------------------------+
- Knife Switch Mounting & Operating Position (NEC 404.6)
Vertical Mounting (404.6(A)): Single-throw knife switches must be mounted in an upright vertical position so that gravity will tend to open the switch blades , never close them.
Line/Load Connections (404.6(C)): Single-throw knife switches must be wired so that the switch blades are de-energized when the switch is open. The supply (line) must connect to the top stationary contact jaws , and the load must connect to the hinged blades.
Accidental Closure (404.6(B)): Double-throw knife switches mounted vertically must be equipped with a mechanical locking device that holds the blades securely in the open position to prevent gravity closure.
Faceplate Grounding & Isolating Screws (NEC 404.9)
Metallic Faceplates (404.9(B)): Metal faceplates must be grounded to the circuit equipment grounding conductor (EGC) by means of a metal mounting screw threaded into a bonded metal device yoke or metal box.
Nonmetallic Faceplates (404.9(C)): Nonmetallic faceplates must cover the entire box opening and extend at least flush with the surrounding wall surface.
Damaged Yokes: Snap switches with broken or cracked mounting yokes must be replaced immediately.
2. Receptacle Ratings & Terminal Identification (NEC Article 406)
NEC Article 406 regulates the rating, type, mounting, and grounding of receptacle outlets, cord connectors, and attachment plugs. +-----------------------------------------------------------------------------+
- | RECEPTACLE TERMINAL IDENTIFICATION |
- | |
- | Terminal Color Conductor Connected NEC Reference |
- | ----------------------------------------------------------------------- |
- | Brass / Bronze Ungrounded (Hot) Conductor NEC 200.10(B) |
- | Silver / White Grounded (Neutral) Conductor NEC 200.10(B) |
- | Green / Hex-Head Screw Equipment Ground (EGC) NEC 250.126 |
- +-----------------------------------------------------------------------------+
- Receptacle Ratings vs. Branch Circuit Ratings (NEC 406.3(A) & 210.21(B))
Single Receptacle on Individual Circuit: A single receptacle installed on an individual branch circuit must have an ampere rating not less than that of the branch circuit (e.g., a 20A dedicated circuit requires a minimum 20A single receptacle).
Multiple Receptacles on Branch Circuit: Where two or more receptacles (or duplex receptacles) are connected to a branch circuit, the receptacle ratings must conform to NEC Table 210.21(B)(2) :
- Branch Circuit Rating (Amperes) Permitted Receptacle Ratings (Amperes)
- 15 A 15 A only
- 20 A 15 A or 20 A
- 30 A 30 A only
- 40 A 40 A or 50 A
- 50 A 50 A only
Note
A standard 15A duplex receptacle consists of two receptacles on a single yoke. Therefore, standard 15A duplex receptacles are fully code-compliant on 20A general-purpose multi-outlet branch circuits!
Grounding Pole & Terminal Connections (NEC 406.4)
Receptacles connected to circuits with an equipment grounding conductor must have their grounding contacts connected to the EGC.
The equipment grounding conductor must be bonded to the metal box using a grounding screw (NEC 250.148) and connected to the receptacle grounding terminal, unless the receptacle is a listed self-grounding type installed in a surface-mounted metal box or flush-mounted metal box with direct metal-to-metal contact (NEC 250.146).
3. Tamper-Resistant (TR) Receptacle Mandates (NEC 406.12)
Tamper-Resistant (TR) receptacles feature built-in UL-listed internal sliding shutters that prevent the insertion of foreign objects (keys, paper clips, hairpins, nails) into the energized slots. The shutters only slide open when equal, simultaneous pressure is applied by the two blades of a standard attachment plug. +-----------------------------------------------------------------------------+
- | MANDATORY TAMPER-RESISTANT (TR) LOCATIONS (NEC 406.12) |
- | |
- | [1] Dwelling Units (All 15A & 20A, 125V & 250V nonlocking receptacles) |
- | [2] Guest Rooms & Guest Suites of Hotels and Motels |
- | [3] Child Care Facilities & Preschools |
- | [4] Elementary Education Facilities & Kindergarten Classrooms |
- | [5] Business Offices, Corridors & Waiting Areas of Pediatric Healthcare |
- | [6] Dormitories, Fraternity & Sorority Houses |
- | [7] Assisted Living & Residential Care Facilities |
- | [8] Airport Passenger Concourse & Gate Waiting Areas |
- +-----------------------------------------------------------------------------+
- Comprehensive List of Required TR Locations
Under NEC 406.12 , all 15- and 20-ampere, 125- and 250-volt nonlocking-type receptacles in the following occupancies must be listed tamper-resistant:
Dwelling Units: All interior and exterior areas, including basements, garages, accessory buildings, hallways, living rooms, bedrooms, and outdoor patios.
