Unit Conversions & Physical Process Principles

ISA CCST Level I Certified Control Systems Technician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Introduction & CCST Level I Certification Overview

About the ISA CCST Level I Exam How to Use This Study Guide & Exam Strategy

2 Chapter 2: Measurement Fundamentals & Electrical Principles

Electrical Fundamentals Measurement Terminology Unit Conversions & Physical Process Principles

3 Chapter 3: Pressure & Temperature Measurement

3.1 Pressure Measurement Instruments 3.2 Temperature Sensors 3.3 Calibration & Maintenance of Pressure & Temperature Transmitters

4 Chapter 4: Level & Flow Measurement

4.1 Level Measurement Instruments 4.2 Flow Measurement Instruments 4.3 Calibration & Troubleshooting of Level & Flow Transmitters

5 Chapter 5: Control Valves & Final Control Elements

5.1 Control Valve Types & Actuators 5.2 Valve Positioners, I/P Transducers & Accessories 5.3 Valve Bench Calibration, Packing Maintenance & Troubleshooting

6 Chapter 6: Signal Transmission, Fieldbus & Converters

6.1 Analog Signal Loops & Electrical Noise 6.2 HART Protocol & Smart Transmitters 6.3 Digital Field Networks & Signal Converters

7 Chapter 7: Process Control Fundamentals & Loop Troubleshooting

7.1 Process Control Modes 7.2 Process Dynamics & Tuning Awareness (Supplemental) 7.3 Systematic Control Loop Troubleshooting

8 Chapter 8: Maintenance, Repair & Safety Standards

8.1 Preventive, Predictive & Corrective Maintenance 8.2 Systematic Troubleshooting Techniques & Test Equipment 8.3 Hazardous Location Classifications & Protection Concepts 8.4 Safety Instrumented Systems (Supplemental Awareness)

9 Chapter 9: Project Start-up, Commissioning & Loop Checks

Commissioning Planning & Pre-Commissioning Activities Loop Checking Procedures & Simulation System Start-up Support & Authorized Bump Testing Handover, Sign-off & As-Built Verification

10 Chapter 10: Process Documentation & Drawings

Piping & Instrumentation Diagrams (P&IDs) Loop Diagrams & Wiring Diagrams Instrument Data Sheets & Calibration Records

Unit Conversions & Physical Process Principles

Key Takeaways Explain This Topic AI

Gauge pressure is relative to local atmospheric pressure and absolute pressure is relative to vacuum: P_abs = P_gauge + P_atm; 14.7 psi is a standard-atmosphere approximation, not every site condition.

Exact temperature conversions require precise scale relationships: T_C = (T_F - 32) / 1.8, T_K = T_C + 273.15, and T_R = T_F + 459.67.

Standard volumetric gas flow corrects actual volume for pressure and temperature using absolute units; use the contract or meter-defined standard base conditions rather than assuming every SCFM value uses the same base.

Hydrostatic head pressure generated by a liquid column is calculated as P (inH2O) = h (inches) * SG, or P (psi) = h (inches) * SG * 0.0361 psi/inH2O.

Closed-vessel DP ranges include the static heads from the actual tap, transmitter, dry-leg, wet-leg, or remote-seal geometry; these may create zero suppression or elevation.

Last updated: August 2026

Pressure Units and Pressure Scale Conversions

Pressure ( P P P ) is defined as force ( F F F ) exerted per unit area ( A A A ): P = F A P = \frac{F}{A} P = A F ​

Technicians must routinely convert between imperial, metric, and liquid column units.

Pressure Unit Equivalencies

Standard atmospheric pressure at sea level serves as the primary baseline for unit conversion: 1.000 atm = 14.696 psi = 101.325 kPa = 1.01325 bar = 760.0 mmHg (Torr) = 29.92 inHg = 407.2 inH 2 O 1.000\text{ atm} = 14.696\text{ psi} = 101.325\text{ kPa} = 1.01325\text{ bar} = 760.0\text{ mmHg (Torr)} = 29.92\text{ inHg} = 407.2\text{ inH}_2\text{O} 1.000 atm = 14.696 psi = 101.325 kPa = 1.01325 bar = 760.0 mmHg (Torr) = 29.92 inHg = 407.2 inH 2 ​ O

