11.3 Combustion Air, Draft Hoods & Venting of Fuel-Fired Water Heaters
Indiana Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Orientation & Trade Mathematics
1.1 Exam Format, Prov Testing Policies & Code References 1.2 Navigating the 2006 IPC & 2012 Indiana Amendments 1.3 Trade Math: Slopes, Head Pressure, Volumes & Fitting Allowances
2 Chapter 2: General Regulations, Structural Safety & Supports
2.1 Piping Protection, Corrosion, Freezing & Sleeving 2.2 Structural Safety: Cutting, Notching & Boring in Joists and Studs 2.3 Pipe Hangers, Brackets, Anchoring & Support Spacing
3 Chapter 3: Plumbing Fixtures, Faucets & Accessibility
3.1 Minimum Plumbing Facilities & Fixture Count Sizing 3.2 Water Closets, Urinals & Flushometer Sizing 3.3 Lavatories, Showers, Bathtubs & Scald Prevention (ASSE 1016/1017)
4 Chapter 4: Traps, Interceptors & Indirect Waste
4.1 Trap Design, Liquid Seal Protection, Primers & Prohibited Traps 4.2 Grease Interceptors, Oil Separators & Sand Traps 4.3 Indirect Waste, Air Gaps, Air Breaks & Food Preparation Waste
5 Chapter 5: Sanitary Drainage: Sizing, Slopes & Materials
5.1 Drainage Fixture Units (DFU) & Horizontal Branch Sizing 5.2 Building Drain & Building Sewer Sizing, Slopes & Velocities 5.3 Drainage Pipe Materials, Solvent Cementing & Mechanical Joints
6 Chapter 6: Sanitary Drainage: Cleanouts, Sumps & Testing
6.1 Cleanout Locations, Sizing, Clearances & Accessibility 6.2 Drainage Sumps, Sewage Ejectors & Backwater Valves 6.3 Drainage System Inspection & Testing (Water, Air & Smoke)
7 Chapter 7: Vents: Principles, Stacks & Terminals
7.1 DWV Venting Principles, Hydraulic Gradients & Trap Protection 7.2 Individual, Common & Relief Vents 7.3 Vent Terminals, Roof Extensions & Frost Closure (IPC Section 904) 7.4 Vent Stacks, Stack Vents, Vent Headers & Waste Stack Vents
8 Chapter 8: Vents: Advanced Systems & Special Venting
8.1 Horizontal & Vertical Wet Venting Systems 8.2 Circuit Venting & Loop Venting Systems 8.3 Combination Waste and Vent Systems & Island Fixture Venting 8.4 Air Admittance Valves (AAVs) & Installation Limits 8.5 Vent Pipe Sizing: Table 916.1, Section 916.2 & Developed Length
9 Chapter 9: Water Supply: Sizing, Distribution & Materials
9.1 Water Service Sizing, Street Pressure & Pressure Regulators 9.2 Water Supply Fixture Units (WSFU) & Pipe Sizing Tables 9.3 Water Distribution Materials, Copper Joining & PEX Systems 9.4 Water Hammer Arrestors & Thermal Expansion Control
10 Chapter 10: Backflow Prevention & Cross-Connection Control
10.1 Cross-Connection Hazards, Backpressure & Backsiphonage 10.2 Backflow Prevention Assemblies: RPZ, DCVA, PVB & Vacuum Breakers 10.3 Containment vs. Isolation, Installation Clearances & Testing
11 Chapter 11: Water Heaters: Sizing, Combustion & Safety
11.1 Water Heater Sizing, Clearances, Drain Pans & Elevation in Garages 11.2 Temperature and Pressure (T&P) Relief Valves & Discharge Piping 11.3 Combustion Air, Draft Hoods & Venting of Fuel-Fired Water Heaters
12 Chapter 12: Storm Drainage Systems & Roof Drainage
12.1 Indiana Rainfall Rates, Projected Roof Area & Roof Drain Sizing 12.2 Vertical Conductors, Downspouts & Horizontal Storm Drains 12.3 Subsoil Drains, Sump Pumps & Secondary Emergency Overflows
13 Chapter 13: Developed Length, Isometric Analysis & Offset Math
13.1 Reading Plumbing Blueprints, Symbols & DWV Riser Diagrams 13.2 Isometric Drawing Interpretation & Three-Dimensional Layouts 13.3 Developed Length Calculations, 45-Degree Offsets & Rolling Offsets
