14.2 Fixed Fire-Extinguishing Systems: CO2, Water Mist & Hi-Expansion Foam
DG Shipping General Purpose Rating Final Exam India
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Introduction to Shipping, Ship Structure & Organization
1.1 Maritime Trade, Ship Types & Principal Dimensions 1.2 Shipboard Organization, Ranks & Trainee GP Rating Duties 1.3 Hull Structure, Compartments & Watertight Openings 1.4 Computer Operation, Shipboard IT Systems & Digital Basics
2 Chapter 2: Navigation Basics, Bridge Equipment & Watchkeeping
2.1 Bridge Layout, Compass, Helmsman Duties & Steering Orders 2.2 Lookout Duties, Night Vision & STCW Bridge Watchkeeping 2.3 IALA Maritime Buoyage System (Region A) & Basic COLREGs Lights/Shapes
3 Chapter 3: Anchor Work, Mooring Operations & Tug Safety
3.1 Ground Tackle: Anchors, Cables, Windlass & Hawse Pipe 3.2 Mooring Equipment, Lines & Deck Fittings 3.3 Mooring & Unmooring Operations, Snap-Back Zones & Tug Safety
4 Chapter 4: Cargo Handling Gear, Stowage & Hold Maintenance
4.1 Cargo Handling Appliances: Derricks, Cranes & Safe Working Load (SWL) 4.2 Cargo Hold Preparation, Dunnage & Hold Cleaning 4.3 Container Cargo, Bulk Cargoes & IMDG Code Awareness
5 Chapter 5: Seamanship, Ropes, Rigging & Deck Maintenance
5.1 Natural, Synthetic & Wire Ropes: Care, Coiling & Splicing 5.2 Seamanship Knots, Bends, Hitches & Block/Tackle Rigging 5.3 Deck Maintenance: Chipping, Wire-Brushing, Painting & Working Aloft/Overside
6 Chapter 6: Shipboard Safety, Safe Working Practices & Permits
6.1 Personal Protective Equipment (PPE) & Risk Assessment Onboard 6.2 Permit to Work Systems & Enclosed Space Entry 6.3 Hot Work Precautions, Electrical Safety on Deck & Gangway Watch
7 Chapter 7: STCW Basic Safety, Firefighting & Life Saving Appliances
7.1 Life-Saving Appliances: Lifejackets, Immersion Suits & Lifebuoys 7.2 Survival Craft: Lifeboats, Liferafts & Launching Appliances 7.3 Basic Firefighting Principles, Fire Triangle & Portable Extinguishers 7.4 Elementary First Aid, CPR, Bleeding Control & Medical Emergency Response
8 Chapter 8: Marine Pollution Prevention & MARPOL Regulations
8.1 MARPOL Overview & Annex I: Oil Pollution Prevention 8.2 MARPOL Annex V: Garbage Management & Shipboard Waste 8.3 Bunkering Procedures, SOPEP & Spill Response
9 Chapter 9: Engine Room Familiarization, Watchkeeping & Safety
9.1 Engine Room Layout, Bilges, Tank Tops & Trainee Ratings Duties 9.2 Engine Room Instrumentation, Alarms & Emergency Escapes 9.3 Quick-Closing Valves, Emergency Stops & Fire Dampers
10 Chapter 10: Marine Diesel Engines: Cycles, Components & Systems
10.1 Two-Stroke & Four-Stroke Marine Diesel Operating Principles 10.2 Main Engine Structural Components & Moving Parts 10.3 Engine Support Systems: Fuel Oil, Lubricating Oil & Starting Air 10.4 Engine Cooling Water Systems & Scavenge Fires
11 Chapter 11: Marine Auxiliary Machinery, Heat Exchangers & Boilers
11.1 Air Compressors, Compressed Air Receivers & Centrifugal Purifiers 11.2 Fresh Water Generators (Evaporators) & Heat Exchangers 11.3 Marine Boilers, Exhaust Gas Economizers & Steam Systems 11.4 Domestic Services, Refrigeration, Air Conditioning & Sewage Treatment
12 Chapter 12: Marine Pumps, Piping Systems, Valves & Steering Gear
