Study guide

10.2 Backflow Prevention Assemblies: RPZ, DCVA, PVB & Vacuum Breakers

Indiana Journeyman Plumber Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Orientation & Trade Mathematics

1.1 Exam Format, Prov Testing Policies & Code References 1.2 Navigating the 2006 IPC & 2012 Indiana Amendments 1.3 Trade Math: Slopes, Head Pressure, Volumes & Fitting Allowances

2 Chapter 2: General Regulations, Structural Safety & Supports

2.1 Piping Protection, Corrosion, Freezing & Sleeving 2.2 Structural Safety: Cutting, Notching & Boring in Joists and Studs 2.3 Pipe Hangers, Brackets, Anchoring & Support Spacing

3 Chapter 3: Plumbing Fixtures, Faucets & Accessibility

3.1 Minimum Plumbing Facilities & Fixture Count Sizing 3.2 Water Closets, Urinals & Flushometer Sizing 3.3 Lavatories, Showers, Bathtubs & Scald Prevention (ASSE 1016/1017)

4 Chapter 4: Traps, Interceptors & Indirect Waste

4.1 Trap Design, Liquid Seal Protection, Primers & Prohibited Traps 4.2 Grease Interceptors, Oil Separators & Sand Traps 4.3 Indirect Waste, Air Gaps, Air Breaks & Food Preparation Waste

5 Chapter 5: Sanitary Drainage: Sizing, Slopes & Materials

5.1 Drainage Fixture Units (DFU) & Horizontal Branch Sizing 5.2 Building Drain & Building Sewer Sizing, Slopes & Velocities 5.3 Drainage Pipe Materials, Solvent Cementing & Mechanical Joints

6 Chapter 6: Sanitary Drainage: Cleanouts, Sumps & Testing

6.1 Cleanout Locations, Sizing, Clearances & Accessibility 6.2 Drainage Sumps, Sewage Ejectors & Backwater Valves 6.3 Drainage System Inspection & Testing (Water, Air & Smoke)

7 Chapter 7: Vents: Principles, Stacks & Terminals

7.1 DWV Venting Principles, Hydraulic Gradients & Trap Protection 7.2 Individual, Common & Relief Vents 7.3 Vent Terminals, Roof Extensions & Frost Closure (IPC Section 904) 7.4 Vent Stacks, Stack Vents, Vent Headers & Waste Stack Vents

8 Chapter 8: Vents: Advanced Systems & Special Venting

8.1 Horizontal & Vertical Wet Venting Systems 8.2 Circuit Venting & Loop Venting Systems 8.3 Combination Waste and Vent Systems & Island Fixture Venting 8.4 Air Admittance Valves (AAVs) & Installation Limits 8.5 Vent Pipe Sizing: Table 916.1, Section 916.2 & Developed Length

9 Chapter 9: Water Supply: Sizing, Distribution & Materials

9.1 Water Service Sizing, Street Pressure & Pressure Regulators 9.2 Water Supply Fixture Units (WSFU) & Pipe Sizing Tables 9.3 Water Distribution Materials, Copper Joining & PEX Systems 9.4 Water Hammer Arrestors & Thermal Expansion Control

10 Chapter 10: Backflow Prevention & Cross-Connection Control

10.1 Cross-Connection Hazards, Backpressure & Backsiphonage 10.2 Backflow Prevention Assemblies: RPZ, DCVA, PVB & Vacuum Breakers 10.3 Containment vs. Isolation, Installation Clearances & Testing

11 Chapter 11: Water Heaters: Sizing, Combustion & Safety

11.1 Water Heater Sizing, Clearances, Drain Pans & Elevation in Garages 11.2 Temperature and Pressure (T&P) Relief Valves & Discharge Piping 11.3 Combustion Air, Draft Hoods & Venting of Fuel-Fired Water Heaters

12 Chapter 12: Storm Drainage Systems & Roof Drainage

12.1 Indiana Rainfall Rates, Projected Roof Area & Roof Drain Sizing 12.2 Vertical Conductors, Downspouts & Horizontal Storm Drains 12.3 Subsoil Drains, Sump Pumps & Secondary Emergency Overflows

13 Chapter 13: Developed Length, Isometric Analysis & Offset Math

13.1 Reading Plumbing Blueprints, Symbols & DWV Riser Diagrams 13.2 Isometric Drawing Interpretation & Three-Dimensional Layouts 13.3 Developed Length Calculations, 45-Degree Offsets & Rolling Offsets