  • Pressure Unit Abbreviation Conversion to 1 PSI Conversion to 1 Bar
  • Pounds per Square Inch psi 1.000 psi 14.5038 psi 14.5038\text{ psi} 14.5038 psi

Inches of Water ( 39.2 ∘ F 39.2^\circ\text{F} 39. 2 ∘ F ) inH 2 _2 2 ​ O 27.680 inH 2 O 27.680\text{ inH}_2\text{O} 27.680 inH 2 ​ O 401.463 inH 2 O 401.463\text{ inH}_2\text{O} 401.463 inH 2 ​ O

Inches of Mercury ( 32 ∘ F 32^\circ\text{F} 3 2 ∘ F ) inHg 2.0360 inHg 2.0360\text{ inHg} 2.0360 inHg 29.530 inHg 29.530\text{ inHg} 29.530 inHg

  • Kilopascals kPa 6.89476 kPa 6.89476\text{ kPa} 6.89476 kPa 100.000 kPa 100.000\text{ kPa} 100.000 kPa
  • Bar bar 0.0689476 bar 0.0689476\text{ bar} 0.0689476 bar 1.000 bar

Millimeters of Mercury mmHg 51.7149 mmHg 51.7149\text{ mmHg} 51.7149 mmHg 750.062 mmHg 750.062\text{ mmHg} 750.062 mmHg

Gauge, Absolute, Vacuum, and Differential Pressure Absolute Scale (psia) Gauge Scale (psig) Vacuum Scale (inHg Vac)

  • ==================== =================== =======================
  • P_abs = 29.7 psia ------------> P_gauge = 15.0 psig

P_atm = 14.7 psia ------------> P_gauge = 0.0 psig ---------> 0.0 inHg Vac

P_abs = 9.7 psia -------------> P_gauge = -5.0 psig --------> 10.18 inHg Vac

P_abs = 0.0 psia (Absolute Zero) 29.92 inHg Vac (Full Vac)

Absolute Pressure ( P abs P_{\text{abs}} P abs ​ / psia): Measured relative to a perfect vacuum ( 0.0 psia 0.0\text{ psia} 0.0 psia ). Absolute pressure is nonnegative, with zero representing a perfect vacuum.

Gauge Pressure ( P gauge P_{\text{gauge}} P gauge ​ / psig): Measured relative to local ambient atmospheric pressure ( P atm P_{\text{atm}} P atm ​ ). Standard sea level P atm = 14.7 psi P_{\text{atm}} = 14.7\text{ psi} P atm ​ = 14.7 psi . P abs = P gauge + P atm P_{\text{abs}} = P_{\text{gauge}} + P_{\text{atm}} P abs ​ = P gauge ​ + P atm ​ P gauge = P abs − P atm P_{\text{gauge}} = P_{\text{abs}} - P_{\text{atm}} P gauge ​ = P abs ​ − P atm ​

Vacuum Pressure ( P vac P_{\text{vac}} P vac ​ ): Pressure below atmospheric pressure, often measured in inches of mercury vacuum (inHg Vac) or mmHg. P vac_inHg = ( P atm_psia − P abs_psia ) × 2.0360 inHg/psi P_{\text{vac\_inHg}} = (P_{\text{atm\_psia}} - P_{\text{abs\_psia}}) \times 2.0360\text{ inHg/psi} P vac_inHg ​ = ( P atm_psia ​ − P abs_psia ​ ) × 2.0360 inHg/psi

Differential Pressure ( Δ P \Delta P Δ P / psid / inH 2 O \text{inH}_2\text{O} inH 2 ​ O ): The algebraic difference between two pressure points ( P High − P Low P_{\text{High}} - P_{\text{Low}} P High ​ − P Low ​ ).

