13.3 Vapour Compression & Vapour Absorption Refrigeration Systems
Coal India Management Trainee CIL MT
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: CIL MT Exam Overview & Coal Sector Landscape
1.1 CIL MT Exam Pattern, Marking Scheme & Strategy 1.2 Coal India Limited: Corporate Structure, Maharatna Status & Subsidiaries 1.3 Indian Coal Mining Sector, Energy Mix & Environmental Regulations
2 Chapter 2: Paper-I General Awareness, Polity & Current Affairs
2.1 Indian Constitution, Governance & Statutory Bodies 2.2 Indian Economy, Union Budget & Economic Planning 2.3 Indian Geography, Mineral Belts & Environmental Ecology 2.4 Modern Indian History, Freedom Struggle & Cultural Heritage 2.5 General Science: Physics, Chemistry & Biology Fundamentals 2.6 Inventions, Discoveries & Scientific-Technological Development 2.7 Uses of Internet, Computer Awareness & Digital Governance 2.8 National & International Organisations 2.9 Awards, Honours & Sports 2.10 Books & Authors, Important Monuments & Places of India 2.11 Ports, Power Plants & Infrastructure of India 2.12 Climate Change, SDGs, National Parks & Wildlife Sanctuaries 2.13 Flagship Government Programmes & Current Affairs Method 2.14 World Physical, Social & Economic Geography
3 Chapter 3: Paper-I Reasoning & Logical Ability
3.1 Series Completion, Coding-Decoding & Semantic Analogies 3.2 Syllogisms, Logical Deduction & Venn Diagrams 3.3 Seating Arrangements, Linear/Circular Alignments & Puzzles 3.4 Direction Sense, Blood Relations & Order/Ranking 3.5 Alphabetical & Alphanumeric Series 3.6 Statement & Conclusions, Statement & Arguments 3.7 Clocks & Calendars 3.8 Cubes, Dice & Figure Counting 3.9 Mirror Images, Water Images, Embedded Figures & Non-Verbal Series 3.10 Decision Making & Data Analysis in Reasoning
4 Chapter 4: Paper-I Numerical Ability & Quantitative Aptitude
4.1 Arithmetic Foundations: Percentages, Profit & Loss, Ratio & Proportion 4.2 Averages, Simple/Compound Interest, Alligations & Mixtures 4.3 Time & Work, Pipes & Cisterns, Time, Speed & Distance 4.4 Algebra, Mensuration, Geometry & Data Interpretation (DI) 4.5 Number System, LCM, HCF & Decimal Fractions 4.6 Surds, Indices & Simplification 4.7 Problems on Ages 4.8 Boats & Streams and Problems on Trains 4.9 Permutations & Combinations 4.10 Probability for Quantitative Aptitude
5 Chapter 5: Paper-I General English & Verbal Ability
5.1 English Grammar, Error Spotting & Sentence Correction 5.2 Vocabulary Building: Synonyms, Antonyms, Idioms & Phrases 5.3 Reading Comprehension, Cloze Tests & Para Jumbles 5.4 Fill in the Blanks, Cloze Passages & Sentence Completion 5.5 Jumbled Sentences & Sentence Improvement
6 Chapter 6: Paper-II Engineering Mathematics
6.1 Matrix Algebra, Rank & Systems of Linear Equations 6.2 Eigenvalues, Eigenvectors & the Cayley-Hamilton Theorem 6.3 Limits, Continuity, Differentiability & Mean Value Theorems 6.4 Maxima-Minima, Indeterminate Forms & Taylor Series 6.5 Definite, Improper, Double & Triple Integrals 6.6 Partial Derivatives, Total Derivative & Multivariable Optimisation 6.7 First-Order Differential Equations: Linear & Non-Linear 6.8 Higher-Order Linear Differential Equations & Engineering Applications 6.9 Laplace Transforms & Transfer-Function Methods 6.10 Probability, Conditional Probability & Bayes' Theorem 6.11 Random Variables, Distributions & Descriptive Statistics 6.12 Numerical Methods: Root Finding, Integration & ODE Solvers
7 Chapter 7: Paper-II Engineering Mechanics & Statics-Dynamics
7.1 Force Systems, Coplanar Equilibrium & Lami's Theorem 7.2 Plane Trusses, Friction Mechanics & Screws/Wedges 7.3 Centroids, Center of Gravity & Moment of Inertia 7.4 Kinematics, Kinetics of Particles & Rigid Body Dynamics 7.5 Virtual Work & Lagrange's Equation 7.6 Rolling Friction, Belt-Pulley Drives, Brakes, Clutches & Vehicle Dynamics
8 Chapter 8: Paper-II Mechanics of Materials & Structural Integrity
8.1 Simple Stresses, Strains, Elastic Moduli & Thermal Stresses 8.2 Principal Stresses, Strain Energy & Mohr's Circle 8.3 Shear Force & Bending Moment Diagrams, Beam Bending & Shear Stresses 8.4 Torsion of Circular Shafts, Springs & Column Buckling 8.5 Thin Cylinders, Spheres & Thick-Walled Pressure Vessels 8.6 Deflection of Beams: Double Integration, Macaulay & Moment-Area 8.7 Shear Centre & Unsymmetrical Bending 8.8 Strain Gauges, Rosettes & Experimental Stress Analysis 8.9 Mechanical Testing: Universal Testing Machine, Hardness & Impact