14 Chapter 14: Indiana Plumbing Laws, Rules, Code Amendments & Business

14.1 Indiana Plumbing Commission (IC 25-28.5) & Licensing Standards 14.2 Key Indiana Amendments to the 2006 IPC (675 IAC 16-1.4) 14.3 Plumbing Permits, Local Administrative Rules & Inspections 14.4 Plumbing Business, OSHA Safety & Project Management Fundamentals

10.2 Backflow Prevention Assemblies: RPZ, DCVA, PVB & Vacuum Breakers

Key Takeaways Explain This Topic AI

A physical air gap conforming to ASME A112.1.2 provides an unobstructed vertical physical separation equal to at least twice the effective diameter of the supply pipe (minimum 1.0 inch), representing the highest level of backflow protection.

A Reduced Pressure Principle Backflow Preventer (RPZ conforming to ASSE 1013) uses two independent spring-loaded check valves and a central differential relief valve discharging to atmosphere, approved for both High and Low hazards under continuous backpressure and backsiphonage.

A Double Check Valve Assembly (DCVA conforming to ASSE 1015) consists of two independent check valves, test cocks, and shutoffs, but is strictly prohibited on High Hazard (health hazard) installations due to the absence of an atmospheric relief discharge.

A Pressure Vacuum Breaker (PVB conforming to ASSE 1020) protects against backsiphonage only under continuous pressure, and must be installed at least 12 inches above all downstream piping, valves, and outlets.

An Atmospheric Vacuum Breaker (AVB conforming to ASSE 1001) protects against backsiphonage only, must be installed at least 6 inches above downstream outlets, is strictly rated for non-continuous pressure (maximum 12 hours), and cannot have any downstream shutoff valves.

Last updated: September 2026

10.2 Backflow Prevention Assemblies: RPZ, DCVA, PVB & Vacuum Breakers

Core Principle: Mechanical backflow protection requires matching the exact engineering capabilities of an assembly to the operational demands of the system. IPC Table 608.1 prescribes specific standards established by the American Society of Sanitary Engineering (ASSE) and American Society of Mechanical Engineers (ASME). Selecting an improper assembly—such as installing a Double Check Valve on a high-hazard chemical line or placing an Atmospheric Vacuum Breaker under continuous static pressure—violates plumbing codes and creates an immediate danger to the public water distribution network.

Assemblies vs. Devices: The Critical Trade Distinction

In the plumbing trade and across licensing examinations, plumbers must understand the legal and functional distinction between a backflow prevention assembly and a backflow prevention device :

Backflow Prevention Assembly: A complete, factory-manufactured, field-testable unit that includes an approved body containing internal operating mechanisms, two tightly closing shutoff valves (typically resilient-seated full-port ball valves or OS&Y gate valves), and four calibrated test cocks. Assemblies can be tested in-line by certified testers using differential pressure gauges to verify hydraulic integrity without dismantling the valve. Examples include the RPZ (ASSE 1013) , DCVA (ASSE 1015) , PVB (ASSE 1020) , and SVB (ASSE 1056) .

Backflow Prevention Device: A non-testable mechanical component designed to prevent backflow that lacks test cocks and integral shutoff valves. Devices cannot be field-tested with test gauges; their internal springs or check discs can only be inspected visually or verified by rebuilding/replacing internal parts. Examples include AVBs (ASSE 1001) , Hose Bibb Vacuum Breakers (ASSE 1011) , and Dual Check Valves (ASSE 1024) .

1. Physical Air Gap (ASME A112.1.2)

A physical air gap is the unobstructed vertical distance through free atmosphere between the lowest opening of any pipe or faucet supplying potable water and the flood-level rim of the receiving receptacle, fixture, or tank. PHYSICAL AIR GAP GEOMETRY

  • Potable Supply Pipe
  • +-----------------+
  • | | d |
  • +--------+--------+
  • |
  • | <--- Effective Opening Diameter (d)
  • |
  • | | | | |
  • | | V | |
  • | | ============================== | |
  • | | ^ | |
  • | | | | |
  • | | | AIR GAP (2 x d) | |
  • | | | (Min. 1.0 Inch) | |
  • | | | | |
  • | | v | |
  • FLOOD-LEVEL | +-------------------------------------+ | FLOOD-LEVEL
  • RIM --------+ +-------- RIM
  • | RECEPTACLE |
  • | OR FIXTURE |
  • +-----------------------------------------+
  • Geometric and Code Sizing Rules (IPC Section 608.15.1)

Standard Vertical Clearance: The vertical air gap must be at least twice the effective diameter ( 2 × d 2 \times d 2 × d ) of the supply pipe opening, but in no case less than 1.0 inch (25 mm) .