12.1 Centrifugal & Positive Displacement Marine Pumps 12.2 Valves, Filters, Strainers & Pipeline Identification 12.3 Bilge, Ballast & Oily Water Separator (OWS) Systems 12.4 Steering Gear Systems & Emergency Steering Procedures 12.5 Shipboard Plumbing Repairs, Pipe Clamping & Pipeline Maintenance
13 Chapter 13: Workshop Tools, Fitting, Hot Work & Electrical Safety
13.1 Workshop Hand Tools, Fitting Practices & Precision Measurement 13.2 Power Tools, Grinding, Drilling & Safe Workshop Operations 13.3 Gas Welding, Electric Arc Welding & Hot Work Safety 13.4 Electrical Safety, Isolation, LOTO & Hazards in Machinery Spaces 13.5 Lathe Machine Operations, Centering & Fabrication 13.6 Shipboard Carpentry, Woodworking & Cement Box Emergency Repairs
14 Chapter 14: Engine Room Firefighting, Fixed Systems & Emergency Response
14.1 Machinery Space Fire Hazards & Flammable Liquids Management 14.2 Fixed Fire-Extinguishing Systems: CO2, Water Mist & Hi-Expansion Foam 14.3 Emergency Procedures: Blackout, Flooding, Abandon Ship & Engine Room Safety Drills
14.2 Fixed Fire-Extinguishing Systems: CO2, Water Mist & Hi-Expansion Foam
Key Takeaways Explain This Topic AI
The fixed high-pressure CO 2 \text{CO}_2 CO 2 total flooding system smothers engine room fires by reducing atmospheric oxygen from 21 % 21\% 21% down to below 15 % 15\% 15% ; SOLAS mandates that 85 % 85\% 85% of the required gas charge must be discharged within 2 minutes.
Before authorized CO2 release, evacuate and account for personnel, stop affected machinery and oil feeds, isolate ventilation and close the space. Follow the posted controls: automatic pre-discharge warning must allow evacuation and last at least 20 seconds; open the distribution valve before releasing the cylinders.
Approved local water-based or equivalent systems protect machinery fire hazards without requiring prior engine shutdown, evacuation or sealing for activation. Water mist cools and suppresses the fire, but smoke, heat and the atmosphere can still require evacuation or breathing apparatus. Know the installed manual and automatic controls.
High-expansion foam systems can use expansion ratios between 500:1 and 1000:1 to rapidly submerge the entire machinery space from floor to deckhead in a dense blanket of bubbles, smothering fuel pools and suppressing smoke.
After CO2 flooding, keep the space closed until extinction and cooling are assessed, then ventilate and re-enter only under the ship’s controlled procedure. Normal oxygen alone is insufficient: test CO2, combustion gases and any flammability hazard as well. Initial entry into an unsafe or uncertain atmosphere requires trained personnel with suitable SCBA and back-up.
Last updated: November 2026
14.2 Fixed Fire-Extinguishing Systems: CO2, Water Mist & Hi-Expansion Foam
When a major fire erupts in a ship's machinery space—fueled by ruptured fuel oil pipes, boiler blowbacks, or scavenge conflagrations—portable and mobile fire extinguishers are rapidly overwhelmed. In such catastrophic scenarios, ship survival depends upon fixed fire-extinguishing systems . Trainee General Purpose (GP) Ratings must thoroughly understand the engineering architecture, smothering mechanisms, operating sequences, and critical life-safety interlocks of the three primary fixed systems: High-Pressure Carbon Dioxide ( CO 2 \text{CO}_2 CO 2 ) Total Flooding, Local Application Water Mist (Hyper-Mist), and High-Expansion Foam.