9 Chapter 9: Paper-II Theory of Machines & Mechanical Vibrations
9.1 Simple Mechanisms, Kinematic Inversions & Velocity/Acceleration Diagrams 9.2 Cams & Followers, Toothed Gearing & Epicyclic Gear Trains 9.3 Flywheels, Centrifugal/Inertia Governors & Rotor Balancing 9.4 Free, Damped & Forced Single-Degree-of-Freedom Vibrations 9.5 Gyroscopic Couple & Gyroscopic Effects
10 Chapter 10: Paper-II Machine Design & Failure Theories
10.1 Static Failure Theories & Variable/Fatigue Loading 10.2 Design of Threaded Fasteners, Welded & Riveted Joints 10.3 Design of Shafts, Keys, Couplings & Rolling/Sliding Bearings 10.4 Design of Spur, Helical, Bevel & Worm Gears 10.5 Design of Helical, Leaf & Torsion Springs 10.6 Design of Brakes & Clutches: Energy, Lining Pressure & Heat
11 Chapter 11: Paper-II Fluid Mechanics & Hydraulic Machinery
11.1 Fluid Properties, Hydrostatic Forces & Buoyancy 11.2 Fluid Kinematics, Continuity & Bernoulli's Equation 11.3 Viscous Flow in Pipes, Boundary Layer & Minor Losses 11.4 Hydraulic Turbines, Centrifugal & Reciprocating Pumps 11.5 Dimensional Analysis, Similitude & Model Testing 11.6 Control-Volume Analysis: Continuity, Momentum & Energy
12 Chapter 12: Paper-II Thermodynamics, Thermal Cycles & Turbomachinery
12.1 Fundamental Concepts, First & Second Laws of Thermodynamics 12.2 Entropy, Availability, Exergy & Properties of Pure Substances 12.3 Air-Standard Gas Power Cycles: Otto, Diesel, Dual & Brayton 12.4 Vapour Power Cycles: Ideal, Reheat & Regenerative Rankine Cycles 12.5 Thermodynamic Relations: Maxwell, Clausius-Clapeyron & Joule-Thomson 12.6 Behaviour of Ideal & Real Gases and Equations of State 12.7 Air & Gas Compressors: Reciprocating, Rotary & Multi-Stage 12.8 Steam & Gas Turbines: Impulse, Reaction & Velocity Diagrams
13 Chapter 13: Paper-II Heat Transfer, Refrigeration & Air Conditioning
13.1 Steady & Unsteady Conduction, Extended Surfaces (Fins) 13.2 Forced/Natural Convection, Radiation & Heat Exchanger LMTD/NTU 13.3 Vapour Compression & Vapour Absorption Refrigeration Systems 13.4 Psychrometric Properties, Processes & Air Conditioning Systems 13.5 Gas Refrigeration, Heat Pump Cycles & Cryogenics
14 Chapter 14: Paper-II Materials Science, Metallurgy & Manufacturing Technology
14.1 Crystal Structures, Phase Diagrams & Iron-Iron Carbide Equilibrium 14.2 Heat Treatment Processes & Engineering Alloy Steels 14.3 Casting Processes, Metal Forming & Welding Metallurgy 14.4 Metal Cutting Mechanics, Tool Life & Machine Tools 14.5 Plastic Deformation, Yield Criteria & Load Estimation in Bulk Forming 14.6 Sheet Metal Forming: Shearing, Bending & Deep Drawing 14.7 Powder Metallurgy 14.8 Brazing, Soldering & Adhesive Bonding 14.9 Non-Traditional Machining: EDM, ECM, USM, AJM, LBM & EBM 14.10 Abrasive Machining, Grinding & Superfinishing 14.11 Principles of Work Holding, Jigs & Fixtures 14.12 Economics of Machining & Tool Life Optimisation
15 Chapter 15: Paper-II Metrology, Quality Control & Industrial Engineering / OR
15.1 Limits, Fits, Tolerances, Gauges & Surface Metrology 15.2 Production Planning, Forecasting & Inventory Control Models 15.3 Operations Research: Linear Programming & Transportation/Assignment 15.4 Project Management: CPM, PERT, Network Analysis & Crashing 15.5 Comparators & Interferometry 15.6 Coordinate Measuring Machines & Machine Tool Alignment Testing 15.7 Computer Integrated Manufacturing: CAD/CAM & Integration Tools 15.8 NC/CNC Machines & CNC Part Programming 15.9 Material Requirements Planning, Scheduling & Sequencing 15.10 Queuing Theory & Simple Queuing Models 15.11 Network Flow Models: Shortest Route, Maximal Flow & Spanning Tree
13.3 Vapour Compression & Vapour Absorption Refrigeration Systems
Key Takeaways Explain This Topic AI
The standard Vapour Compression Refrigeration System (VCRS) operates on four state changes: isentropic compression (1-2), isobaric condensation (2-3), isenthalpic throttling expansion (3-4, h3=h4), and isobaric evaporation (4-1), with COP = (h1-h4)/(h2-h1).