14 Chapter 14: Indiana Plumbing Laws, Rules, Code Amendments & Business
14.1 Indiana Plumbing Commission (IC 25-28.5) & Licensing Standards 14.2 Key Indiana Amendments to the 2006 IPC (675 IAC 16-1.4) 14.3 Plumbing Permits, Local Administrative Rules & Inspections 14.4 Plumbing Business, OSHA Safety & Project Management Fundamentals
11.3 Combustion Air, Draft Hoods & Venting of Fuel-Fired Water Heaters
Key Takeaways Explain This Topic AI
Complete combustion of natural gas requires approximately 10 cubic feet of atmospheric air per 1,000 BTU of fuel gas burned, with additional excess and dilution air necessary to prevent lethal carbon monoxide generation.
An unconfined space is defined as having a room volume of at least 50 cubic feet per 1,000 BTU/hr of aggregate appliance input; spaces below this threshold are confined spaces requiring dedicated combustion air openings.
Confined spaces obtaining combustion air from outdoors require either two vertical openings/ducts sized at 1 sq in per 4,000 BTU/hr, two horizontal ducts at 1 sq in per 2,000 BTU/hr, or a single high opening at 1 sq in per 3,000 BTU/hr.
Confined spaces obtaining combustion air from inside the building require two permanent openings located within 12 inches of the top and bottom of the space, each sized at 1 sq in per 1,000 BTU/hr with an absolute minimum of 100 sq inches each.
Category I atmospheric gas water heaters require negative draft venting with Type B double-wall pipe (1-inch clearance to combustibles) and draft hoods, while Category IV high-efficiency appliances use positive-pressure, condensing plastic vents (PVC/CPVC/polypropylene) pitched 1/4" per foot.
Last updated: September 2026
11.3 Combustion Air, Draft Hoods & Venting of Fuel-Fired Water Heaters
Core Principle: Fuel gas combustion consumes large quantities of atmospheric oxygen. Every fuel-fired appliance must be provided with adequate combustion, ventilation and dilution air, and its flue gases must be exhausted safely to the outdoors. Insufficient combustion air starves burner flames, generating carbon monoxide (CO) and causing vent spillage into living areas.
Which code book answers a combustion air question in Indiana? IPC Section 502.1 says gas-fired water heaters "shall conform to the requirements of the International Fuel Gas Code ," oil-fired heaters to the International Mechanical Code, and electric heaters to the ICC Electrical Code. In Indiana that means the Indiana Fuel Gas Code (675 IAC 25) and the Indiana Mechanical Code (675 IAC 18) . Neither is on the Prov reference list for the Journeyman Plumber exam, so combustion air items are written to be answerable from trade knowledge and from what Indiana put into the plumbing code :
Section 502.2 (Rooms Used as a Plenum): water heaters using solid, liquid or gas fuel shall not be installed in a room containing air-handling machinery when that room is used as a plenum.
Indiana Section 502.2.1 (added by 675 IAC 16-1.4-6(c)): fuel-fired appliances shall not be located in, or obtain combustion air from, sleeping rooms, bathrooms, toilet rooms, storage closets or surgical rooms , with exceptions for direct-vent appliances taking all combustion air from outdoors, certain solid fuel-fired appliances, and appliances in a dedicated enclosure taking all combustion air from outdoors per Section 703 of the Indiana Mechanical Code, accessed through a weather-stripped, self-closing solid door.