1. Fixed High-Pressure Carbon Dioxide ( CO 2 \text{CO}_2 CO 2 ) Total Flooding System
High-pressure CO 2 \text{CO}_2 CO 2 remains the most widely installed total flooding medium for engine rooms, pump rooms, and cargo holds on merchant ships. Because carbon dioxide is an inert, non-conductive gas that leaves no chemical residue, it extinguishes three-dimensional liquid spray fires without damaging electrical switchboards or delicate turbo-machinery. FIXED HIGH-PRESSURE CO2 TOTAL FLOODING SYSTEM
- +-------------------------------------------------------------+
- | CO2 BATTERY ROOM (Dedicated deckhouse outside engine room) |
- | |
- | [Cyl] [Cyl] [Cyl] [Cyl] [Cyl] [Cyl] [Cyl] [Cyl] [Cyl] |
- | | | | | | | | | | |
- | +-----------------------------------------------------+ |
- | | High-Pressure Distribution Manifold | |
- | +--------------------------+--------------------------+ |
- | | |
- | +--------v--------+ |
- | | Main Stop Valve | |
- | +--------+--------+ |
- | | |
- | PILOT RELEASE CABINET | |
- | +---------------------+ | |
- | | [Door Microswitch] | | |
- | | (Alarm Initiation) | | |
- | | [Pilot Gas Bottle] |----+ |
- | | [Release Levers] | | |
- | +---------------------+ | |
- +------------------------------|------------------------------+
- |
- | Distribution Pipe to Engine Room
- v
- +-------------------------------------------------------------+
- | MACHINERY SPACE (ENGINE ROOM) |
- | |
- | (Nozzle) (Nozzle) (Nozzle) |
- | v v v |
- | * * * * * * * * * * * * |
- | * * * * * * * * * * * * * * * |
- | * * * * * * * * * * * * * * * * * * |
- | Tank Top Bilges Cylinder Tops Purifier Room |
- +-------------------------------------------------------------+
- System Layout and Storage Architecture
CO 2 \text{CO}_2 CO 2 Battery Room :
Located outside the engine room boundaries, typically on the open boat deck or upper superstructure deck, with direct access from the open weather deck.
Keep the room within the system’s approved ambient-temperature limits. SOLAS requires bottom-extract mechanical ventilation of at least six air changes per hour for storage spaces below deck or without access from the open deck. High-pressure storage is distinct from refrigerated low-pressure CO2 storage.
Housed with dozens or hundreds of high-tensile seamless steel cylinders (each typically 45 kg 45\text{ kg} 45 kg or 67.5 liter 67.5\text{ liter} 67.5 liter capacity) pressurized with liquid CO 2 \text{CO}_2 CO 2 at approximately 57 bar 57\text{ bar} 57 bar at 20 ∘ C 20^\circ\text{C} 2 0 ∘ C .
Cylinders are fitted with siphon dip-tubes extending to the cylinder bottom, ensuring liquid CO 2 \text{CO}_2 CO 2 is forced out under its own vapor pressure when released.
Distribution Manifold & Directional Valves :
Each cylinder is connected to a common high-pressure manifold via high-pressure flexible loops and non-return check valves.
Directional distribution section valves direct the gas charge to specific compartments: Engine Room, Auxiliary Boiler Space, Purifier Room, or Cargo Holds.
Discharge Nozzles :
Orifice and horn-type nozzles strategically distributed across three elevations: (1) beneath floor plates over bilge wells and pipe trenches, (2) over middle platform auxiliary machinery, and (3) around the upper deckhead casing.
Extinguishing Mechanism & SOLAS Performance Criteria
Oxygen Displacement (Smothering) : Atmospheric air contains approximately 20.95 % O 2 20.95\%\text{ O}_2 20.95% O 2 . Hydrocarbon liquid fires require at least 15 % – 16 % O 2 15\%\text{--}16\%\text{ O}_2 15% – 16% O 2 to sustain open combustion. When discharged, high-pressure CO 2 \text{CO}_2 CO 2 gas—which is 1.5 times heavier than air 1.5\text{ times heavier than air} 1.5 times heavier than air —expands rapidly across the space, diluting the oxygen available for combustion to suppress the fire. Retain the extinguishing concentration and keep the space closed while hot machinery cools; premature ventilation can cause re-ignition.