Operating conditions dictate performance: liquid subcooling at condenser exit always increases refrigeration effect RE and COP; suction vapor superheating in evaporator increases RE but also compressor work Wc; decreasing evaporator temperature drastically reduces COP and increases compressor displacement volume.
One Ton of Refrigeration (1 TR) is defined as the heat extraction rate of 3.517 kW (210 kJ/min or 12,000 Btu/hr), equivalent to the latent heat rate required to freeze 1 short ton of water at 0°C into ice at 0°C in 24 hours.
Multi-stage compression with intermediate flash chambers and intercooling minimizes power consumption and prevents excessive discharge temperatures when total pressure ratio r_p > 6 to 8, with optimum intermediate pressure P_i = sqrt(P_e * P_c).
Vapour Absorption Systems (VARS) replace the mechanical compressor with an absorber, solution pump, and generator to utilize low-grade thermal energy; maximum theoretical COP equals eta_Carnot_HE * COP_Carnot_Refrig = [(T_g - T_a)/T_g] * [T_e/(T_a - T_e)].
Last updated: August 2026
Vapour Compression & Vapour Absorption Refrigeration Systems
Refrigeration is the process of removing thermal energy from a low-temperature reservoir and discharging it to a higher-temperature reservoir through the input of mechanical or thermal work. In modern industrial mining operations, massive refrigeration systems provide chilling for underground mine ventilation air (counteracting rock geothermal gradients and equipment heat loads), industrial chiller plants for heavy equipment lubricants, and cooling systems in Coal Handling Plants (CHP).
1. Thermodynamic Fundamentals & The Ton of Refrigeration
A refrigerator operates on a reversed thermodynamic cycle. The performance index is the Coefficient of Performance (COP) : COP Ref = Desired Refrigerating Effect ( Q L ) Net Work Input ( W net ) = Q L Q H − Q L \text{COP}_{\text{Ref}} = \frac{\text{Desired Refrigerating Effect } (Q_L)}{\text{Net Work Input } (W_{\text{net}})} = \frac{Q_L}{Q_H - Q_L} COP Ref = Net Work Input ( W net ) Desired Refrigerating Effect ( Q L ) = Q H − Q L Q L
For a Reversed Carnot Cycle operating between low temperature T L T_L T L and high temperature T H T_H T H (in Kelvin): COP Carnot, Ref = T L T H − T L \text{COP}_{\text{Carnot, Ref}} = \frac{T_L}{T_H - T_L} COP Carnot, Ref = T H − T L T L COP Carnot, Heat Pump = T H T H − T L = COP Carnot, Ref + 1 \text{COP}_{\text{Carnot, Heat Pump}} = \frac{T_H}{T_H - T_L} = \text{COP}_{\text{Carnot, Ref}} + 1 COP Carnot, Heat Pump = T H − T L T H = COP Carnot, Ref + 1
The Ton of Refrigeration (TR)
The commercial unit of cooling capacity is the Ton of Refrigeration (TR) , defined as the steady rate of heat removal required to freeze 1 short ton ( 2000 lb = 907.185 kg 2000\text{ lb} = 907.185\text{ kg} 2000 lb = 907.185 kg ) of pure water at 0 ∘ C 0^{\circ}\text{C} 0 ∘ C into ice at 0 ∘ C 0^{\circ}\text{C} 0 ∘ C in exactly 24 hours: Latent heat of fusion of ice h s f = 333.55 kJ/kg \text{Latent heat of fusion of ice } h_{sf} = 333.55 \ \text{kJ/kg} Latent heat of fusion of ice h s f = 333.55 kJ/kg 1 TR = 907.185 kg × 333.55 kJ/kg 24 × 3600 s = 302 , 601 kJ 86 , 400 s = 3.502 