Hotel and Motel Guest Rooms and Guest Suites.
Child Care Facilities (as defined in Article 100).
Preschools and Elementary Education Facilities.
Pediatric Healthcare Spaces: Business offices, waiting rooms, examination rooms, and hallways of clinics and hospitals.
Dormitory Units in colleges, universities, and schools.
Residential Care and Assisted Living Facilities.
Airport Passenger Waiting Areas and Concourses.
Exceptions to NEC 406.12 (TR Not Required):
Receptacles located more than 5-1/2 feet (1.7 m) above the finished floor.
Receptacles that are part of a luminaire or appliance.
A single receptacle located within a dedicated space for an appliance that, in normal use, is not easily moved (e.g., behind a refrigerator, washing machine, or built-in microwave).
4. Damp & Wet Location Receptacles & Extra-Duty Covers (NEC 406.9)
Receptacles installed outdoors or in moisture-prone interior environments must withstand weather exposure, corrosion, and water infiltration. +-----------------------------------------------------------------------------+
- | OUTDOOR RECEPTACLE ENCLOSURE STANDARDS (406.9) |
- | |
- | DAMP LOCATIONS (406.9(A)) WET LOCATIONS (406.9(B)(1)) |
- | (Under covered porches, canopies) (Uncovered, rain, snow, spray) |
- | |
- | +--------------------------+ +--------------------------+ |
- | | Standard Weatherproof | | "EXTRA-DUTY" HOOD | |
- | | Cover (Weatherproof ONLY | | (While-In-Use Cover) | |
- | | when plug is removed / | | Keeps enclosure WR | |
- | | flap closed) | | EVEN WHEN CORD IS | |
- | | | | PLUGGED IN! | |
- | +--------------------------+ +--------------------------+ |
- | Receptacle: Must be listed Receptacle: Must be listed |
- | Weather-Resistant (WR) Weather-Resistant (WR) |
- +-----------------------------------------------------------------------------+
- Detailed Breakdown of NEC 406.9 Requirements
Location / Voltage Class Mandatory Cover Type Receptacle Listing Required
Damp Location (Covered porch, open barn, roofed patio) Weatherproof enclosure (closure cover weatherproof when plug is removed) Listed Weather-Resistant (WR) (NEC 406.9(A))
Wet Location: 15A & 20A, 120V & 250V (Open outdoors, garden, deck) Listed Extra-Duty Outlet Box Hood (while-in-use cover weatherproof whether plug is inserted or removed) Listed Weather-Resistant (WR) (NEC 406.9(B)(1))
Wet Location: Other than 15A/20A 120/250V (e.g., 30A, 50A RV/welder) Weatherproof enclosure (while-in-use cover if portable equipment; weatherproof flap if equipment not continuous) Standard heavy-duty industrial rating
Warning
Extra-Duty Mandate: The "Extra-Duty" while-in-use hood mandate under NEC 406.9(B)(1) applies to ALL wet location 15A and 20A, 120V and 250V receptacles , regardless of whether the installation is residential, commercial, or industrial! Flat spring-loaded snap covers are strictly prohibited in wet locations for standard 15A/20A plugs.
Weather-Resistant (WR) Receptacle Construction
Listed Weather-Resistant (WR) receptacles are constructed with UV-stabilized nonmetallic faceplates , heavy-duty brass mounting straps, stainless steel assembly screws, and corrosion-resistant contact springs to survive sub-zero freezing, high humidity, and sunlight exposure.
