5.2 Outside Branch Circuits, Feeders & Overhead/Underground Clearances

Idaho Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Orientation, NEC Navigation & Idaho Regulations

1.1 Idaho Journeyman Exam Format, PSI Logistics & Rapid NEC Navigation 1.2 Idaho Electrical Licensing Laws (Title 54, Ch. 10) & IDAPA 24.39.10 Requirements 1.3 Idaho Permits, Inspection Procedures & State-Specific NEC Amendments 1.4 NEC Article 90 Scope, Code Arrangement & Article 110 General Requirements

2 Chapter 2: Electrical Theory & Essential Math Calculations

2.1 Ohm's Law, Joule's Law & DC Circuit Calculations 2.2 Single-Phase & Three-Phase AC Fundamentals and Power Factor 2.3 DC & AC Voltage Drop Calculations and Conductor Sizing 2.4 NEC Article 100 Essential Definitions for Journeymen

3 Chapter 3: Conductors, Raceways & Box Sizing Calculations

3.1 Conductor Ampacity, Insulation Types & Terminal Temperature Ratings 3.2 Ambient Temperature Correction & Raceway Conductor Bundling Derating 3.3 Outlet & Junction Box Volume Fill Calculations (NEC 314.16) 3.4 Conduit Fill Calculations & Large Pull Box Sizing (NEC 314.28)

4 Chapter 4: Branch Circuits & Overcurrent Protection

4.1 Branch Circuit Ratings, Multiwire Circuits & Receptacle Placement 4.2 GFCI & AFCI Protection Mandates and Idaho Code Clarifications 4.3 Overcurrent Protective Devices, Standard Ratings & Small Conductor Rules 4.4 Feeder & Transformer Tap Rules (NEC 240.21)

5 Chapter 5: Feeders, Services & Outside Branch Circuits

5.1 Feeder Conductor Sizing, Neutral Calculations & Voltage Drop 5.2 Outside Branch Circuits, Feeders & Overhead/Underground Clearances 5.3 Service Drop, Service Lateral & Service-Entrance Sizing 5.4 Service Disconnecting Means, Emergency Disconnects & Surge Protection

6 Chapter 6: Load Calculations: Dwellings & Commercial

6.1 General Lighting, Small Appliance & Laundry Load Calculations 6.2 Standard Method Single-Family Dwelling Service Calculations (NEC 220 Part III) 6.3 Optional Method Single-Family & Multifamily Calculations (NEC 220 Part IV) 6.4 Commercial & Industrial Feeder/Service Calculations

7 Chapter 7: Grounding and Bonding: Systems & Electrodes

7.1 Grounding vs. Bonding Fundamentals & System Grounding 7.2 Grounding Electrodes & Grounding Electrode Conductor (GEC) Sizing 7.3 Main Bonding Jumpers, System Bonding Jumpers & Supply-Side Bonding

8 Chapter 8: Grounding and Bonding: Equipment & Enclosures

8.1 Equipment Grounding Conductors (EGC) Types, Installation & Sizing (Table 250.122) 8.2 Separately Derived Systems (SDS) Transformers & Generator Grounding 8.3 Service Enclosure Bonding, Concentric Knockouts & Effective Ground-Fault Path

9 Chapter 9: Wiring Methods, Cables & Conduits

9.1 General Requirements for Wiring Methods & Underground Installations (Article 300) 9.2 Nonmetallic-Sheathed (NM), Metal-Clad (MC) & Armored (AC) Cables 9.3 Metallic & Nonmetallic Raceway Systems (EMT, PVC, RMC, FMC) 9.4 Cabinets, Cutout Boxes & Outlet Box Installation Rules (Articles 312 & 314)

10 Chapter 10: Equipment for General Use: Devices, Luminaires & Appliances

10.1 Switches, Receptacles & Device Installation Standards (Articles 404 & 406) 10.2 Luminaire Clearances, Closet Rules & Lighting Track (Article 410) 10.3 Household Appliances & Fixed Electric Space Heating (Articles 422 & 424) 10.4 Generators, Transformer Overcurrent Protection & Panelboards

11 Chapter 11: Motors, Motor Circuits & Controllers

11.1 Motor Nameplate vs. Table FLC & Branch Circuit Conductor Sizing 11.2 Branch Circuit Short-Circuit & Ground-Fault Protection (Table 430.52) 11.3 Motor Overload Protection Sizing & Selection (NEC 430 Part III) 11.4 Motor Disconnects, Controllers & Multimotor Feeder Calculations