Wall Interference Adjustment: If the potable supply pipe outlet is located close to a vertical wall (closer than 3 times the diameter of the pipe) or intersecting corner walls (closer than 4 times the diameter), the surrounding surfaces interfere with free atmospheric airflow. In such cases, the required vertical air gap increases to three times the effective diameter ( 3 × d 3 \times d 3 × d ) , but never less than 1.5 inches (38 mm) .

Protection Capability: The air gap provides the absolute highest degree of protection known to hydraulic engineering. It protects against both High Hazard (contamination) and Low Hazard (pollution) , and is 100% fail-safe against both backpressure and backsiphonage under continuous or intermittent flow. It cannot jam, corrode, or foul mechanically.

2. Reduced Pressure Principle Backflow Preventer (RPZ / RPBA per ASSE 1013)

The Reduced Pressure Principle Backflow Preventer (RPZ) , also designated as a Reduced Pressure Principle Assembly (RPBA) under AWWA C511, represents the highest level of mechanical backflow protection recognized by plumbing codes. REDUCED PRESSURE PRINCIPLE ASSEMBLY (RPZ - ASSE 1013)

  • Shutoff #1 Shutoff #2
  • [VALVE] [VALVE]
  • | |
  • TC #1 | TC #2 TC #3 | TC #4
  • (o) | (o) (o) | (o)
  • | v | | v |
  • ======+----+---------+-----+------------------+-----+-------------+----+======>
  • Potable | CHECK #1 | INTERMEDIATE | CHECK #2 | Discharge to
  • Supply | (Loaded to | ZONE (Maintained| (Loaded to | Protected
  • Inlet | min 5 psi) | >=2.0 psi lower| min 1 psi) | System
  • (e.g. +--------------+ than inlet) +--------------+
  • 60 psi) | |
  • +----------------+----------------+
  • |
  • v
  • +----------------------+
  • | DIFFERENTIAL RELIEF |
  • | VALVE (Opens if |=====> Discharge to Air Gap
  • | Delta P < 2.0 psid) | Funnel & Drain
  • +----------------------+
  • Construction and Operating Dynamics

An RPZ assembly consists of:

Two independently acting, spring-loaded check valves in series.

A hydraulically balanced, spring-loaded differential relief valve located between the two check valves in an intermediate chamber.

Two tightly closing resilient-seated shutoff valves (one upstream, one downstream).

Four field test cocks for differential pressure gauge attachment.

Normal Flow Condition: Water enters through Check Valve 1, which has a heavy spring creating an internal pressure drop of at least 5.0 to 9.0 psi . Water fills the intermediate chamber and flows through Check Valve 2 (loaded to open at 1.0 to 2.0 psi) into the downstream system. Because of the pressure drop across Check 1, intermediate chamber pressure is always lower than incoming supply pressure.

Differential Pressure Relief Valve Operation: The internal relief valve diaphragm senses incoming supply pressure on one side and intermediate zone pressure on the other. Supply pressure pushes the relief valve closed against its internal spring. As long as supply pressure exceeds intermediate zone pressure by at least 2.0 psi , the relief valve remains closed. If Check Valve 1 fouls (allowing supply pressure to leak into the zone), or if downstream backpressure forces contaminated water past Check Valve 2, the pressure differential between the supply and intermediate zone drops below 2.0 psi. The relief valve spring immediately drives the relief port open to atmosphere, dumping the backflowing water onto the floor through an air gap drain.

Code Ratings: Approved for High Hazard and Low Hazard ; handles both Backpressure and Backsiphonage ; rated for Continuous Pressure .

3. Double Check Valve Assembly (DCVA per ASSE 1015)

The Double Check Valve Assembly (DCVA) , governed by ASSE 1015 and AWWA C510, consists of two independently acting, spring-loaded check valves housed in a single body, equipped with two tightly closing shutoff valves and four test cocks. DOUBLE CHECK VALVE ASSEMBLY (DCVA - ASSE 1015)

  • Shutoff #1 Shutoff #2
  • [VALVE] [VALVE]
  • | |
  • TC #1 | TC #2 TC #3 | TC #4
  • (o) | (o) (o) | (o)
  • | v | | v |
  • ======+----+---------+-----+------------------+-----+-------------+----+======>
  • Potable | CHECK #1 | CENTRAL | CHECK #2 | Low-Hazard
  • Supply | (Loaded to | CHAMBER | (Loaded to | Protected
  • Inlet | min 1 psi) | (No Relief | min 1 psi) | System
  • +--------------+ Discharge) +--------------+

Operating Principles: The first check valve is spring-loaded to hold tight against a minimum of 1.0 psid ; the second check valve is also loaded to hold tight against a minimum of 1.0 psid . Under normal forward flow, both checks open. Under backflow, reverse hydraulic force drives both check valves closed against their elastomeric seats.