kW ( Standard Definition: 3.51685 ≈ 3.517 kW ) 1 \ \text{TR} = \frac{907.185 \ \text{kg} \times 333.55 \ \text{kJ/kg}}{24 \times 3600 \ \text{s}} = \frac{302,601 \ \text{kJ}}{86,400 \ \text{s}} = 3.502 \ \text{kW} \quad (\text{Standard Definition: } 3.51685 \approx 3.517 \ \text{kW}) 1 TR = 24 × 3600 s 907.185 kg × 333.55 kJ/kg = 86 , 400 s 302 , 601 kJ = 3.502 kW ( Standard Definition: 3.51685 ≈ 3.517 kW ) 1 TR = 3.517 kW = 210 kJ/min = 12 , 000 Btu/hr 1 \ \text{TR} = 3.517 \ \text{kW} = 210 \ \text{kJ/min} = 12,000 \ \text{Btu/hr} 1 TR = 3.517 kW = 210 kJ/min = 12 , 000 Btu/hr
2. Standard Vapour Compression Refrigeration System (VCRS)
The Vapour Compression Refrigeration System (VCRS) is the most widely utilized refrigeration cycle. It eliminates the impractical wet compression and expansion cylinder expansion work of the reversed Carnot cycle by employing dry isentropic compression and an isenthalpic throttling expansion valve. +-----------------------------------------------------------------------------------------+
- | STANDARD VCRS SCHEMATIC & CYCLE DIAGRAMS |
- | |
- | SCHEMATIC: |
- | +------------------- [ CONDENSER ] <-------------------+ |
- | | (Q_out = q_c) | |
- | v | (State 2: Super-|
- | (State 3: Sat Liquid) | heated vapor) |
- | [ EXPANSION VALVE ] [ COMPRESSOR ] |
- | (h3 = h4 Throttling) (W_in = W_c) |
- | | ^ |
- | v | (State 1: Sat |
- | +------------------> [ EVAPORATOR ] --------------------+ vapor) |
- | (Q_in = RE) |
- | |
- | PRESSURE-ENTHALPY (P-h) DIAGRAM: TEMPERATURE-ENTROPY (T-s) DIAGRAM: |
- | P ^ T ^ |
- | | 2-3: Condenser | 2-3: Condenser |
- | Pc |--------* 3 <=========== 2 (Superheated) | * 3 <========= 2 |
- | | /| \ | / | | (s1 = s2) |
- | | / | \ | / | | |
- | Pe |-----*--* 4 -----------> 1 * | / * 4 -------> * 1 |
- | | / | 4-1: Evaporator | / \ |
- | +---+----+--------------------> h +-----+--------------------> s |
- | h3=h4 h1 h2 |
- +-----------------------------------------------------------------------------------------+
- The Four Thermodynamic Processes
Process 1-2 (Isentropic Compression): Saturated vapor at evaporator pressure P e P_e P e is compressed isentropically ( s 1 = s 2 s_1 = s_2 s 1 = s 2 ) in a mechanical compressor to superheated vapor at condenser pressure P c P_c P c . Work input: w c = h 2 − h 1 w_c = h_2 - h_1 w c = h 2 − h 1 .
Process 2-3 (Isobaric Heat Rejection): Superheated refrigerant vapor is desuperheated, condensed to saturated liquid, and subcooled inside the condenser at constant pressure P c P_c P c . Heat rejected: q c = h 2 − h 3 q_c = h_2 - h_3 q c = h 2 − h 3 .
Process 3-4 (Isenthalpic Throttling Expansion): Saturated liquid expands irreversibly through a throttling capillary tube or thermostatic expansion valve (TXV) from P c P_c P c down to P e P_e P e . Throttling is adiabatic with zero work output: h 4 = h 3 h_4 = h_3 h 4 = h 3 .
Process 4-1 (Isobaric Evaporation): Low-quality liquid-vapor mixture absorbs thermal energy from the cold refrigerated space at constant pressure P e P_e P e until it reaches saturated vapor (state 1). Refrigerating effect: RE = q e = h 1 − h 4 = h 1 − h 3 \text{RE} = q_e = h_1 - h_4 = h_1 - h_3 RE = q e = h 1 − h 4 = h 1 − h 3 .
