9.2 Nonmetallic-Sheathed (NM), Metal-Clad (MC) & Armored (AC) Cables

Idaho Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Orientation, NEC Navigation & Idaho Regulations

1.1 Idaho Journeyman Exam Format, PSI Logistics & Rapid NEC Navigation 1.2 Idaho Electrical Licensing Laws (Title 54, Ch. 10) & IDAPA 24.39.10 Requirements 1.3 Idaho Permits, Inspection Procedures & State-Specific NEC Amendments 1.4 NEC Article 90 Scope, Code Arrangement & Article 110 General Requirements

2 Chapter 2: Electrical Theory & Essential Math Calculations

2.1 Ohm's Law, Joule's Law & DC Circuit Calculations 2.2 Single-Phase & Three-Phase AC Fundamentals and Power Factor 2.3 DC & AC Voltage Drop Calculations and Conductor Sizing 2.4 NEC Article 100 Essential Definitions for Journeymen

3 Chapter 3: Conductors, Raceways & Box Sizing Calculations

3.1 Conductor Ampacity, Insulation Types & Terminal Temperature Ratings 3.2 Ambient Temperature Correction & Raceway Conductor Bundling Derating 3.3 Outlet & Junction Box Volume Fill Calculations (NEC 314.16) 3.4 Conduit Fill Calculations & Large Pull Box Sizing (NEC 314.28)

4 Chapter 4: Branch Circuits & Overcurrent Protection

4.1 Branch Circuit Ratings, Multiwire Circuits & Receptacle Placement 4.2 GFCI & AFCI Protection Mandates and Idaho Code Clarifications 4.3 Overcurrent Protective Devices, Standard Ratings & Small Conductor Rules 4.4 Feeder & Transformer Tap Rules (NEC 240.21)

5 Chapter 5: Feeders, Services & Outside Branch Circuits

5.1 Feeder Conductor Sizing, Neutral Calculations & Voltage Drop 5.2 Outside Branch Circuits, Feeders & Overhead/Underground Clearances 5.3 Service Drop, Service Lateral & Service-Entrance Sizing 5.4 Service Disconnecting Means, Emergency Disconnects & Surge Protection

6 Chapter 6: Load Calculations: Dwellings & Commercial

6.1 General Lighting, Small Appliance & Laundry Load Calculations 6.2 Standard Method Single-Family Dwelling Service Calculations (NEC 220 Part III) 6.3 Optional Method Single-Family & Multifamily Calculations (NEC 220 Part IV) 6.4 Commercial & Industrial Feeder/Service Calculations

7 Chapter 7: Grounding and Bonding: Systems & Electrodes

7.1 Grounding vs. Bonding Fundamentals & System Grounding 7.2 Grounding Electrodes & Grounding Electrode Conductor (GEC) Sizing 7.3 Main Bonding Jumpers, System Bonding Jumpers & Supply-Side Bonding

8 Chapter 8: Grounding and Bonding: Equipment & Enclosures

8.1 Equipment Grounding Conductors (EGC) Types, Installation & Sizing (Table 250.122) 8.2 Separately Derived Systems (SDS) Transformers & Generator Grounding 8.3 Service Enclosure Bonding, Concentric Knockouts & Effective Ground-Fault Path

9 Chapter 9: Wiring Methods, Cables & Conduits

9.1 General Requirements for Wiring Methods & Underground Installations (Article 300) 9.2 Nonmetallic-Sheathed (NM), Metal-Clad (MC) & Armored (AC) Cables 9.3 Metallic & Nonmetallic Raceway Systems (EMT, PVC, RMC, FMC) 9.4 Cabinets, Cutout Boxes & Outlet Box Installation Rules (Articles 312 & 314)

10 Chapter 10: Equipment for General Use: Devices, Luminaires & Appliances

10.1 Switches, Receptacles & Device Installation Standards (Articles 404 & 406) 10.2 Luminaire Clearances, Closet Rules & Lighting Track (Article 410) 10.3 Household Appliances & Fixed Electric Space Heating (Articles 422 & 424) 10.4 Generators, Transformer Overcurrent Protection & Panelboards