Worked Example: Pressure Scale Conversion

Scenario: A vacuum distillation column operates at an absolute pressure of 3.20 psia 3.20\text{ psia} 3.20 psia . Calculate the equivalent pressure in gauge pressure ( psig \text{psig} psig ) and inches of mercury vacuum ( inHg Vac \text{inHg Vac} inHg Vac ) assuming standard P atm = 14.70 psia P_{\text{atm}} = 14.70\text{ psia} P atm ​ = 14.70 psia . Gauge Pressure: P gauge = 3.20 psia − 14.70 psia = − 11.50 psig \text{Gauge Pressure: } P_{\text{gauge}} = 3.20\text{ psia} - 14.70\text{ psia} = -11.50\text{ psig} Gauge Pressure: P gauge ​ = 3.20 psia − 14.70 psia = − 11.50 psig Vacuum Pressure: P vac = ( 14.70 psia − 3.20 psia ) × 2.0360 inHg/psi = 11.50 × 2.0360 = 23.414 inHg Vac \text{Vacuum Pressure: } P_{\text{vac}} = (14.70\text{ psia} - 3.20\text{ psia}) \times 2.0360\text{ inHg/psi} = 11.50 \times 2.0360 = 23.414\text{ inHg Vac} Vacuum Pressure: P vac ​ = ( 14.70 psia − 3.20 psia ) × 2.0360 inHg/psi = 11.50 × 2.0360 = 23.414 inHg Vac

Temperature Scales and Exact Conversion Formulas

Process measurement utilizes four temperature scales: two relative scales (Fahrenheit and Celsius) and two absolute scales (Rankine and Kelvin). +-----------------------------------------------------------------------------------------+

  • | TEMPERATURE SCALE RELATIONSHIPS |
  • | |
  • | Water Boiling Point 212 °F --------- 100 °C --------- 373.15 K --------- 671.67 °R |
  • | Water Freezing Point 32 °F --------- 0 °C --------- 273.15 K --------- 491.67 °R |
  • | Absolute Zero -459.67 °F ------- -273.15 °C ------- 0 K ----------- 0 °R |
  • +-----------------------------------------------------------------------------------------+

Exact Conversion Formulas Celsius to Fahrenheit: T ∘ F = ( T ∘ C × 1.8 ) + 32 \text{Celsius to Fahrenheit: } T_{^\circ\text{F}} = (T_{^\circ\text{C}} \times 1.8) + 32 Celsius to Fahrenheit: T ∘ F ​ = ( T ∘ C ​ × 1.8 ) + 32 Fahrenheit to Celsius: T ∘ C = T ∘ F − 32 1.8 \text{Fahrenheit to Celsius: } T_{^\circ\text{C}} = \frac{T_{^\circ\text{F}} - 32}{1.8} Fahrenheit to Celsius: T ∘ C ​ = 1.8 T ∘ F ​ − 32 ​ Celsius to Kelvin (Absolute): T K = T ∘ C + 273.15 \text{Celsius to Kelvin (Absolute): } T_{\text{K}} = T_{^\circ\text{C}} + 273.15 Celsius to Kelvin (Absolute): T K ​ = T ∘ C ​ + 273.15 Fahrenheit to Rankine (Absolute): T ∘ R = T ∘ F + 459.67 \text{Fahrenheit to Rankine (Absolute): } T_{^\circ\text{R}} = T_{^\circ\text{F}} + 459.67 Fahrenheit to Rankine (Absolute): T ∘ R ​ = T ∘ F ​ + 459.67 Kelvin to Rankine: T ∘ R = T K × 1.8 \text{Kelvin to Rankine: } T_{^\circ\text{R}} = T_{\text{K}} \times 1.8 Kelvin to Rankine: T ∘ R ​ = T K ​ × 1.8

Worked Example: Temperature Conversion

Scenario: A heat exchanger outlet temperature transmitter reads 356.0 ∘ F 356.0\text{ }^\circ\text{F} 356.0 ∘ F . Convert this reading to Celsius ( ∘ C ^\circ\text{C} ∘ C ) and Kelvin ( K \text{K} K ). T ∘ C = 356.0 − 32 1.8 = 324.0 1.8 = 180.0 ∘ C T_{^\circ\text{C}} = \frac{356.0 - 32}{1.8} = \frac{324.0}{1.8} = 180.0\text{ }^\circ\text{C} T ∘ C ​ = 1.8 356.0 − 32 ​ = 1.8 324.0 ​ = 180.0 ∘ C T K = 180.0 + 273.15 = 453.15 K T_{\text{K}} = 180.0 + 273.15 = 453.15\text{ K} T K ​ = 180.0 + 273.15 = 453.15 K

Volumetric Flow, Mass Flow, and Standard Volumetric Flow

Flow rate measurement is categorized into three fundamental physical types:

1. Volumetric Flow ( Q v Q_v Q v ​ )

Measures physical fluid volume passing a point per unit time (e.g., Gallons Per Minute [GPM], Actual Cubic Feet Per Minute [ACFM], Cubic Meters Per Hour [ m 3 / hr \text{m}^3/\text{hr} m 3 / hr ]).