Indiana Section 502.1.1.1 (parking garages): two-door vestibule separation, or a single door where ignition sources are elevated per Section 304.3 of the Indiana Mechanical Code.
The sizing methods below are the standard fuel-gas-code methods. Learn them as trade competency, and cite the fuel gas code rather than the IPC when a stem asks for the source.
Combustion Air Physics & Stoichiometric Chemistry
Natural gas is composed primarily of methane ( CH 4 \text{CH}_4 CH 4 ). Complete combustion requires mixing methane with oxygen in precise stoichiometric proportions: CH 4 + 2 O 2 → CO 2 + 2 H 2 O + Heat \text{CH}_4 + 2\text{O}_2 \rightarrow \text{CO}_2 + 2\text{H}_2\text{O} + \text{Heat} CH 4 + 2 O 2 → CO 2 + 2 H 2 O + Heat
The 10:1 Air-to-Gas Ratio
Notice that burning 1 cubic foot of methane requires exactly 2 cubic feet of pure oxygen ( O 2 \text{O}_2 O 2 ) . Ambient atmospheric air contains approximately 21% oxygen and 78% nitrogen (with trace gases). To supply 2 cubic feet of pure oxygen, an appliance must ingest: Theoretical Air Volume = 2.0 cu ft O 2 0.2095 ≈ 9.53 to 10.0 cubic feet of air \text{Theoretical Air Volume} = \frac{2.0 \text{ cu ft } \text{O}_2}{0.2095} \approx 9.53 \text{ to } 10.0 \text{ cubic feet of air} Theoretical Air Volume = 0.2095 2.0 cu ft O 2 ≈ 9.53 to 10.0 cubic feet of air
Because 1 cubic foot of natural gas produces approximately 1,000 BTU of heat energy, complete combustion demands at least 10 cubic feet of fresh atmospheric air for every 1,000 BTU of gas consumed . +-------------------------------------------------------------------------+
- | AIR COMPONENTS FOR GAS APPLIANCE COMBUSTION |
- +-------------------------------------------------------------------------+
- | Primary Air | Air mixed with gas inside burner throat before |
- | | ignition (governs flame shape and initial burn) |
- | Secondary Air | Air surrounding the flame outer mantle to complete |
- | | the combustion reaction |
- | Excess Air | Extra air (30% to 50% surplus) required to ensure |
- | | zero unburned hydrocarbons under varying barometrics |
- | Dilution Air | Air entering the draft hood relief opening to cool |
- | | flue gases and maintain steady chimney draft |
- | Total Demand | ~15 to 30 cubic feet of air per 1,000 BTU/hr input |
- +-------------------------------------------------------------------------+
- Hazards of Incomplete Combustion
If the mechanical space lacks sufficient fresh air, oxygen levels drop below critical thresholds. The chemical reaction deteriorates: 2 CH 4 + 3 O 2 → 2 CO + 4 H 2 O + Soot (C) 2\text{CH}_4 + 3\text{O}_2 \rightarrow 2\text{CO} + 4\text{H}_2\text{O} + \text{Soot (C)} 2 CH 4 + 3 O 2 → 2 CO + 4 H 2 O + Soot (C)
Instead of harmless carbon dioxide ( CO 2 \text{CO}_2 CO 2 ), the starved flame produces carbon monoxide (CO) —an odorless, colorless, lethal neurotoxin that binds to human hemoglobin with 200 times greater affinity than oxygen. Incomplete combustion also produces thick carbon soot that clogs heat exchanger passages, causing burner back-flashing and fire hazards.
Unconfined vs. Confined Space Determination
Before designing combustion air intake grilles, the plumber must mathematically determine whether the installation room contains enough natural air infiltration or must be treated as a confined space.