11 Chapter 11: Motors, Motor Circuits & Controllers

11.1 Motor Nameplate vs. Table FLC & Branch Circuit Conductor Sizing 11.2 Branch Circuit Short-Circuit & Ground-Fault Protection (Table 430.52) 11.3 Motor Overload Protection Sizing & Selection (NEC 430 Part III) 11.4 Motor Disconnects, Controllers & Multimotor Feeder Calculations

12 Chapter 12: Special Occupancies & Hazardous Locations

12.1 Hazardous (Classified) Locations: Classes, Divisions, Zones & Seals 12.2 Commercial Garages, Repair Hangars & Fuel Dispensing Facilities 12.3 Health Care Facilities: Patient Care Spaces & Redundant Grounding (Article 517) 12.4 Agricultural Buildings, Marinas, Boatyards & RV Parks

13 Chapter 13: Special Equipment, Emergency Systems & Renewable Energy

13.1 Swimming Pools, Spas, Hot Tubs & Equipotential Bonding (Article 680) 13.2 Electric Vehicle Supply Equipment (EVSE) Installation & Sizing (Article 625) 13.3 Solar Photovoltaic (PV) Systems & Energy Storage Systems (Articles 690 & 706) 13.4 Emergency, Standby Power Systems & Fire Pumps (Articles 700, 701, 702 & 695) 13.5 Fire Alarm, Optical Fiber & Power-Limited Circuits (Articles 760, 770 & 800)

9.2 Nonmetallic-Sheathed (NM), Metal-Clad (MC) & Armored (AC) Cables

Key Takeaways Explain This Topic AI

Type NM cable (Romex) is permitted in 1- and 2-family dwellings and Types III, IV, and V structures, but is prohibited in commercial drop ceilings, wet/damp locations, theatres, and commercial buildings of Type I/II construction unless enclosed in 15-minute thermal barriers.

Per NEC 334.80, conductors in Type NM cable are rated at 90°C for ampacity derating and temperature correction, but the final allowable ampacity is capped at the 60°C column of Table 310.16.

Type MC cable (Article 330) is approved for virtually all construction types and occupancies, requires support within 12 inches of boxes and every 6 feet along runs (10 ft for vertical runs), and utilizes either an insulated wire EGC or listed interlocking armor with bonding strip (MC-AP).

Type AC cable (BX - Article 320) utilizes flexible metallic armor with an internal 16 AWG bonding strip as its EGC, and NEC 320.40 strictly mandates listed anti-short insulating bushings ('red devils') at all terminations.

Bundling more than two NM cables through a single framing hole draftstopped or firestopped with insulation or sealant for more than 24 inches triggers ampacity derating per Table 310.15(C)(1).

Last updated: August 2026

9.2 Nonmetallic-Sheathed (NM), Metal-Clad (MC) & Armored (AC) Cables

Factory-manufactured multiconductor cable assemblies represent the primary wiring methods utilized in modern residential and light commercial construction. In the 2023 National Electrical Code, three distinct cable assemblies dominate the trade: Nonmetallic-Sheathed Cable (Type NM/NMC/NMS - Article 334) , Metal-Clad Cable (Type MC - Article 330) , and Armored Cable (Type AC - Article 320) .

While these cable types may appear similar in basic application, their structural composition, allowed building construction types, equipment grounding configurations, supporting rules, and ampacity derating procedures differ substantially.

1. Type NM, NMC & NMS Nonmetallic-Sheathed Cable (Article 334)

Commonly known by the trade name Romex , Nonmetallic-Sheathed Cable consists of insulated conductors enclosed within an overall nonmetallic outer jacket. +-----------------------------------------------------------------------------+

  • | NONMETALLIC-SHEATHED CABLE TYPES (334.2) |
  • | |
  • | [TYPE NM] ---> Flame-retardant, moisture-resistant nonmetallic sheath. |
  • | Permitted for EXPOSED and CONCEALED work in DRY locations.|
  • | |
  • | [TYPE NMC] ---> Flame-retardant, moisture-resistant, FUNGUS-resistant, |
  • | and CORROSION-resistant. Permitted in dry, moist, damp, |
  • | and corrosive locations (e.g., dairy barns). |
  • | |
  • | [TYPE NMS] ---> Hybrid cable containing power conductors alongside fiber- |
  • | optic / network communication signaling conductors. |
  • +-----------------------------------------------------------------------------+
  • Uses Permitted & Prohibited (NEC 334.10 & 334.12)