5. Controlled Receptacles for Energy Management (NEC 406.3(E))
Modern building energy conservation codes (ASHRAE 90.1, IECC, and California Title 24) mandate that at least 50% of 125V, 15A and 20A receptacles in private offices, open plan office cubicles, and hotel guest rooms be automatically shut off when unoccupied to reduce plug load phantom power draw. +-----------------------------------------------------------------------------+
- | NEC 406.3(E) CONTROLLED RECEPTACLE MARKING ICON |
- | |
- | |\ /| |
- | | \ / | |
- | | \ / | |
- | | \/ | |
- | ( [()] ) |
- | \ / |
- | \ / |
- | \ / |
- | \/ |
- | |
- | Word: "CONTROLLED" |
- | * Symbol and word MUST be permanently marked on face of receptacle. |
- | * For split-wired duplexes, marking must clearly identify which socket. |
- +-----------------------------------------------------------------------------+
Marking Mandate: All nonlocking-type 125V, 15A and 20A receptacles that are automatically controlled by an energy management timer, occupancy sensor, or BAS system must be marked with the universal power symbol icon and the word "CONTROLLED" .
Split-Wired Receptacles: Where only one half of a duplex receptacle is automatically switched and the other half remains unswitched (hot 240/7), the controlled socket face must be permanently marked with the symbol and text.
6. Receptacle Replacement Rules (NEC 406.4(D))
When replacing existing receptacles during remodeling or service upgrades, the replacement receptacles must comply with the current National Electrical Code requirements outlined in NEC 406.4(D) . +-----------------------------------------------------------------------------+
- | RECEPTACLE REPLACEMENT PROTOCOL (406.4(D)) |
- | |
- | EXISTING BOX CONDITION PERMITTED REPLACEMENT METHOD |
- | ----------------------------------------------------------------------- |
- | [1] Grounding EGC Available -> Standard Grounding-type Receptacle |
- | (or GFCI/AFCI/TR where required by code)|
- | |
- | [2] No EGC in Box -> Method A: Replace with another |
- | (Old 2-wire cloth / knob- non-grounding 2-wire receptacle. |
- | and-tube wiring) -> Method B: Replace with GFCI receptacle |
- | marked "No Equipment Ground". |
- | -> Method C: Replace with standard 3-wire |
- | grounding receptacle supplied from |
- | upstream GFCI, marked BOTH |
- | "GFCI Protected" AND |
- | "No Equipment Ground". |
- +-----------------------------------------------------------------------------+
- Replacement Requirements Summary (NEC 406.4(D))
Grounding-Type Receptacles (406.4(D)(1)): Where a grounding means exists in the box, grounding-type receptacles must be installed and bonded to the EGC.
Non-Grounding Receptacle Replacement (406.4(D)(2)): Where no equipment ground exists, three compliant options exist:
Replace with another non-grounding (2-prong) receptacle.
Replace with a GFCI receptacle, provided it is permanently marked "No Equipment Ground" .
Replace with a standard grounding-type (3-prong) receptacle fed from an upstream GFCI, provided the receptacle is marked "GFCI Protected" AND "No Equipment Ground" .
GFCI Protection Mandate (406.4(D)(3)): If a replacement receptacle is located in an area where NEC 210.8 currently requires GFCI protection (kitchen counters, bathrooms, outdoors, garages, basements, laundry), the replacement MUST be GFCI-protected , even if GFCI protection was not required when the building was originally constructed.
AFCI Protection Mandate (406.4(D)(4)): Where receptacles are replaced in branch circuits requiring AFCI protection under NEC 210.12, the replacement receptacle must be AFCI protected (via AFCI breaker, outlet branch-circuit AFCI receptacle at first outlet, or system combination).
Tamper-Resistant Mandate (406.4(D)(5)): Receptacles replaced in locations specified by NEC 406.12 (dwellings, daycares, hotels) must be Tamper-Resistant (TR) .
Weather-Resistant Mandate (406.4(D)(6)): Receptacles replaced in damp or wet locations must be listed Weather-Resistant (WR) .