The Standard Unconfined Space Rule (50 cu ft / 1,000 BTU/hr)
Under IPC Chapter 5 and IFGC Section 304, an unconfined space is defined as:
A room or connected space whose total interior volume is at least 50 cubic feet per 1,000 BTU/hr ( 4.8 m 3 / kW 4.8 \text{ m}^3/\text{kW} 4.8 m 3 / kW ) of the aggregate input rating of all fuel-burning appliances installed in that space. Required Unconfined Volume ( V req ) = Total Appliance Input (BTU/hr) 1 , 000 × 50 cu ft \text{Required Unconfined Volume } (V_{\text{req}}) = \frac{\text{Total Appliance Input (BTU/hr)}}{1,000} \times 50 \text{ cu ft} Required Unconfined Volume ( V req ) = 1 , 000 Total Appliance Input (BTU/hr) × 50 cu ft
If the actual room volume is equal to or greater than V req V_{\text{req}} V req , standard building air infiltration through doors and windows provides sufficient combustion air without dedicated exterior ducts (in buildings of standard construction). If the volume is less than V req V_{\text{req}} V req , the room is legally classified as a confined space , and permanent combustion air openings must be cut.
Mathematical Step-by-Step Evaluation Example
Installation Parameters: A mechanical utility room measures 14 feet wide by 18 feet long with an 8-foot ceiling . The room contains:
- One gas storage water heater: 40,000 BTU/hr
- One gas central warm-air furnace: 80,000 BTU/hr
Step 1: Calculate Actual Room Volume ( V actual V_{\text{actual}} V actual ) V actual = Length × Width × Height = 18 ft × 14 ft × 8 ft = 2 , 016 cubic feet V_{\text{actual}} = \text{Length} \times \text{Width} \times \text{Height} = 18\text{ ft} \times 14\text{ ft} \times 8\text{ ft} = 2,016 \text{ cubic feet} V actual = Length × Width × Height = 18 ft × 14 ft × 8 ft = 2 , 016 cubic feet
Step 2: Calculate Total Aggregate Input Total Input = 40 , 000 BTU/hr + 80 , 000 BTU/hr = 120 , 000 BTU/hr \text{Total Input} = 40,000 \text{ BTU/hr} + 80,000 \text{ BTU/hr} = 120,000 \text{ BTU/hr} Total Input = 40 , 000 BTU/hr + 80 , 000 BTU/hr = 120 , 000 BTU/hr
Step 3: Calculate Required Unconfined Volume ( V req V_{\text{req}} V req ) V req = ( 120 , 000 BTU/hr 1 , 000 ) × 50 cu ft = 120 × 50 = 6 , 000 cubic feet V_{\text{req}} = \left(\frac{120,000 \text{ BTU/hr}}{1,000}\right) \times 50 \text{ cu ft} = 120 \times 50 = 6,000 \text{ cubic feet} V req = ( 1 , 000 120 , 000 BTU/hr ) × 50 cu ft = 120 × 50 = 6 , 000 cubic feet
Step 4: Determine Space Classification V actual ( 2 , 016 cu ft ) < V req ( 6 , 000 cu ft ) V_{\text{actual}} (2,016 \text{ cu ft}) < V_{\text{req}} (6,000 \text{ cu ft}) V actual ( 2 , 016 cu ft ) < V req ( 6 , 000 cu ft )
The utility room is a confined space . It possesses only 33.6 % 33.6\% 33.6% of the required volume. The plumber must provide dedicated combustion air openings .