12 Chapter 12: Special Occupancies & Hazardous Locations

12.1 Hazardous (Classified) Locations: Classes, Divisions, Zones & Seals 12.2 Commercial Garages, Repair Hangars & Fuel Dispensing Facilities 12.3 Health Care Facilities: Patient Care Spaces & Redundant Grounding (Article 517) 12.4 Agricultural Buildings, Marinas, Boatyards & RV Parks

13 Chapter 13: Special Equipment, Emergency Systems & Renewable Energy

13.1 Swimming Pools, Spas, Hot Tubs & Equipotential Bonding (Article 680) 13.2 Electric Vehicle Supply Equipment (EVSE) Installation & Sizing (Article 625) 13.3 Solar Photovoltaic (PV) Systems & Energy Storage Systems (Articles 690 & 706) 13.4 Emergency, Standby Power Systems & Fire Pumps (Articles 700, 701, 702 & 695) 13.5 Fire Alarm, Optical Fiber & Power-Limited Circuits (Articles 760, 770 & 800)

5.2 Outside Branch Circuits, Feeders & Overhead/Underground Clearances

Key Takeaways Explain This Topic AI

NEC Article 225 governs outside branch circuits and feeders run on or between buildings, structures, or poles on the premises.

Overhead span clearances under NEC 225.18 and 230.24 require 10 ft above pedestrian walkways (<=150V to ground), 12 ft over residential driveways (<=300V to ground), 15 ft over driveways exceeding 300V, 18 ft over public roads and commercial truck traffic areas, and 24.5 ft over railroad tracks.

Open conductors must maintain a minimum clearance of 3 feet from windows that are designed to open, doors, porches, balconies, ladders, stairs, and fire escapes per NEC 225.19(D) and 230.9(A).

Overhead conductors passing over roofs must maintain 8 ft vertical clearance over flat roofs (225.19(A)), reduced to 3 ft for roof pitches 4:12 or steeper, and reduced to 18 inches for through-the-roof mast installations terminating within 6 ft of the roof edge.

NEC Table 300.5 establishes mandatory minimum underground cover depths: 24 inches for direct burial cables (Column 1), 6 inches for Rigid Metal Conduit (Column 2), 18 inches for PVC Schedule 40/80 (Column 3), and 12 inches for residential 120V GFCI circuits (Column 4).

Last updated: August 2026

5.2 Outside Branch Circuits, Feeders & Overhead/Underground Clearances

Wiring installed outdoors between separate buildings or structures—such as running power from a residential dwelling to a detached shop, or distributing three-phase feeders across a commercial campus—is governed by NEC Article 225 (Outside Branch Circuits and Feeders) , Article 230 (Services) , and Article 300 (Wiring Methods) .

Because outdoor wiring is exposed to severe environmental stressors, mechanical impacts, vehicle traffic, snow accumulation, and structural maintenance hazards, the National Electrical Code enforces strict vertical, horizontal, roof, and underground cover clearances .

1. Outside Branch Circuits & Outbuilding Disconnects (NEC Article 225)

When a feeder or branch circuit supplies a detached building or structure (such as a garage, agricultural barn, pump house, or commercial storage facility), specific disconnect and grounding rules apply. +-----------------------------------------------------------------------------+

  • | OUTBUILDING FEEDER DISCONNECT REQUIREMENTS |
  • | |
  • | [DISCONNECTING MEANS (NEC 225.31 & 225.32)] |
  • | * A disconnecting means must be provided at the detached structure to |
  • | disconnect all ungrounded conductors simultaneously. |
  • | * Location: Readily accessible at the point of entrance (interior or ext).|
  • | |
  • | [NUMBER OF SUPPLIES PERMITTED (NEC 225.30)] |
  • | * General Rule: A building or structure can only be served by ONE feeder |
  • | or branch circuit from another building. |
  • | * Exceptions: Fire pumps, emergency systems, multi-voltage requirements, |
  • | or large capacity installations by special permission. |
  • | |
  • | [GROUNDING AT DETACHED BUILDING (NEC 250.32)] |
  • | * Feeder MUST include an Equipment Grounding Conductor (4-wire feeder). |
  • | * Detached building must have its OWN grounding electrode system (e.g., |
  • | ground rods or concrete-encased electrode). |
  • | * Neutral and Ground busbars MUST REMAIN ISOLATED (Floating neutral). |
  • +-----------------------------------------------------------------------------+
  • 2. Overhead Span Clearances Above Grade (NEC 225.18 & 230.24(B))