Permitted Uses (NEC 334.10) Prohibited Uses (NEC 334.12)

One- and two-family dwellings and their accessory structures In any dwelling or structure not classified as Type III, IV, or V (i.e., prohibited in Type I & II steel/concrete commercial high-rises unless concealed within 15-min thermal barriers)

Multifamily dwellings permitted to be of Types III, IV, and V construction As open runs in drop or suspended ceilings in commercial or other non-dwelling buildings

Other structures permitted to be Types III, IV, and V construction In damp or wet locations (Type NM is strictly dry only)

Exposed or concealed in normally dry locations In commercial garages , repair hangars, storage battery rooms, or hoistways

Installed in cable trays in industrial establishments (where listed) In theatres and places of assembly (except as permitted in 518.4)

Embedded in masonry plaster / dry adobe (Type NMC only) Embedded in poured concrete, aggregate, or direct buried in earth

The 60°C Ampacity Rule & 90°C Derating (NEC 334.80)

One of the most heavily tested topics on the journeyman exam is the dual-temperature ampacity calculation for Type NM cable:

Conductor Insulation Rating (90°C): Conductors inside modern NM-B cable are insulated with 90°C-rated material (e.g., THHN). This 90°C rating must be used as the starting ampacity when applying ambient temperature correction factors (Table 310.15(B)(1)) and bundle adjustment factors (Table 310.15(C)(1)).

Final Ampacity Limitation (60°C Column): Regardless of the calculation, the final allowable ampacity of Type NM cable shall not exceed that of a 60°C rated conductor in Table 310.16.

  • Final Allowable Ampacity = min(Ampacity_90°C x Adjustment Factors, Ampacity_60°C)
  • Bundling Rules (NEC 334.80)

Where more than two NM cables containing two or more current-carrying conductors are installed through the same wood framing hole that is sealed with thermal insulation, firestop caulk, or draftstop foam for a length exceeding 24 inches (600 mm) , the ampacity of each conductor must be derated per Table 310.15(C)(1) (e.g., 4–6 current-carrying conductors derated to 80%; 7–9 conductors derated to 70%).

2. Type MC Metal-Clad Cable Architecture & Applications (Article 330)

Type MC cable contains one or more insulated circuit conductors enclosed in an armor of interlocking metal tape (steel or aluminum) or a smooth or corrugated metallic tube . +-----------------------------------------------------------------------------+

  • | TYPE MC CABLE ANATOMY & EGC |
  • | |
  • | [STANDARD TYPE MC] |
  • | * Interlocking Aluminum or Steel Armor (Mechanical protection only) |
  • | * Insulated Phase Conductors (THHN / XHHW 90°C) |
  • | * Insulated or Bare Green Full-Size EQUIPMENT GROUNDING CONDUCTOR (EGC) |
  • | * Armor alone CANNOT serve as the equipment grounding path! |
  • | |
  • | [TYPE MC-AP / SMARTGROUND (ALL-PURPOSE)] |
  • | * Interlocking Aluminum Armor + Bare Aluminum Bonding Strip (in contact) |
  • | * Armor + Bonding Strip combination IS listed as an EGC (250.118(10)) |
  • | * No separate green wire needed for standard circuits! |
  • +-----------------------------------------------------------------------------+
  • Key MC Cable Requirements (NEC 330.10, 330.30)

Uses Permitted: Permitted in all occupancies, including commercial high-rises (Type I and II), industrial plants, cable trays, exposed or concealed, and in wet locations if jacketed with sunlight-resistant PVC and conductors are listed for wet locations.

Support Spacing (NEC 330.30(B)): Must be secured within 12 inches (300 mm) of every box, cabinet, or fitting, and supported at intervals not exceeding 6 feet (1.8 m) along the run.

Vertical Riser Support (NEC 330.30(E)): Vertical runs of MC cable with interlocked armor can be supported at intervals up to 10 feet (3.0 m) if listed for vertical support.

Unsupported Drops: Unsupported runs up to 3 feet (900 mm) are permitted from the last support to a luminaire or device where flexibility is necessary.