Confined Space Methods & Opening Sizing (IFGC Section 304)
Where an installation is confined, combustion air must be brought into the space using one of four code-approved methods. +-----------------------------------------------------------------------------------------+
- | CONFINED SPACE COMBUSTION AIR SIZING METHODS |
- +-----------------------------------------------------------------------------------------+
- | Method & Air Source | Number & Location of Openings | Free Area Sizing Ratio |
- |--------------------------------+-------------------------------+------------------------|
- | Method 1: All Air From Inside | 2 Openings (1 within 12" top, | 1 sq in per 1,000 BTU/h|
- | Building (Interior Unconfined) | 1 within 12" bottom) | (Min. 100 sq in each) |
- | Method 2: All Air From Outdoor | 2 Openings or Vertical Ducts | 1 sq in per 4,000 BTU/h|
- | Vertical Ducts / Roof Openings | (1 within 12" top & bottom) | each opening |
- | Method 3: All Air From Outdoor | 2 Openings / Horizontal Ducts | 1 sq in per 2,000 BTU/h|
- | Horizontal Wall Ducts | (1 within 12" top & bottom) | each opening |
- | Method 4: All Air From Outdoor | 1 Single Opening | 1 sq in per 3,000 BTU/h|
- | Single High Opening | (Within upper 12" of space) | (≥ sum of vent areas) |
+-----------------------------------------------------------------------------------------+ COMBUSTION AIR DUCT CONFIGURATIONS (CONFINED SPACES)
- METHOD 2: TWO VERTICAL DUCTS METHOD 3: TWO HORIZONTAL DUCTS
- (1 sq in / 4,000 BTU) (1 sq in / 2,000 BTU)
- Attic Space / Roof Exterior Wall
- +---------+ +---------+ ===============================
- | Intake | | Intake |
- +----+----+ +----+----+ +---------------+ (Within 12")
- | | | UPPER OPENING |=====> FRESH AIR
- | (Duct to | (Duct to +---------------+ (OUTSIDE)
- | within 12" | within 12" |
- | of CEILING) | of FLOOR) |
- v | | WATER HEATER |
- +---------+ | | & FURNACE |
- | CEILING | | | |
- +---------+ | |
- | | +---------------+ (Within 12")
- [APPLIANCE] | | LOWER OPENING |=====> FRESH AIR
- | v +---------------+ (OUTSIDE)
- +---------+ +---------+ ===============================
- | FLOOR | | FLOOR | CONCRETE SLAB FLOOR
- +---------+ +---------+
- Method 1: All Air from Inside Building (Indoor Air)
Combustion air is borrowed from adjacent, large unconfined rooms (such as open basements):
Two Permanent Openings: One commencing within 12 inches (305 mm) of the top of the enclosure; one commencing within 12 inches of the bottom.
Sizing: Each opening must have a minimum net free area of 1 square inch per 1,000 BTU/hr of total aggregate appliance input.
Absolute Floor Limit: Neither opening may be smaller than 100 square inches ( 0.065 m 2 0.065 \text{ m}^2 0.065 m 2 ), regardless of how small the appliances are.
Example: For the 120,000 BTU/hr mechanical room, each interior opening must measure: 120 , 000 / 1 , 000 = 120 square inches 120,000 / 1,000 = \mathbf{120\text{ square inches}} 120 , 000/1 , 000 = 120 square inches .
Method 2: Outdoor Air via Two Vertical Ducts / Openings
Combustion air is drawn from the outdoors, a ventilated attic, or a crawl space through vertical ducts:
Two Openings: One within the upper 12 inches; one within the lower 12 inches.
Sizing: Each opening and duct requires 1 square inch per 4,000 BTU/hr of total aggregate input.
Example: For 120,000 BTU/hr: 120 , 000 / 4 , 000 = 30 square inches 120,000 / 4,000 = \mathbf{30\text{ square inches}} 120 , 000/4 , 000 = 30 square inches for the top duct and 30 square inches \mathbf{30\text{ square inches}} 30 square inches for the bottom duct.
Method 3: Outdoor Air via Two Horizontal Ducts
Combustion air is drawn horizontally through an exterior sidewall:
Two Openings: One upper (within 12 inches of ceiling); one lower (within 12 inches of floor).
Sizing: Each opening and duct requires 1 square inch per 2,000 BTU/hr of total input.
Why Double the Area of Vertical? Horizontal ducts encounter far greater airflow friction and lack the natural thermal buoyancy (stack effect) that assists vertical flow. Therefore, horizontal ducts require twice the cross-sectional area of vertical ducts.
Example: For 120,000 BTU/hr: 120 , 000 / 2 , 000 = 60 square inches 120,000 / 2,000 = \mathbf{60\text{ square inches}} 120 , 000/2 , 000 = 60 square inches each.