Limitation: Gas and liquid volume expands or contracts with changing temperature and pressure, making raw volumetric flow inaccurate for mass balance custody transfer.

2. Mass Flow ( Q m Q_m Q m ​ )

Measures actual mass of fluid passing a point per unit time (e.g., Pounds Per Hour [lb/hr], Kilograms Per Second [kg/s]). Q m = ρ × Q v Q_m = \rho \times Q_v Q m ​ = ρ × Q v ​

Where ρ \rho ρ is fluid density.

Advantage: Mass flow expresses quantity directly as mass per time and does not require choosing standard volumetric base conditions; the actual process and meter performance can still depend on temperature, pressure, composition, and phase.

3. Standard Volumetric Flow ( Q s Q_s Q s ​ - SCFM vs. ACFM)

Gas flow is frequently expressed in Standard Cubic Feet Per Minute (SCFM) . A standard-volume result is meaningful only when its reference pressure and temperature are stated. The worked examples here use T std = 60.0 ∘ F = 519.67 ∘ R T_{\text{std}} = 60.0\text{ }^\circ\text{F} = 519.67\text{ }^\circ\text{R} T std ​ = 60.0 ∘ F = 519.67 ∘ R and P std = 14.696 psia P_{\text{std}} = 14.696\text{ psia} P std ​ = 14.696 psia ; contracts, industries, and meter configurations may use different base conditions.

For the simplified case in which ideal-gas behavior is assumed and compressibility effects cancel, the Ideal Gas Law ( P V = n R T P V = n R T P V = n RT ) converts Actual Cubic Feet Per Minute (ACFM) measured at actual process pressure ( P act P_{\text{act}} P act ​ ) and actual process temperature ( T act T_{\text{act}} T act ​ ) is converted to SCFM: SCFM = ACFM × ( P actual_psia P std_psia ) × ( T std_Rankine T actual_Rankine ) \text{SCFM} = \text{ACFM} \times \left( \frac{P_{\text{actual\_psia}}}{P_{\text{std\_psia}}} \right) \times \left( \frac{T_{\text{std\_Rankine}}}{T_{\text{actual\_Rankine}}} \right) SCFM = ACFM × ( P std_psia ​ P actual_psia ​ ​ ) × ( T actual_Rankine ​ T std_Rankine ​ ​ )

CRITICAL EXAM RULE: Temperatures MUST be converted to Absolute Rankine ( ∘ R = ∘ F + 459.67 ^\circ\text{R} = ^\circ\text{F} + 459.67 ∘ R = ∘ F + 459.67 ) and pressures MUST be converted to Absolute Pressure ( psia = psig + 14.7 \text{psia} = \text{psig} + 14.7 psia = psig + 14.7 ).

Worked Example: ACFM to SCFM Conversion

Scenario: An air compressor delivers 400.0 ACFM 400.0\text{ ACFM} 400.0 ACFM through a discharge line operating at 100.0 psig 100.0\text{ psig} 100.0 psig pressure and 140.0 ∘ F 140.0\text{ }^\circ\text{F} 140.0 ∘ F temperature. Calculate the mass-equivalent flow rate in SCFM \text{SCFM} SCFM .