3. Type AC Armored Cable ("BX") & Anti-Short Bushings (Article 320)

Type AC cable consists of insulated conductors individual-wrapped in fibrous moisture-resistant paper, enclosed inside a flexible, interlocking galvanized steel or aluminum armor. +-----------------------------------------------------------------------------+

  • | TYPE AC CABLE ANATOMY & ANTI-SHORT BUSHING |
  • | |
  • | +---------------------------------------------------------------------+ |
  • | | Interlocking Armor | Paper Wrap | Conductors (THHN) | 16 AWG Bond | |
  • | +---------------------------------------------------------------------+ |
  • | \ / | |
  • | [ANTI-SHORT BUSHING ("RED DEVIL")] | |
  • | NEC 320.40 Mandate: Must be placed at every 16 AWG Aluminum or |
  • | termination between conductors and armor to Copper bonding strip|
  • | prevent sharp armor edges cutting insulation! in intimate contact |
  • | with outer armor. |
  • +-----------------------------------------------------------------------------+
  • Critical AC Cable Code Rules (Article 320)

Grounding Mechanism (NEC 250.118(8)): Type AC cable does NOT contain an insulated green ground wire . Instead, the outer interlocking armor in combination with the internal 16 AWG aluminum or copper bonding strip acts as the Equipment Grounding Conductor.

Mandatory Anti-Short Bushings (NEC 320.40): An approved anti-short bushing (red devil) or its equivalent must be inserted between the conductors and the outer armor at every cable termination. The connector must have an inspection window allowing the inspector to visually confirm the bushing is in place.

Uses Prohibited (NEC 320.12): Prohibited in damp/wet locations, direct burial in earth, commercial garages, theatres, places of assembly, and hazardous locations.

Support Spacing (NEC 320.30): Supported within 12 inches (300 mm) of boxes and every 4.5 feet (1.4 m) along runs.

4. Cable Securing, Supporting & Protection in Attics (320.23, 334.23, 334.30) +-----------------------------------------------------------------------------+

  • | ATTIC CABLE RUN PROTECTION RULES (NEC 320.23) |
  • | |
  • | ACCESSIBLE BY STAIRS OR PERMANENT LADDER: |
  • | * Cables across tops of floor joists or face of rafters within 7 ft of |
  • | floor MUST be protected by substantial GUARD STRIPS or RUNNING BOARDS. |
  • | |
  • | ACCESSIBLE BY SCUTTLE HOLE / HATCH ONLY: |
  • | * Guard strips required ONLY within 6 FEET (1.8 m) of the entrance hatch. |
  • | * Beyond 6 feet, cables can be run directly across joist tops. |
  • +-----------------------------------------------------------------------------+
  • Nonmetallic Box Support Exception (NEC 334.30(A) Ex. 1)

Where Type NM cable enters a single-gang nonmetallic outlet box without an internal cable clamp (maximum volume 100 cm³ / 6.1 in³), the cable must be secured within 8 inches (200 mm) of the box (rather than 12 inches), and the outer cable sheath must extend into the box at least 1/4 inch (6 mm) .

5. Master Cable Assembly Comparison Matrix

  • Technical Parameter Type NM (Romex) Type MC (Metal-Clad) Type AC (BX / Armored)
  • Governing NEC Article Article 334 Article 330 Article 320
  • Conductor Rating 90°C rated conductors 90°C rated conductors 90°C rated conductors

Final Ampacity Column 60°C column only (334.80) 75°C or 90°C column (terminal dependent) 75°C or 90°C column (terminal dependent)

Outer Armor / Jacket PVC nonmetallic sheath Interlocking Al/Steel or corrugated tube Interlocking galvanized steel or aluminum

Equipment Ground Path Bare/insulated copper EGC Dedicated EGC wire OR listed armor + strip Armor + internal 16 AWG bonding strip

  • Anti-Short Bushing Not applicable Recommended by MFR (not NEC mandated) MANDATORY by NEC 320.40 (Red Devil)
  • Distance to Box Support 12 in. (8 in. for non-clamp box) 12 in. (330.30) 12 in. (320.30)
  • Maximum Support Interval 4.5 feet (1.4 m) 6.0 feet (1.8 m) (10 ft vertical) 4.5 feet (1.4 m)
  • Drop Ceilings (Commercial) PROHIBITED (334.12(A)(2)) PERMITTED PERMITTED
  • Wet / Damp Locations Prohibited (except NMC in damp) Permitted if jacketed & listed PROHIBITED (320.12)