FSS Code Chapter 5 Performance Requirement :
Important
For machinery spaces of Category A, the fixed CO 2 \text{CO}_2 CO 2 system piping must be sized and arranged such that at least 85 % 85\% 85% of the statutory required gas volume is discharged into the space within 2 minutes from release actuation.
The current FSS Code paragraph 2.2.1.6 specifies this rapid discharge. Successful suppression also depends on stopping fuel feed, closing the space and retaining the gas; the discharge time is not proof that the fire is out.
Release Preparations, Controls & Safety Interlocks
CO2 flooding creates a life-threatening atmosphere. Follow the ship’s emergency plan and the operating instructions posted at the release station. The Master, or the responsible officer authorized by the ship’s procedures, directs release after the safety preparations have been verified. CO2 RELEASE — CHECK THE SHIP’S INSTRUCTIONS
- Evacuate protected space -> Account for everyone / verify headcount
- |
- v
- Stop ventilation -> Close dampers, skylights and other gas/air openings
- |
- v
- Stop affected machinery/pumps -> Isolate fuel/oil feeds as directed
- |
- v
- Authorized release -> Confirm correct space and pre-discharge warning
- |
- v
- Open distribution valve -> Release CO2 from the storage cylinders
Evacuate and Account for Personnel : Leave by safe escape routes and muster as directed. Confirm that everyone has left the protected space and complete the headcount before discharge. Report anyone missing immediately.
Isolate Ventilation and Close the Space : Operate the remote fan stops and close the relevant dampers, skylights and other openings that admit air or allow gas to escape. Verify closure; do not assume a release-cabinet switch has stopped every fan.
Stop Machinery and Fuel Feed : Stop the machinery and oil pumps in the affected space and operate the designated quick-closing valves under the emergency plan. Prevent continued fuel or oil supply to the fire.
Select and Check the Release Station : Confirm that the controls serve the correct space. If the release box is locked, the FSS Code requires its key in a conspicuous adjacent break-glass enclosure. Follow the installed controls and instructions.
Pre-Discharge Warning : The audible and visual alarm starts automatically, for example when the cabinet door opens. It must sound for the time needed to evacuate, never less than 20 seconds before discharge . The alarm is an immediate escape signal; it does not replace the evacuation and headcount check.
Operate the Two Release Controls : First open the distribution valve to the selected protected space, then discharge the storage cylinders. Approved interlocks ensure the correct sequence. Pilot-gas actuation is a common arrangement, but the exact levers and controls are those shown in the ship’s instructions.
Asphyxiation, Cryogenic & Post-Discharge Hazards
Lethal Exposure Hazard : Carbon dioxide is colourless and odourless. High concentrations have direct toxic effects as well as reducing available oxygen, and can rapidly cause unconsciousness and death. Never rely on symptoms or a supposedly safe delay: evacuate before release, account for personnel, and prevent unauthorized re-entry.
Cryogenic Temperatures & Static Electricity : Discharge can produce very cold gas and dry-ice particles. At atmospheric pressure, dry ice sublimes at − 78.5 ∘ C -78.5^\circ\text{C} − 78. 5 ∘ C . Avoid skin contact with cold discharge equipment and liquid or solid CO2 because of frostbite risk. Maintain the system’s bonding and earthing arrangements.
Post-Discharge Waiting Period & Re-Entry Protocol :
Caution
CONTROL RE-ENTRY AFTER CO2 DISCHARGE :
Keep the space closed until the responsible officers have established that the fire is extinguished and machinery has cooled sufficiently to prevent re-ignition. Monitor boundaries and apply boundary cooling as directed; seek specialist advice where needed.
Ventilate only when authorized by the fire-response plan. Keep personnel clear of exhaust outlets. Time spent ventilating does not by itself prove that the atmosphere is safe.