Mathematical Formulation of Performance Refrigerating Effect (RE) = h 1 − h 4 = h 1 − h 3 ( kJ/kg ) \text{Refrigerating Effect (RE)} = h_1 - h_4 = h_1 - h_3 \quad (\text{kJ/kg}) Refrigerating Effect (RE) = h 1 − h 4 = h 1 − h 3 ( kJ/kg ) Compressor Work ( w c ) = h 2 − h 1 ( kJ/kg ) \text{Compressor Work } (w_c) = h_2 - h_1 \quad (\text{kJ/kg}) Compressor Work ( w c ) = h 2 − h 1 ( kJ/kg ) Coefficient of Performance (COP) = RE w c = h 1 − h 4 h 2 − h 1 = h 1 − h 3 h 2 − h 1 \text{Coefficient of Performance (COP)} = \frac{\text{RE}}{w_c} = \frac{h_1 - h_4}{h_2 - h_1} = \frac{h_1 - h_3}{h_2 - h_1} Coefficient of Performance (COP) = w c RE = h 2 − h 1 h 1 − h 4 = h 2 − h 1 h 1 − h 3 Refrigerant Mass Flow Rate ( m ˙ r ) = Plant Capacity (kW) RE = Plant Capacity (kW) h 1 − h 3 ( kg/s ) \text{Refrigerant Mass Flow Rate } (\dot{m}_r) = \frac{\text{Plant Capacity (kW)}}{\text{RE}} = \frac{\text{Plant Capacity (kW)}}{h_1 - h_3} \quad (\text{kg/s}) Refrigerant Mass Flow Rate ( m ˙ r ) = RE Plant Capacity (kW) = h 1 − h 3 Plant Capacity (kW) ( kg/s ) Compressor Power Input ( P ) = m ˙ r w c = m ˙ r ( h 2 − h 1 ) ( kW ) \text{Compressor Power Input } (P) = \dot{m}_r w_c = \dot{m}_r (h_2 - h_1) \quad (\text{kW}) Compressor Power Input ( P ) = m ˙ r w c = m ˙ r ( h 2 − h 1 ) ( kW ) Heat Rejection Ratio (HRR) = q c RE = h 2 − h 3 h 1 − h 3 = 1 + 1 COP \text{Heat Rejection Ratio (HRR)} = \frac{q_c}{\text{RE}} = \frac{h_2 - h_3}{h_1 - h_3} = 1 + \frac{1}{\text{COP}} Heat Rejection Ratio (HRR) = RE q c = h 1 − h 3 h 2 − h 3 = 1 + COP 1
3. Influence of Operating Parameters on VCRS Performance +-----------------------------------------------------------------------------------------+
- | VCRS OPERATING PARAMETER SENSITIVITY |
- | |
- | Parameter Modification RE (kJ/kg) W_c (kJ/kg) COP V_piston |
- | -------------------------- ------------- ------------- --------- --------- |
- | 1. Subcooling of Liquid Increases Unchanged Increases Unchanged |
- | at Condenser Exit (3->3') |
- | 2. Superheating Vapor Increases Increases Varies Increases |
- | in Evaporator (1->1') (R134a +) |
- | 3. Decreasing Evaporator Decreases Increases Decreases Increases |
- | Temperature (Te drops) sharply severely greatly |
- | 4. Increasing Condenser Decreases Increases Decreases Slight |
- | Temperature (Tc rises) moderately increase |
+-----------------------------------------------------------------------------------------+ +-----------------------------------------------------------------------------------------+
- | EFFECTS ON P-h DIAGRAM: SUBCOOLING & SUPERHEAT |
- | |
- | P ^ |
- | | 3' 3 2 2' |
- | Pc |-----------*<----*===================================*=====>* |
- | | /| | \ \ |
- | | / | | \ \ |
- | Pe |--------*--*<----*--------------------------------------*----->* |
- | | / 4' 4 1 1' |
- | +------+----+-----+--------------------------------------+------+--> h |
- | |<-Delta_h->| |<-Dh->| |
- | Subcooling Gain (RE increases) Superheating Gain |
- +-----------------------------------------------------------------------------------------+
- 1. Subcooling of Liquid Refrigerant ( 3 → 3 ′ 3 \to 3' 3 → 3 ′ )
Cooling liquid refrigerant below saturation temperature before throttling ( T 3 ′ < T sat ( P c ) T_{3'} < T_{\text{sat}}(P_c) T 3 ′ < T sat ( P c ) ):
State 4 shifts left to 4 ′ 4' 4 ′ ( h 4 ′ < h 4 h_{4'} < h_4 h 4 ′ < h 4 ).
Refrigerating effect increases: RE ′ = h 1 − h 4 ′ > RE \text{RE}' = h_1 - h_{4'} > \text{RE} RE ′ = h 1 − h 4 ′ > RE .
Compressor work w c = h 2 − h 1 w_c = h_2 - h_1 w c = h 2 − h 1 is unaffected.
COP \text{COP} COP always increases .
2. Superheating of Suction Vapor ( 1 → 1 ′ 1 \to 1' 1 → 1 ′ )
Heating vapor above saturation temperature prior to compression ( T 1 ′ > T sat ( P e ) T_{1'} > T_{\text{sat}}(P_e) T 1 ′ > T sat ( P e ) ):
Useful Superheating (inside refrigerated space): Increases RE \text{RE} RE ( h 1 ′ − h 3 > h 1 − h 3 h_{1'} - h_3 > h_1 - h_3 h 1 ′ − h 3 > h 1 − h 3 ) while increasing w c = h 2 ′ − h 1 ′ w_c = h_{2'} - h_{1'} w c = h 2 ′ − h 1 ′ due to diverging constant entropy lines at higher temperatures. For R-134a and R-12, COP increases slightly; for Ammonia (R-717), COP decreases.
Non-Useful Superheating (in connecting pipework outside cold room): RE \text{RE} RE remains unchanged while w c w_c w c increases, leading to a decrease in COP .