Method 4: Outdoor Air via a Single Opening
Under the fuel gas code (IFGC Section 304.6.2; in Indiana the Indiana Fuel Gas Code, 675 IAC 25 ), a single opening to the outdoors is permitted if located within the upper 12 inches of the enclosure:
Sizing: 1 square inch per 3,000 BTU/hr of total input.
Minimum Floor Area: The free area cannot be less than the sum of the cross-sectional areas of all vent connectors serving appliances in the space.
Clearances: Appliances must have minimum clearances of 1 inch from sides/back and 6 inches from the front.
Example: For 120,000 BTU/hr: 120 , 000 / 3 , 000 = 40 square inches 120,000 / 3,000 = \mathbf{40\text{ square inches}} 120 , 000/3 , 000 = 40 square inches .
Louvers, Grilles & Free Area Reductions
When sizing physical metal or wood wall louvers, plumbers must account for the obstruction created by louver blades:
Metal Louvers: Typically provide 75% net free area ( 0.75 0.75 0.75 ).
Wood Louvers: Typically provide only 25% net free area ( 0.25 0.25 0.25 ).
Calculation: If code requires 60 sq inches of net free area and a metal louver is used: Gross Louver Area = 60 / 0.75 = 80 square inches \text{Gross Louver Area} = 60 / 0.75 = \mathbf{80\text{ square inches}} Gross Louver Area = 60/0.75 = 80 square inches (e.g., an 8 " × 10 " 8" \times 10" 8" × 10" grille).
Venting Categories & Appliance Designations
Gas appliances and their venting systems are classified into four distinct categories under ANSI Z21.13 / NFPA 54 / IFGC based on flue gas temperature (condensing vs. non-condensing) and vent pressure (negative vs. positive). +-------------------------------------------------------------------------+
- | FUEL GAS APPLIANCE VENTING CATEGORIES |
- +-------------------------------------------------------------------------+
- | Category | Vent Static Pressure | Flue Gas Condensation | Approved Vent |
- |----------+----------------------+-----------------------+---------------|
- | CAT I | Non-Positive (Draft) | Non-Condensing (>140°)| Type B, Metal |
- | CAT II | Non-Positive (Draft) | Condensing (≤ 140°F) | Rare / Special|
- | CAT III | Positive (Forced) | Non-Condensing (>140°)| AL29-4C Steel |
- | CAT IV | Positive (Forced) | Condensing (≤ 140°F) | PVC, CPVC, PP |
- +-------------------------------------------------------------------------+
- Category I: Atmospheric Draft Hood Appliances
Operation: Operates with a negative (or neutral) static vent pressure created by thermal chimney draft, with flue gas temperatures well above the dew point ( > 140 ∘ F > 140^\circ\text{F} > 14 0 ∘ F ), preventing internal condensation.
Approved Venting Materials: Type B double-wall metal gas vent (galvanized steel outer wall, aluminum inner liner) or a listed masonry chimney liner. Type B vent requires a minimum 1-inch clearance to combustible materials .
Single-Wall Metal Connectors: Permitted only as interior vent connectors leading to the Type B chimney. Single-wall metal pipe requires a 6-inch clearance to combustibles and must never pass through combustible walls, floors, or attics.
Category IV: High-Efficiency Condensing Appliances
Operation: High-efficiency tankless and storage water heaters ( > 90 % > 90\% > 90% thermal efficiency) extract so much latent heat from exhaust gases that the flue temperature drops below 140 ∘ F 140^\circ\text{F} 14 0 ∘ F . Water vapor condenses into acidic liquid moisture (pH 3.0 to 5.0). Furthermore, these units utilize an internal mechanical blower, creating positive vent static pressure .
Approved Venting Materials: Acid-resistant, gas-tight plastic piping conforming to UL 1738 or ASTM standards: Schedule 40 PVC, CPVC, or Polypropylene (PP) .