Open overhead conductors and multi-conductor cables operating at 600V nominal or less must maintain minimum vertical clearances above finished grade, sidewalks, platforms, and roadways. +-----------------------------------------------------------------------------+

  • | OVERHEAD SPAN CLEARANCE MATRIX (NEC 225.18) |
  • | |
  • | 24.5 FT =========================================> Railroad Tracks |
  • | |
  • | 18.0 FT =========================================> Public Roads, Streets,|
  • | Alleys, Commercial |
  • | Truck Parking |
  • | |
  • | 15.0 FT =========================================> Residential Driveways |
  • | Exceeding 300V to Gnd |
  • | |
  • | 12.0 FT =========================================> Residential Driveways |
  • | & Commercial Areas |
  • | Max 300V to Ground |
  • | |
  • | 10.0 FT =========================================> Pedestrian Walkways & |
  • | Platforms Only |
  • | Max 150V to Ground |
  • +-----------------------------------------------------------------------------+
  • Detailed Clearance Applications

Elevation Requirement Applicable Ground Condition / Surface Area Voltage Restriction Code Citation

10 Feet (3.0 m) Above finished grade, sidewalks, platforms, or any projection from which conductors might be reached by pedestrians only. Max 150V to ground NEC 225.18(1) & 230.24(B)(1)

12 Feet (3.7 m) Over residential property and driveways, and commercial areas not subject to commercial truck traffic. Max 300V to ground NEC 225.18(2) & 230.24(B)(2)

15 Feet (4.5 m) Over residential property, driveways, and commercial areas where voltage exceeds 300V to ground. Exceeding 300V to ground NEC 225.18(3) & 230.24(B)(3)

18 Feet (5.5 m) Over public streets, alleys, roads, parking areas subject to truck traffic, driveways on other than residential property, and cultivated/grazing agricultural fields. Max 600V nominal NEC 225.18(4) & 230.24(B)(4)

24.5 Feet (7.5 m) Track clearance over railroad tracks. Max 600V nominal NEC 225.18(5) & 230.24(B)(5)

Important

Exam Distinction Between 12 Ft and 15 Ft Driveway Rules: For a standard 120/240V single-phase residential driveway (where voltage to ground is 120V), the minimum overhead clearance is 12 feet . If the overhead span is a 480V 3-phase delta or 277/480V wye feeder crossing a driveway, the voltage to ground exceeds 300V (or is 277V/480V), requiring a minimum clearance of 15 feet .

3. Clearances from Building Openings & Surfaces (NEC 225.19 & 230.9)

Conductors installed outdoors must be kept away from building openings to protect occupants and maintenance personnel from accidental contact. +-----------------------------------------------------------------------------+

  • | CLEARANCE FROM BUILDING OPENINGS (NEC 230.9) |
  • | |
  • | +------------------------+ |
  • | | WINDOW (OPENS) | |
  • | | | |
  • | +------------------------+ |
  • | | | |
  • | <-- 3 FT -->| |<-- 3 FT --> |
  • | [CLEARANCE] [CLEARANCE] |
  • | |
  • | * Minimum 3 Feet (900 mm) clearance required from windows that OPEN, |
  • | doors, porches, balconies, stairs, ladders, and fire escapes. |
  • | * EXCEPTION: Conductors run ABOVE the top level of a window are permitted |
  • | to be less than 3 feet from the window. |
  • +-----------------------------------------------------------------------------+
  • Key Building Opening Rules

3-Foot Envelope: Overhead conductors must maintain at least 3 feet (900 mm) of clearance from windows that open, doors, porches, balconies, stairs, and fire escapes.

Top of Window Exception: Conductors installed above the upper trim level of a window are not within reach of persons leaning out and therefore are exempt from the 3-foot horizontal clearance.

Vegetation / Trees (NEC 225.26 & 230.10): Vegetation such as live trees shall never be used for the support of overhead conductor spans or outdoor lighting fixtures (except for temporary decorative holiday lighting under Article 590).