Step 1: Convert pressure to Absolute Pressure (psia) P actual = 100.0 psig + 14.7 = 114.7 psia P_{\text{actual}} = 100.0\text{ psig} + 14.7 = 114.7\text{ psia} P actual ​ = 100.0 psig + 14.7 = 114.7 psia P standard = 14.7 psia P_{\text{standard}} = 14.7\text{ psia} P standard ​ = 14.7 psia

Step 2: Convert temperatures to Absolute Temperature (Rankine) T actual = 140.0 ∘ F + 459.67 = 599.67 ∘ R T_{\text{actual}} = 140.0\text{ }^\circ\text{F} + 459.67 = 599.67\text{ }^\circ\text{R} T actual ​ = 140.0 ∘ F + 459.67 = 599.67 ∘ R T standard = 60.0 ∘ F + 459.67 = 519.67 ∘ R T_{\text{standard}} = 60.0\text{ }^\circ\text{F} + 459.67 = 519.67\text{ }^\circ\text{R} T standard ​ = 60.0 ∘ F + 459.67 = 519.67 ∘ R

Step 3: Calculate SCFM SCFM = 400.0 × ( 114.7 14.7 ) × ( 519.67 599.67 ) \text{SCFM} = 400.0 \times \left( \frac{114.7}{14.7} \right) \times \left( \frac{519.67}{599.67} \right) SCFM = 400.0 × ( 14.7 114.7 ​ ) × ( 599.67 519.67 ​ ) SCFM = 400.0 × ( 7.8027 ) × ( 0.86659 ) = 2,704.7 SCFM \text{SCFM} = 400.0 \times (7.8027) \times (0.86659) = 2{,}704.7\text{ SCFM} SCFM = 400.0 × ( 7.8027 ) × ( 0.86659 ) = 2 , 704.7 SCFM

Hydrostatic Head Pressure and Liquid Level Calculations

A column of liquid exerts hydrostatic pressure at its base due to gravity: P = h × ρ × g P = h \times \rho \times g P = h × ρ × g

In industrial engineering units, hydrostatic pressure is governed by Specific Gravity (SG) , the dimensionless ratio of fluid density to a stated reference-fluid density at stated conditions. The following water-column examples use the stated SG value directly. P (inH 2 O) = h (inches) × SG P\text{ (inH}_2\text{O)} = h\text{ (inches)} \times \text{SG} P (inH 2 ​ O) = h (inches) × SG P (psi) = h (inches) × SG × 0.036127 psi/inH 2 O P\text{ (psi)} = h\text{ (inches)} \times \text{SG} \times 0.036127\text{ psi/inH}_2\text{O} P (psi) = h (inches) × SG × 0.036127 psi/inH 2 ​ O P (psi) = h (inches) × SG 27.680 inH 2 O/psi P\text{ (psi)} = \frac{h\text{ (inches)} \times \text{SG}}{27.680\text{ inH}_2\text{O/psi}} P (psi) = 27.680 inH 2 ​ O/psi h (inches) × SG ​

Worked Example: Tank Level Hydrostatic Pressure

Scenario: An open storage tank contains sulfuric acid (Specific Gravity SG = 1.84 \text{SG} = 1.84 SG = 1.84 ) filled to a liquid height of 150.0 inches 150.0\text{ inches} 150.0 inches . Calculate the hydrostatic pressure at the bottom tap in inH 2 O \text{inH}_2\text{O} inH 2 ​ O and psig \text{psig} psig . P (inH 2 O) = 150.0 in × 1.84 = 276.0 inH 2 O P\text{ (inH}_2\text{O)} = 150.0\text{ in} \times 1.84 = 276.0\text{ inH}_2\text{O} P (inH 2 ​ O) = 150.0 in × 1.84 = 276.0 inH 2 ​ O P (psig) = 276.0 inH 2 O 27.680 inH 2 O/psi = 9.971 psig P\text{ (psig)} = \frac{276.0\text{ inH}_2\text{O}}{27.680\text{ inH}_2\text{O/psi}} = 9.971\text{ psig} P (psig) = 27.680 inH 2 ​ O/psi 276.0 inH 2 ​ O ​ = 9.971 psig

Differential Pressure Level Connections: Dry Leg vs. Wet Leg

When measuring liquid level in enclosed pressure vessels, static vapor space pressure must be canceled out using a Differential Pressure (DP) transmitter. DRY LEG INSTALLATION WET LEG INSTALLATION

(Non-Condensable Vapor) (Condensable Vapor / Steam)

  • +--------------+ +--------------+
  • | Vapor Space | (Dry Leg) | Vapor Space | (Condensate Leg)
  • | |----[LP] | |====[LP]
  • | | | | | | (Pre-filled
  • | Liquid (SG) | | | Liquid (SG) | | SG_leg)
  • | |----[HP] | |====[HP]
  • +--------------+ +--------------+
  • DP Transmitter DP Transmitter
  • P_HP = h*SG; P_LP = 0 P_HP = h*SG; P_LP = H*SG_leg
  • Dry Leg Installations

Used when the gas or vapor above the liquid does not condense at ambient room temperature.