Any initial entry into an unsafe or uncertain atmosphere requires a trained team using suitable SCBA, communications and rescue/back-up arrangements. Apply the ship’s entry permit and risk assessment; an EEBD is for escape.
Before entry without breathing apparatus, use suitable instruments and representative sampling at all levels and poorly ventilated areas. Current IMO recommendations call for 20.9% oxygen, CO2 below 0.5% by volume, less than 1% LFL where a flammable atmosphere is possible, and toxic gases below 50% of their occupational exposure limits . Test specifically for CO2 and combustion gases; a normal oxygen result alone is insufficient.
Maintain ventilation, atmospheric monitoring, an attendant, communications and rescue readiness while occupied. Leave immediately if conditions deteriorate or ventilation fails.
2. Local Application Water Mist Systems (Hyper-Mist)
Local application water-based systems can suppress a fire at its source promptly, while preparations for any necessary total flooding continue. Unlike CO2 flooding, activation does not require prior shutdown, sealing or evacuation of the whole space.
SOLAS II-2/10.5.6 applies to passenger ships of 500 GT and above and cargo ships of 2,000 GT and above . Machinery spaces of category A above 500 m³ require an approved fixed water-based or equivalent local application system , in addition to the main fixed system. Water mist is a common solution; high-pressure equipment is one example. LOCAL APPLICATION WATER MIST — EXAMPLE
- +--------------------+ +-----------------------+
- | Fresh Water Supply |---> High-Pressure Plunger |
- | Storage Tank | | Pump (100 to 140 bar) |
- +--------------------+ +-----------+-----------+
- |
- v High-Pressure Stainless Main
- +--------------------------------------+-----------------------------------+
- | | | |
- v Section Valve A v Section Valve B v Section Valve C v
- +--------------------+ +--------------------+ +--------------------+ +---+
- | MAIN ENGINE TOPS | | DIESEL GENERATORS | | PURIFIER ROOM | |BOI|
- | Micro-Nozzles | | Micro-Nozzles | | Micro-Nozzles | |LER|
- | [Atomized Droplets]| | [Atomized Droplets]| | [Atomized Droplets]| | |
- | (50-100 microns) | | (50-100 microns) | | (50-100 microns) | | |
- +--------------------+ +--------------------+ +--------------------+ +---+
- Local Protection Areas
Local application systems protect selected hazards rather than flooding the entire engine room. Instead, specialized micro-nozzles are positioned directly above specific high-risk fire zones:
Main engine cylinder heads, fuel injection pumps, and high-pressure fuel rails.
Auxiliary diesel generator cylinder tops, exhaust lines, and turbochargers.
Marine auxiliary boiler burner fronts, fuel valve manifolds, and furnace doors.
Purifiers for heated fuel oil; other oil-treatment hazards may also be covered by the approved design.
Waste incinerator burner fronts and fuel pumps.
Operating Principles & Dual Extinguishing Kinetics
High-Pressure Example : A plunger pump can deliver water through stainless steel piping at 100 – 140 bar 100\text{--}140\text{ bar} 100 – 140 bar . Actual pressure, supply and nozzle arrangement are those of the approved system; a local section may share a suitably designed water-based main system.
Micro-Droplet Atomization : Specialized micro-orifice spray nozzles shatter the high-pressure water stream into a dense, fog-like mist with droplet diameters of 50 – 100 microns 50\text{--}100\text{ microns} 50 – 100 microns ( 0.05 – 0.1 mm 0.05\text{--}0.1\text{ mm} 0.05 – 0.1 mm ) .
Extinguishing Action 1: Enormous Surface Cooling :
By atomizing 1 liter 1\text{ liter} 1 liter of water into 50-micron droplets, the total water surface area is approximately 120 square meters 120\text{ square meters} 120 square meters .
These micro-droplets absorb the high latent heat of vaporization of water ( 2 , 260 kJ/kg 2,260\text{ kJ/kg} 2 , 260 kJ/kg ) instantly, cooling the flame zone and adjacent fuel surfaces below ignition temperatures.