3. Evaporator Temperature Drop
Lowering T e T_e T e decreases suction pressure P e P_e P e :
Specific volume v 1 v_1 v 1 at compressor suction increases exponentially ( v 1 ∝ 1 / P e v_1 \propto 1/P_e v 1 ∝ 1/ P e ).
Compressor volumetric efficiency drops: η v = 1 + c − c ( P c P e ) 1 / γ \eta_v = 1 + c - c\left(\frac{P_c}{P_e}\right)^{1/\gamma} η v = 1 + c − c ( P e P c ) 1/ γ .
Mass flow rate delivered by a fixed displacement compressor drops drastically.
4. Multi-Stage Compression with Flash Intercooling
When the overall pressure ratio r p = P c / P e r_p = P_c / P_e r p = P c / P e exceeds 6 to 8 6\text{ to }8 6 to 8 (e.g., low-temperature blast freezing or deep-shaft mine cooling), single-stage VCRS suffers from:
Severe deterioration in compressor volumetric efficiency.
Extremely high compressor discharge temperatures ( T 2 > 130 ∘ C T_2 > 130^{\circ}\text{C} T 2 > 13 0 ∘ C ), which break down lubricating oils and cause valve carbonization.
Large throttling irreversibility losses. +-----------------------------------------------------------------------------------------+
- | TWO-STAGE COMPRESSION WITH FLASH INTERCOOLER |
- | |
- | SCHEMATIC: |
- | |
- | +---------------- [ CONDENSER (Pc) ] <----------------+ |
- | | | |
- | v | (HP Compressor) |
- | [ EXPANSION VALVE 1 ] | |
- | | | |
- | v (State 5: Flash Liquid) (State 3: Saturated) | |
- | +-> [ FLASH CHAMBER (Pi) ] -----------> [ INTERCOOLER ] ------+ |
- | | | ^ |
- | | v | (LP Compressor) |
- | | [ EXPANSION VALVE 2 ] | |
- | | | | |
- | | v | |
- | +-------+----------------> [ EVAPORATOR (Pe) ]+ |
- | |
- | Optimum Intermediate Pressure: P_i = sqrt( P_e * P_c ) |
- +-----------------------------------------------------------------------------------------+
- Optimum Intermediate Pressure ( P i P_i P i )
To minimize total compressor power input for a two-stage system with perfect intercooling between stages: P i = P e P c P_i = \sqrt{P_e P_c} P i = P e P c Pressure Ratio per Stage: r p , 1 = r p , 2 = P c P e \text{Pressure Ratio per Stage: } \quad r_{p,1} = r_{p,2} = \sqrt{\frac{P_c}{P_e}} Pressure Ratio per Stage: r p , 1 = r p , 2 = P e P c
5. Vapour Absorption Refrigeration System (VARS)
The Vapour Absorption Refrigeration System (VARS) replaces the power-hungry mechanical compressor of the VCRS with a thermal compressor assembly comprising an Absorber, Solution Pump, Generator, and Pressure Reducing Valve. It is driven primarily by low-grade thermal waste heat (steam from mine boilers, exhaust gas from diesel generators, or solar collectors). +-----------------------------------------------------------------------------------------+
- | VAPOUR ABSORPTION SYSTEM (VARS) SCHEMATIC |
- | |
- | Heat In (Q_g at T_g) |
- | v |
- | +-------------------+ |
- | | GENERATOR | |
- | | (Vapor Separated) | |
- | +-------------------+ |
- | | High-P Vapor ^ Weak Solution (Rich in Refrigerant) |
- | v | |
- | [ CONDENSER (Pc) ] [ SOLUTION PUMP ] (Work input W_p ~ 0) |
- | | ^ |
- | v | |
- | [ EXPANSION VALVE ] +-------------------+ |
- | | | ABSORBER | ---> Heat Out (Q_a at T_a) |
- | v | (Vapor Absorbed) | |
- | [ EVAPORATOR (Pe) ]-> +-------------------+ |
- | ^ |
- | | |
- | Cooling Load (Q_e at T_e) |
- +-----------------------------------------------------------------------------------------+
- Maximum Theoretical COP of VARS (Carnot Analysis)
A VARS can be modeled as a combined system: a reversible Carnot Heat Engine operating between generator temperature T g T_g T g and ambient/absorber temperature T a T_a T a , producing mechanical work W W W that directly drives a reversible Carnot Refrigerator operating between T e T_e T e and T a T_a T a . η Carnot, HE = W Q g = T g − T a T g \eta_{\text{Carnot, HE}} = \frac{W}{Q_g} = \frac{T_g - T_a}{T_g} η Carnot, HE = Q g W = T g T g − T a COP Carnot, Ref = Q e W = T e T a − T e \text{COP}_{\text{Carnot, Ref}} = \frac{Q_e}{W} = \frac{T_e}{T_a - T_e} COP Carnot, Ref = W Q e = T a − T e T e COP max, VARS = Q e Q g = η Carnot, HE × COP Carnot, Ref = ( T g − T a T g ) ( T e T a − T e ) \text{COP}_{\text{max, VARS}} = \frac{Q_e}{Q_g} = \eta_{\text{Carnot, HE}} \times \text{COP}_{\text{Carnot, Ref}} = \left(\frac{T_g - T_a}{T_g}\right) \left(\frac{T_e}{T_a - T_e}\right) COP max, VARS = Q g Q e = η Carnot, HE × COP Carnot, Ref = ( T g T g − T a ) ( T a − T e T e )
Where all temperatures ( T g , T a , T e T_g, T_a, T_e T g , T a , T e ) must be expressed in Kelvin .