High Pressure (HP) Port: Connected to bottom liquid tap.

Low Pressure (LP) Port: Connected to top vapor space tap via a dry pipe.

Pressure Equations:

At 0% Level ( h = 0 h = 0 h = 0 ): P HP = P vapor P_{\text{HP}} = P_{\text{vapor}} P HP ​ = P vapor ​ , P LP = P vapor P_{\text{LP}} = P_{\text{vapor}} P LP ​ = P vapor ​ . Δ P LRV = P HP − P LP = 0.0 inH 2 O \Delta P_{\text{LRV}} = P_{\text{HP}} - P_{\text{LP}} = 0.0\text{ inH}_2\text{O} Δ P LRV ​ = P HP ​ − P LP ​ = 0.0 inH 2 ​ O

At 100% Level ( h = h max h = h_{\text{max}} h = h max ​ ): Δ P URV = h max × SG \Delta P_{\text{URV}} = h_{\text{max}} \times \text{SG} Δ P URV ​ = h max ​ × SG

Calibration Range: 0.0 to ( h max × SG ) inH 2 O 0.0\text{ to } (h_{\text{max}} \times \text{SG})\text{ inH}_2\text{O} 0.0 to ( h max ​ × SG ) inH 2 ​ O .

Wet Leg Installations (Zero Elevation)

Used when vapor above the liquid condenses into liquid (e.g., steam boilers, distillation columns). The Low Pressure (LP) reference pipe is intentionally pre-filled with a reference liquid of known density ( SG leg \text{SG}_{\text{leg}} SG leg ​ ) to maintain a constant, stable liquid column height ( H H H ).

The Zero Elevation Effect:

In the illustrated geometry, the full wet-leg head on the LP port exceeds the HP-side static head at empty, so the 0% differential is negative. Calculate the actual LRV from tap, transmitter, and reference-leg elevations rather than assuming every wet-leg installation has the same sign.

Calibration Equations for Wet Leg DP Transmitter: Δ P = P HP − P LP \Delta P = P_{\text{HP}} - P_{\text{LP}} Δ P = P HP ​ − P LP ​ Δ P LRV (0% Level) = ( 0 × SG ) − ( H × SG leg ) = − ( H × SG leg ) \Delta P_{\text{LRV (0\% Level)}} = (0 \times \text{SG}) - (H \times \text{SG}_{\text{leg}}) = -(H \times \text{SG}_{\text{leg}}) Δ P LRV (0% Level) ​ = ( 0 × SG ) − ( H × SG leg ​ ) = − ( H × SG leg ​ ) Δ P URV (100% Level) = ( h max × SG ) − ( H × SG leg ) \Delta P_{\text{URV (100\% Level)}} = (h_{\text{max}} \times \text{SG}) - (H \times \text{SG}_{\text{leg}}) Δ P URV (100% Level) ​ = ( h max ​ × SG ) − ( H × SG leg ​ ) Span = Δ P URV − Δ P LRV = h max × SG \text{Span} = \Delta P_{\text{URV}} - \Delta P_{\text{LRV}} = h_{\text{max}} \times \text{SG} Span = Δ P URV ​ − Δ P LRV ​ = h max ​ × SG

Comprehensive Worked Example: Wet Leg Transmitter Calibration

Scenario: A closed boiler steam drum uses a wet leg DP level transmitter. The vertical distance between vessel taps is H = 100.0 inches H = 100.0\text{ inches} H = 100.0 inches . Maximum liquid measuring height is h max = 80.0 inches h_{\text{max}} = 80.0\text{ inches} h max ​ = 80.0 inches . The boiler water specific gravity is SG = 0.90 \text{SG} = 0.90 SG = 0.90 . The reference wet leg is filled with water/glycol condensate having specific gravity SG leg = 1.00 \text{SG}_{\text{leg}} = 1.00 SG leg ​ = 1.00 . The transmitter is mounted exactly level with the bottom tap. Top Tap (LP) =============================================+ (H = 100.0 in, Wet Leg SG_leg = 1.00)