The High-Hazard Prohibition: Unlike an RPZ, a DCVA has no atmospheric relief port . If mineral scale, rust, or debris lodges under both check discs simultaneously, backflow will pass undetected directly through the assembly into the potable water main. For this reason, IPC Section 608.1 strictly prohibits the use of a DCVA on High Hazard (health hazard / toxic chemical) systems.

Code Ratings: Approved for LOW HAZARD ONLY (Pollution) ; handles both Backpressure and Backsiphonage ; rated for Continuous Pressure .

Common Trade Applications: Dedicated fire sprinkler systems without chemical additives, cooling loops using clean potable water, aesthetic food production lines, and residential containment at water meters.

4. Pressure Vacuum Breaker (PVB per ASSE 1020) & Spill-Resistant Vacuum Breaker (SVB per ASSE 1056)

A Pressure Vacuum Breaker (PVB) , conforming to ASSE 1020, consists of an independently acting, spring-loaded check valve and an independently acting, spring-loaded air inlet poppet valve open to atmosphere, complete with two shutoff valves and two test cocks. PRESSURE VACUUM BREAKER (PVB - ASSE 1020)

  • Air Inlet Hood
  • +----------------+
  • | AIR INLET | <--- Atmospheric Vent
  • | VALVE (POPPET)| (Spring-loaded open)
  • +--------+-------+
  • |
  • Supply Inlet | Downstream Outlet
  • (Continuous Press.) v (Elevated >=12 Inches)
  • ==================>----+ +-----+-----+ +------------------------>
  • | | CHECK | |
  • +-+----+ VALVE +----+-+
  • | TC#1 | (Spring- | TC#2 |
  • | (o) | loaded) | (o) |
  • +------+-----------+------+
  • Operating Dynamics and Limitations

Forward Flow: Incoming water pressure pushes the check valve open and simultaneously pushes the air inlet poppet upward against its spring, sealing the atmospheric air port closed.

Backsiphonage Condition: When supply pressure drops to near atmospheric pressure, the spring closes the check valve, and the secondary spring drives the air inlet poppet downward, admitting atmospheric air into the top of the body. This air intake breaks any siphonage vacuum instantly.

The Backpressure Limitation: A PVB is engineered for BACKSIPHONAGE ONLY . It cannot withstand backpressure. If downstream pressure exceeds supply pressure, the reverse flow forces the check valve closed and holds the air inlet poppet jammed upward against its seat, preventing the air inlet from opening.

Mandatory Elevation Rule: Indiana rewrote Section 608.15.4 (675 IAC 16-1.4-7(n)), and it now states that pressure type vacuum breakers shall be set a minimum of twelve (12) inches (304 mm) above all downstream piping and outlets — for example, above the highest sprinkler head on a lawn irrigation zone. The same amended section sets the atmospheric type vacuum breaker critical level at a minimum of six (6) inches (152 mm) above the flood level rim of the fixture or device, and adds that pipe-applied atmospheric-type vacuum breakers are installed not less than 6 inches, and pressure-type not less than 12 inches, above the flood level rim of the fixture, receptor or device served. Vacuum breakers shall not be installed under exhaust hoods or similar locations containing toxic fumes or vapors.

Spill-Resistant Vacuum Breaker (SVB - ASSE 1056): Standard PVBs spit a small volume of water out of the air inlet poppet during startup before the disc seals. The SVB incorporates a dual-action diaphragm that closes the air inlet vent before the check valve opens, eliminating water spillage. SVBs are specifically approved for indoor installations where water spillage would damage building finishes.