Comparison of Commercial Absorption Systems
Feature Aqua-Ammonia ( NH 3 -H 2 O \text{NH}_3\text{-H}_2\text{O} NH 3 -H 2 O ) System Lithium Bromide-Water ( LiBr-H 2 O \text{LiBr-H}_2\text{O} LiBr-H 2 O ) System
- Refrigerant Ammonia ( NH 3 \text{NH}_3 NH 3 ) Water ( H 2 O \text{H}_2\text{O} H 2 O )
- Absorbent Water ( H 2 O \text{H}_2\text{O} H 2 O ) Lithium Bromide Salt ( LiBr \text{LiBr} LiBr )
Volatility of Absorbent Volatile (water evaporates with NH 3 \text{NH}_3 NH 3 ) Completely non-volatile (salt does not evaporate)
Rectifier / Analyzer Mandatory (to remove water trace vapor) Not required (pure water vapor leaves generator)
Operating Pressure High positive pressures ( 10 – 18 bar 10\text{--}18\text{ bar} 10 – 18 bar ) Deep vacuum ( 0.008 – 0.08 bar 0.008\text{--}0.08\text{ bar} 0.008 – 0.08 bar )
Minimum Temperature Sub-zero capability down to − 40 ∘ C -40^{\circ}\text{C} − 4 0 ∘ C Limited to T e > 0 ∘ C T_e > 0^{\circ}\text{C} T e > 0 ∘ C (water freezes at 0 ∘ C 0^{\circ}\text{C} 0 ∘ C )
Primary Application Industrial freezing & low-temp mining cold stores Central commercial Air Conditioning systems
The Three-Fluid Electrolux (Platen-Munters) System
Designed for domestic refrigerators where electricity or mechanical pumps are unavailable:
Working Fluids: Ammonia (Refrigerant), Water (Absorbent), Hydrogen (Inert Auxiliary Gas).
Eliminates Solution Pump: Operates at uniform total pressure ( P total ≈ 15 bar P_{\text{total}} \approx 15\text{ bar} P total ≈ 15 bar ) throughout the system.
Evaporator Principle: Dalton's law of partial pressures: P total = P NH 3 + P H 2 P_{\text{total}} = P_{\text{NH}_3} + P_{\text{H}_2} P total = P NH 3 + P H 2 . Hydrogen gas introduced into the evaporator lowers the partial pressure of ammonia ( P NH 3 ≈ 2 bar P_{\text{NH}_3} \approx 2\text{ bar} P NH 3 ≈ 2 bar ), allowing liquid ammonia to evaporate at low temperature ( − 15 ∘ C -15^{\circ}\text{C} − 1 5 ∘ C ) without requiring a mechanical throttling valve or compressor.
Zero Moving Parts: Circulation occurs entirely via natural thermosiphon buoyancy.
- 6. Refrigerant Chemistry, Nomenclature & Environmental Protocols
- ASHRAE Standard Refrigerant Nomenclature
For halogenated hydrocarbons with chemical formula C m H n F p Cl q \text{C}_m \text{H}_n \text{F}_p \text{Cl}_q C m H n F p Cl q where 2 m + 2 = n + p + q 2m + 2 = n + p + q 2 m + 2 = n + p + q : Refrigerant Number: R- ( m − 1 ) ( n + 1 ) ( p ) \text{Refrigerant Number: } \quad \text{R-}(m-1)(n+1)(p) Refrigerant Number: R- ( m − 1 ) ( n + 1 ) ( p )
Inorganic Compounds: Numbered as R- ( 700 + Molecular Weight ) \text{R-}(700 + \text{Molecular Weight}) R- ( 700 + Molecular Weight ) :
- Ammonia ( NH 3 \text{NH}_3 NH 3 , M = 17 M = 17 M = 17 ): R-717 \text{R-717} R-717
- Water ( H 2 O \text{H}_2\text{O} H 2 O , M = 18 M = 18 M = 18 ): R-718 \text{R-718} R-718
- Carbon Dioxide ( CO 2 \text{CO}_2 CO 2 , M = 44 M = 44 M = 44 ): R-744 \text{R-744} R-744
- Air ( M = 29 M = 29 M = 29 ): R-729 \text{R-729} R-729
- Environmental Impact Metrics & Global Treaties
Ozone Depletion Potential (ODP): Relative index measuring damage to the stratospheric ozone layer compared to trichlorofluoromethane ( R-11 \text{R-11} R-11 , baseline ODP = 1.0 \text{ODP} = 1.0 ODP = 1.0 ).