Pitch and Drainage: Category IV vents must slope back toward the water heater condensate drain at not less than 1/4 inch per foot (2% slope) so that acidic condensate drains into the appliance neutralizer trap rather than pooling in the pipe.
Draft Hood Mechanics & Thermal Spillage Testing
Atmospheric Category I water heaters are fitted with an engineered draft hood (draft diverter) positioned directly above the center flue baffle. DRAFT HOOD (DRAFT DIVERTER) DYNAMICS
- To Type B Vent Chimney
- ^
- |
- +----+----+
- / FLUE \
- / GASES \
- Dilution Air / \ Dilution Air
- Ingestion + + Ingestion
- ===========> / RELIEF OPENING \ <===========
- +-------+ +-------+
- | |
- +--+-----+--+
- | BAFFLE | (Deflects Downward Downdrafts)
- +--+-----+--+
- | |
- | |
- Hot Flue Gas Rise
- From Water Heater Flue
- Three Critical Functions of a Draft Hood
Neutralizes Downdrafts: If strong outdoor wind gusts force air down the chimney, the internal baffle deflects the downdraft outward into the room through the relief skirt, preventing the wind from blowing down into the combustion chamber and extinguishing the pilot or burner.
Stabilizes Updraft: High chimney velocity draws excess dilution air through the relief opening rather than pulling excess draft through the tank, preventing heat from being prematurely stripped from the water.
Provides Dilution Air: Cool ambient room air mixes with hot flue gases inside the hood, lowering flue gas dew points and cooling the chimney stack.
Performing a Thermal Spillage Test
A certified plumber must always test for flue gas spillage upon commissioning any atmospheric water heater:
Close all exterior windows and doors. Turn on all exhaust fans (range hoods, bathroom fans, clothes dryers) to create maximum interior negative pressure.
Ignite the main water heater burner and let it fire continuously for 5 minutes to establish normal chimney thermal buoyancy.
Pass a smoke pencil, incense stick, or strike match around the entire perimeter skirt of the draft hood relief opening (holding it approximately 1 inch from the rim).
Acceptance Standard: The smoke must be drawn cleanly and vigorously into the draft hood and up the vent.
Spillage Failure: If the smoke is blown away from the hood, curls into the room, or moisture droplets fog an inspection mirror held near the rim, the vent is spilling combustion products. The appliance must be shut down immediately to diagnose flue obstructions, insufficient vent height, or mechanical house depressurization.
Vent Terminal Clearances from Building Openings
Category I mechanical draft vents and Category IV direct-vent terminals discharge lethal carbon monoxide and moist acidic vapor. Their outdoor terminal placement must adhere strictly to clearance rules to prevent toxic fumes from re-entering building living spaces. +-------------------------------------------------------------------------+
- | VENT TERMINATION MINIMUM CLEARANCE DISTANCES |
- +-------------------------------------------------------------------------+
- | Operable Door, Window, or | 4 feet below, 4 feet horizontally, or |
- | Gravity Air Intake | 1 foot above opening |
- | Forced Air Supply Intake | 3 feet above if within 10 feet |
- | | horizontally |
- | Finished Ground Grade / Snow | 12 inches minimum above grade or |
- | Accumulation Line | anticipated snow level |
- | Public Sidewalk or Driveway | 7 feet minimum vertical clearance |
- | Inside Corner of Building | 12 to 24 inches (prevents eddy traps) |
- +-------------------------------------------------------------------------+
Operable Openings: Direct-vent terminals and mechanical draft vents must maintain a minimum distance of 4 feet (1.2 m) below, 4 feet horizontally from, or 1 foot (305 mm) above any operable door, operable window, or gravity fresh air intake.
Forced Air Intakes: The vent terminal must be located at least 3 feet above any forced air intake located within a 10-foot horizontal radius.
Grade and Snow Line: Terminals must terminate not less than 12 inches above finished ground grade and high enough above expected regional snow drifts to prevent winter ice blockage.