5. Atmospheric Vacuum Breaker (AVB per ASSE 1001)

An Atmospheric Vacuum Breaker (AVB) , conforming to ASSE 1001, is a non-testable backflow prevention device consisting of a gravity-operated float disc and poppet valve that rises and falls within a bronze body. ATMOSPHERIC VACUUM BREAKER (AVB - ASSE 1001)

  • FORWARD FLOW BACKSIPHONAGE
  • (Poppet Sealed to Vent) (Poppet Drops to Seal Port)
  • Air Vents Air Vents Open
  • +---+ +---+ +---+ +---+
  • | | | | | | | |
  • | +----+ | | v v |
  • | [ POPPET ]| (Seals vent) | |
  • +------+-----+ +----+--+----+
  • | | | (Poppet drops,
  • Supply | Flow Supply| v blocks supply)
  • Flow v Vacuum| [POPPET]
  • =======> <=====
  • Code Mandates and Severe Operational Restrictions

Plumbing licensing exams heavily test the three non-negotiable code rules governing AVBs:

BACKSIPHONAGE ONLY: Like the PVB, an AVB provides zero protection against backpressure.

NON-CONTINUOUS PRESSURE ONLY: Under IPC Section 608.15.4.1, an AVB must never be subjected to continuous pressure for more than 12 consecutive hours . If pressurized continuously, the soft rubber poppet sticks to the upper vent seat due to heat, chlorine, and hydrostatic force. When backsiphonage occurs, the stuck poppet fails to drop, permitting raw wastewater to siphon into the potable line.

ZERO DOWNSTREAM SHUTOFF VALVES: No shutoff valve, solenoid valve, hand sprayer nozzle, or flow-restricting control may ever be installed downstream of an AVB. Any downstream shutoff traps static line pressure under the AVB, converting the installation into an illegal continuous-pressure hazard.

Mandatory Elevation Rule: An AVB must be installed at least 6 inches (152 mm) above the flood-level rim of the fixture or highest downstream outlet.

6. Hose Bibb Vacuum Breakers & Dual Check Devices

Hose Connection Vacuum Breakers (ASSE 1011): A compact device that threads directly onto standard 3/4-inch hose bibbs, sillcocks, and wall hydrants. It incorporates a spring-loaded check and an atmospheric vent. ASSE 1011 devices feature a breakaway snap-off set screw; once tightened onto the hose bibb, the screw shears off, rendering the vacuum breaker tamper-proof and non-removable. Rated for backsiphonage only under non-continuous pressure.

Freeze-Resistant Hose Connection Backflow Preventers (ASSE 1052): Designed with two independent check valves and an atmospheric vent, specifically engineered to drain automatically when the hose is disconnected, protecting frost-proof wall hydrants from bursting in sub-freezing weather. Rated for continuous pressure and testable with special adapters.

Dual Check Valves (ASSE 1024): A non-testable device containing two spring-loaded checks in series with no atmospheric vent. Commonly installed by water utilities directly downstream of residential water meters to provide low-hazard containment against domestic backflow. Prohibited on commercial high-hazard applications.

Master Selection Matrix (IPC Table 608.1 Synthesis)

The following table synthesizes the statutory selection criteria established by IPC Table 608.1 for all major backflow assemblies and devices:

Assembly / Device Type Governing Standard Degree of Hazard Hydraulic Condition Operating Pressure Minimum Installation Elevation / Critical Constraints

Air Gap ASME A112.1.2 High & Low Backpressure & Backsiphonage Continuous Vertical gap ≥ 2 × d \ge 2 \times d ≥ 2 × d (min. 1.0 inch); ≥ 3 × d \ge 3 \times d ≥ 3 × d near walls

Reduced Pressure Assembly (RPZ) ASSE 1013 / AWWA C511 High & Low Backpressure & Backsiphonage Continuous Min. 12" to Max. 60" above floor; Never install in a pit or vault

Double Check Valve Assembly (DCVA) ASSE 1015 / AWWA C510 LOW ONLY Backpressure & Backsiphonage Continuous Accessible for testing; 12" side clearance; pits allowed if drained

Pressure Vacuum Breaker (PVB) ASSE 1020 / AWWA C512 High & Low Backsiphonage ONLY Continuous Min. 12" above highest downstream outlet or piping

Spill-Resistant Vacuum Breaker (SVB) ASSE 1056 High & Low Backsiphonage ONLY Continuous Min. 12" above highest downstream outlet ; approved indoors

Atmospheric Vacuum Breaker (AVB) ASSE 1001 High & Low Backsiphonage ONLY Non-Continuous ( ≤ 12 \le 12 ≤ 12 hrs) Min. 6" above highest outlet; NO downstream shutoff valves

Hose Connection Vacuum Breaker ASSE 1011 High & Low Backsiphonage ONLY Non-Continuous Threads onto hose bibb; breakaway set screw; no backpressure

Dual Check Valve ASSE 1024 LOW ONLY Backpressure & Backsiphonage Continuous Residential meter containment only; non-testable