  • | |
  • |--- 100% Level (h_max = 80.0 in, Process SG = 0.90) |
  • | |
  • | |
  • |--- 0% Level (h = 0.0 in) |
  • Bottom Tap (HP) ==========================================+ (Transmitter mounted here)
  • Step 1: Calculate Δ P \Delta P Δ P at 0% Level (LRV)

At 0 % 0\% 0% level ( h = 0.0 in h = 0.0\text{ in} h = 0.0 in ):

P HP = 0.0 × 0.90 = 0.0 inH 2 O P_{\text{HP}} = 0.0 \times 0.90 = 0.0\text{ inH}_2\text{O} P HP ​ = 0.0 × 0.90 = 0.0 inH 2 ​ O

P LP = H × SG leg = 100.0 in × 1.00 = 100.0 inH 2 O P_{\text{LP}} = H \times \text{SG}_{\text{leg}} = 100.0\text{ in} \times 1.00 = 100.0\text{ inH}_2\text{O} P LP ​ = H × SG leg ​ = 100.0 in × 1.00 = 100.0 inH 2 ​ O Δ P LRV = P HP − P LP = 0.0 − 100.0 = − 100.0 inH 2 O \Delta P_{\text{LRV}} = P_{\text{HP}} - P_{\text{LP}} = 0.0 - 100.0 = -100.0\text{ inH}_2\text{O} Δ P LRV ​ = P HP ​ − P LP ​ = 0.0 − 100.0 = − 100.0 inH 2 ​ O

Step 2: Calculate Δ P \Delta P Δ P at 100% Level (URV)

At 100 % 100\% 100% level ( h = 80.0 in h = 80.0\text{ in} h = 80.0 in ):

P HP = h max × SG = 80.0 in × 0.90 = 72.0 inH 2 O P_{\text{HP}} = h_{\text{max}} \times \text{SG} = 80.0\text{ in} \times 0.90 = 72.0\text{ inH}_2\text{O} P HP ​ = h max ​ × SG = 80.0 in × 0.90 = 72.0 inH 2 ​ O

P LP = 100.0 inH 2 O P_{\text{LP}} = 100.0\text{ inH}_2\text{O} P LP ​ = 100.0 inH 2 ​ O Δ P URV = P HP − P LP = 72.0 − 100.0 = − 28.0 inH 2 O \Delta P_{\text{URV}} = P_{\text{HP}} - P_{\text{LP}} = 72.0 - 100.0 = -28.0\text{ inH}_2\text{O} Δ P URV ​ = P HP ​ − P LP ​ = 72.0 − 100.0 = − 28.0 inH 2 ​ O

Step 3: Calculate Calibrated Span Span = Δ P URV − Δ P LRV = − 28.0 − ( − 100.0 ) = + 72.0 inH 2 O \text{Span} = \Delta P_{\text{URV}} - \Delta P_{\text{LRV}} = -28.0 - (-100.0) = +72.0\text{ inH}_2\text{O} Span = Δ P URV ​ − Δ P LRV ​ = − 28.0 − ( − 100.0 ) = + 72.0 inH 2 ​ O

Summary Calibration Table:

  • LRV (4.00 mA / 0% Level): − 100.0 inH 2 O -100.0\text{ inH}_2\text{O} − 100.0 inH 2 ​ O
  • URV (20.00 mA / 100% Level): − 28.0 inH 2 O -28.0\text{ inH}_2\text{O} − 28.0 inH 2 ​ O
  • Calibrated Span: 72.0 inH 2 O 72.0\text{ inH}_2\text{O} 72.0 inH 2 ​ O

Validation: Notice that Span equals h max × SG = 80.0 × 0.90 = 72.0 inH 2 O h_{\text{max}} \times \text{SG} = 80.0 \times 0.90 = 72.0\text{ inH}_2\text{O} h max ​ × SG = 80.0 × 0.90 = 72.0 inH 2 ​ O . The wet leg creates a constant − 100.0 inH 2 O -100.0\text{ inH}_2\text{O} − 100.0 inH 2 ​ O zero elevation offset, but does not alter the span.