Extinguishing Action 2: Localized Oxygen Starvation (Steam Expansion) :
As the micro-droplets vaporize, they expand 1 , 700 times 1,700\text{ times} 1 , 700 times in volume into water steam.
This sudden steam expansion displaces oxygen in the immediate vicinity of the hotspot, helping suppress the fire locally. This does not make the surrounding fire atmosphere safe to breathe.
Activation and Watchkeeper Safety
Immediate Local Suppression : Activation does not require prior engine shutdown, personnel evacuation, ventilation shutdown or sealing of the space. This allows prompt attack on a developing fire.
Fire Hazards Remain : Smoke, heat, steam and oxygen depletion can still endanger personnel. Follow the alarm and emergency plan, escape when required, and use suitable breathing apparatus for firefighting. Do not interpret water discharge as an all-clear.
Release Modes : Periodically unattended machinery spaces require both automatic and manual release; continuously manned spaces require manual release. Automatic systems use approved detection arrangements, such as two flame detectors or a flame-and-smoke combination. Know the installed controls and section indications.
3. High-Expansion Foam Systems
High-expansion foam systems represent another powerful total-flooding alternative, particularly on roll-on/roll-off (Ro-Ro) vessels, tanker pump rooms, and specialized container engine rooms. OUTSIDE-AIR FOAM GENERATOR — EXAMPLE
- Water Main (Fire Pump) + Foam Concentrate Tank
- |
- v Proportioner (Injects 2% to 3% Concentrate)
- +-------------------------------------------------------------+
- | Foam Solution Delivery Pipeline |
- +-----------------------------+-------------------------------+
- |
- v
- +-----------------------------+
- | HIGH-EXPANSION FOAM GEN |
- | |
- Fresh Air Duct | [ Spray Nozzles ] |
- ==============> | | | |
- (Air Fan Driven)| v v |
- | [ Fine Wire Mesh Net ] |
- | O O O O O O O O |
- | O O O O O O O O O |
- +--------------+--------------+
- |
- v
- Continuous Blanket of Featherweight Bubbles (500:1 to 1000:1)
Submerges Entire Machinery Space from Tank Top to Overhead!
Foam Expansion Ratios & Mechanics
Expansion Ratio : Defines the volume of expanded foam generated from a given volume of liquid water-concentrate solution. Typical high-expansion systems may produce expansion ratios of 500 : 1 to 1000 : 1 500:1\text{ to }1000:1 500 : 1 to 1000 : 1 (one cubic meter of liquid yields 500 to 1,000 cubic meters of foam).
Foam Generation : The proportioner mixes water and the system’s approved concentrate at its specified concentration. In an outside-air system, a fan forces fresh air through a screen wetted by the foam solution. Inside-air systems instead generate foam using air from the protected space. Use the matched generator/concentrate arrangement and the ship’s operating instructions.
Fire Suppressing Mechanism
Smothering : The rapid buildup of foam completely blankets all bilge surfaces, pipes, and fuel tanks, sealing off liquid fuel surfaces from atmospheric oxygen.
Cooling : As the bubble lattice contacts hot metal, the thin water film vaporizes, cooling the steel and generating steam that further dilutes oxygen.
Thermal Insulation & Smoke Scrubbing : The foam blanket acts as a thermal barrier, blocking radiant heat transfer to unignited fuel tanks and trapping toxic soot and smoke particles within the bubble structure.
Escape and Post-Discharge Hazards
Evacuate on the pre-discharge warning; foam can obscure exits and impair hearing and orientation. If caught during discharge:
Don an EEBD immediately if available and continue along the escape route.
Keep contact with a handrail or bulkhead to maintain direction; clear foam from the face as needed to escape.
Do not rely on air in foam bubbles for breathing : the blanket may contain oxygen-deficient air and toxic combustion products.
Re-entry after discharge requires a controlled plan and suitable breathing apparatus. Do not enter to search for a casualty without the trained team and back-up arrangements.