Global Warming Potential (GWP): Index measuring thermal radiation trapped in the atmosphere over 100 years relative to carbon dioxide ( CO 2 \text{CO}_2 CO 2 , baseline GWP = 1.0 \text{GWP} = 1.0 GWP = 1.0 ). +-----------------------------------------------------------------------------------------+
- | REFRIGERANT ENVIRONMENTAL CLASSIFICATION |
- | |
- | Class Examples ODP GWP (100-yr) Regulatory Status |
- | --------- ---------------- -------- ------------- ------------------------ |
- | CFC R-11, R-12, R-115 0.6 - 1.0 4,500 - 10,000 BANNED (Montreal Protocol) |
- | HCFC R-22, R-123 0.02-0.05 700 - 1,800 PHASED OUT (Montreal) |
- | HFC R-134a, R-410A 0.00 1,300 - 4,000 PHASE DOWN (Kigali Amend.) |
- | HFO R-1234yf, R-1234ze 0.00 < 1 Modern Low-GWP Standard |
- | Natural R-290 (Propane) 0.00 3 Eco-friendly Hydrocarbons |
- | Refrigerants R-600a (Isobutane) 0.00 3 Zero ODP, Ultra-low GWP |
- | R-717 (Ammonia) 0.00 0 High efficiency, toxic |
- | R-744 (CO2) 0.00 1 Transcritical cycle |
- +-----------------------------------------------------------------------------------------+
- 7. Step-by-Step Worked Problems: VCRS Cycle & VARS Thermal Efficiency
- Worked Example 1: Standard Industrial VCRS Chiller Performance
A 10 TR R-134a industrial water chilling plant operates on a standard VCRS cycle between an evaporator temperature of − 10 ∘ C -10^{\circ}\text{C} − 1 0 ∘ C ( P e = 2.01 bar P_e = 2.01\text{ bar} P e = 2.01 bar ) and a condenser temperature of + 40 ∘ C +40^{\circ}\text{C} + 4 0 ∘ C ( P c = 10.17 bar P_c = 10.17\text{ bar} P c = 10.17 bar ). Saturated vapor leaves the evaporator and saturated liquid leaves the condenser. The refrigerant enthalpy values are:
Saturated vapor at − 10 ∘ C -10^{\circ}\text{C} − 1 0 ∘ C : h 1 = 392.8 kJ/kg h_1 = 392.8\text{ kJ/kg} h 1 = 392.8 kJ/kg , s 1 = 1.733 kJ/kg ⋅ K s_1 = 1.733\text{ kJ/kg}\cdot\text{K} s 1 = 1.733 kJ/kg ⋅ K
Superheated vapor after isentropic compression at P c P_c P c : h 2 = 425.8 kJ/kg h_2 = 425.8\text{ kJ/kg} h 2 = 425.8 kJ/kg
Saturated liquid at + 40 ∘ C +40^{\circ}\text{C} + 4 0 ∘ C : h 3 = 256.4 kJ/kg h_3 = 256.4\text{ kJ/kg} h 3 = 256.4 kJ/kg
Calculate the COP, mass flow rate of refrigerant (kg/s), and compressor power input (kW). +-----------------------------------------------------------------------------------------+
- | VCRS CHILLER CALCULATION STEPS |
- | |
- | STEP 1: Identify Enthalpies at Key State Points |
- | h1 = 392.8 kJ/kg (Evaporator Exit) |
- | h2 = 425.8 kJ/kg (Compressor Exit) |
- | h3 = 256.4 kJ/kg (Condenser Exit) |
- | h4 = h3 = 256.4 kJ/kg (Expansion Valve Exit, Isenthalpic) |
- | |
- | STEP 2: Calculate Refrigeration Effect (RE) and Compressor Work (Wc) |
- | RE = h1 - h4 = 392.8 - 256.4 = 136.4 kJ/kg |
- | w_c = h2 - h1 = 425.8 - 392.8 = 33.0 kJ/kg |
- | |
- | STEP 3: Calculate Coefficient of Performance (COP) |
- | COP = RE / w_c = 136.4 / 33.0 = 4.133 |
- | |
- | STEP 4: Calculate Total Plant Capacity in kW |
- | Capacity = 10 TR * 3.517 kW/TR = 35.17 kW |
- | |
- | STEP 5: Calculate Refrigerant Mass Flow Rate |
- | m_dot_r = Capacity / RE = 35.17 kW / 136.4 kJ/kg = 0.2578 kg/s |
- | |
- | STEP 6: Calculate Compressor Power Input |
- | Power = m_dot_r * w_c = 0.2578 kg/s * 33.0 kJ/kg = 8.507 kW |
- +-----------------------------------------------------------------------------------------+