4. Overhead Clearances Over Roofs (NEC 225.19(A) & 230.24(A))

Conductors passing over roofs must maintain adequate clearance based on roof slope and installation geometry. +-----------------------------------------------------------------------------+

  • | OVERHEAD CLEARANCE OVER ROOFS MATRIX |
  • | |
  • | [STANDARD FLAT ROOF / LOW-PITCH ROOF (< 4:12 PITCH)] |
  • | * Minimum Vertical Clearance = 8.0 Feet (2.4 m) |
  • | * Must be maintained for at least 3.0 Feet in all directions from edge. |
  • | |
  • | [STEEP-PITCHED ROOF (>= 4:12 PITCH - 4" RISE PER 12" RUN)] |
  • | * Minimum Vertical Clearance = 3.0 Feet (900 mm) |
  • | * Applicable where voltage between conductors does not exceed 300V. |
  • | |
  • | [OVERHANG / SERVICE MAST PENETRATION EXCEPTION (230.24(A) Ex. 3)] |
  • | * Minimum Vertical Clearance = 18 Inches (450 mm) |
  • | * Permitted ONLY IF conductors pass over not more than 4 Feet of roof |
  • | overhang AND terminate at a through-the-roof service mast located |
  • | within 6 Feet of the roof edge. |
  • +-----------------------------------------------------------------------------+
  • Comparison Table: Roof Clearances

Roof Profile & Condition Minimum Vertical Clearance Conditions & Restrictions

Flat Roofs & Low Slopes (< 4:12) 8.0 Feet (2.4 m) Standard rule; pedestrian walkable roofs subject to 8 ft clearance

Roofs with Pitch >= 4:12 3.0 Feet (900 mm) Voltage between conductors must not exceed 300V; steep slope prevents walking

Mast Penetration over Overhang 18 Inches (450 mm) Max 4 ft conductor span over overhang; mast within 6 ft of roof edge

Conductively Attached Overhang 12 Inches (300 mm) Conductors terminate at side of building; passes over eaves only

5. Underground Minimum Cover Depths (NEC Table 300.5)

Underground wiring methods must be buried deep enough to prevent mechanical damage from excavation, vehicular traffic, and landscaping equipment. Cover is defined as the shortest distance measured between the top surface of any direct-buried conductor, cable, or raceway and the finished grade or concrete surface. +-----------------------------------------------------------------------------+

  • | NEC TABLE 300.5 BURIAL DEPTH OVERVIEW |
  • | |
  • | Grade Level ----------------------------------------------------------- |
  • | | |
  • | |-- 6" ---> Column 2: Rigid Metal Conduit (RMC) / IMC |
  • | | |
  • | |-- 12" ---> Column 4: Residential 120V GFCI Branch Circuit (<=20A) |
  • | | |
  • | |-- 18" ---> Column 3: Nonmetallic Raceway (PVC Sch 40/80, RTRC) |
  • | | |
  • | |-- 24" ---> Column 1: Direct Burial Cable (Type UF, USE) |
  • +-----------------------------------------------------------------------------+
  • Master Underground Cover Requirements (Table 300.5)

Location / Surface Condition Col. 1: Direct Burial (UF, USE) Col. 2: Rigid Metal Conduit (RMC/IMC) Col. 3: Rigid PVC (Sch 40/80) Col. 4: Residential 120V GFCI (<= 20A) Col. 5: In/Under 4" Concrete Slab

All locations not specified below (Standard Earth / Soil) 24 in. 6 in. 18 in. 12 in. 18 in.

In trench below 2-in. thick concrete or equivalent pad 18 in. 6 in. 12 in. 6 in. 6 in.

Under minimum 4-in. thick concrete slab (no vehicular traffic) 18 in. 4 in. (or 0" in slab) 4 in. (or 0" in slab) 6 in. 4 in.

Under commercial driveways, parking lots, & alleys 24 in. 24 in. 24 in. 24 in. 24 in.

Under streets, highways, roads, and public thoroughfares 24 in. 24 in. 24 in. 24 in. 24 in.

Airport runways and adjacent vehicular areas 18 in. 18 in. 18 in. 18 in. 18 in.

Note

Critical Underground Rules to Memorize:

Under Commercial Driveways & Streets: ALL wiring methods in Table 300.5—whether direct burial, PVC, or RMC—require a minimum of 24 inches of cover when subjected to vehicular traffic.

Warning Ribbon (NEC 300.5(D)(3)): Underground direct-buried service lateral conductors not encased in concrete must have a continuous, durable warning ribbon placed in the trench at least 12 inches (300 mm) above the conductors .

Raceway Seals (NEC 300.5(G)): Conduits that enter an interior conditioned building from underground exterior locations must be sealed with an approved duct seal compound to prevent moisture condensation and hazardous gas migration.