Study guide
3.1 Ohm's Law, Power, and Basic Units
Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Orientation and Source Control
1.1 ICC R17, T17, G17, and Jurisdiction Variance 1.2 Current Format, Cost, Time, and Passing Score 1.3 Licensing Board vs. Exam Provider 1.4 Official References, Open-Book Rules, and Calculators 1.5 Domain Weights and Study Map 1.6 Using the Practice Bank, Error Log, and NEC Index
2 Chapter 2: NEC Navigation, Definitions, and Code Strategy
2.1 NEC Book Structure and Article Map 2.2 Article 100 Definitions and Exam Language 2.3 Index, Table, and Annex Navigation 2.4 Shall, Shall Not, Permitted, and Informational Notes 2.5 Using Code References Without Overlooking Context 2.6 State Amendments and Code Edition Control 2.7 NEC Navigation Case Lab
3 Chapter 3: Electrical Theory and Calculation Foundations
3.1 Ohm's Law, Power, and Basic Units 3.2 Series, Parallel, and Circuit Behavior 3.3 Single-Phase, Three-Phase, and Voltage Systems 3.4 Continuous Loads, Demand, and 125 Percent Rules 3.5 Voltage Drop and Practical Calculation Setup 3.6 Load Calculation Workflow 3.7 Calculation Foundation Case Lab
4 Chapter 4: Services, Service Equipment, and Grounding/Bonding
4.1 Service Point, Service Conductors, and Disconnects 4.2 Service Load Calculation and Sizing 4.3 Service Equipment, Panelboards, and Switchboards 4.4 Grounding Electrode System and GEC 4.5 Bonding, Main Bonding Jumpers, and Effective Fault Path 4.6 Transformers and Separately Derived Systems 4.7 Services and Grounding Case Lab
5 Chapter 5: Feeders, Branch Circuits, and Conductor Sizing
5.1 Feeder vs. Branch Circuit Boundaries 5.2 Branch Circuit Ratings and Required Outlets 5.3 Conductor Ampacity, Temperature, and Terminal Ratings 5.4 Adjustment, Correction, and More Than Three Conductors 5.5 Overcurrent Protection and Small-Conductor Rules 5.6 GFCI, AFCI, Equipment Grounding, and Dwelling Circuits 5.7 Feeders and Branch Circuits Case Lab
6 Chapter 6: Wiring Methods, Raceways, Boxes, and Cables
6.1 Raceway Selection and Installation Logic 6.2 Underground Wiring, Wet Locations, and Protection 6.3 Boxes, Enclosures, and Conduit Bodies 6.4 Box Fill, Conductor Counting, and Device Yokes 6.5 Cabinets, Panelboards, and Switchboards 6.6 Flexible Cords, Cables, and Temporary Wiring 6.7 Wiring Methods Case Lab
7 Chapter 7: Equipment, Devices, Luminaires, and Controls
7.1 Receptacles, Switches, and Device Selection 7.2 Luminaires, Lampholders, and Lighting Outlets 7.3 Appliances and Utilization Equipment 7.4 Heating, Cooling, and HVAC Electrical Connections 7.5 Disconnects, Controllers, and Switching Devices 7.6 Equipment Grounding, Bonding, and Listing Markings 7.7 Equipment and Devices Case Lab
8 Chapter 8: Motors, Generators, Transformers, and Special Equipment
8.1 Motor Circuit Anatomy and Article 430 Navigation 8.2 Motor Conductors, Overload, and Short-Circuit Protection 8.3 Motor Controllers, Disconnects, and Nameplates 8.4 Generators, Transfer Equipment, and Optional Standby 8.5 Transformer Sizing, Protection, and Grounding 8.6 Emergency Systems, Fire Alarms, and Signaling Overview 8.7 Motors and Generators Case Lab
9 Chapter 9: Special Occupancies, Renewables, and Safety
9.1 Hazardous Classified Locations 9.2 Healthcare, Marinas, RV Parks, and Mobile Home Parks 9.3 Pools, Spas, and Similar Installations 9.4 Solar PV, Energy Storage, and Renewable Systems 9.5 Temporary Power, Emergency Systems, and Special Conditions 9.6 OSHA Subpart K and Safe Work Practice Context 9.7 Special Occupancies Case Lab
10 Chapter 10: Open-Book Exam Workflow and Mixed Code Labs
10.1 Four-Hour Pacing and Question Triage 10.2 Look-Up vs. Know-From-Memory Decisions 10.3 Mixed Calculation Lab 10.4 Mixed Code Navigation Lab 10.5 Diagnostic Report and Error Log Remediation 10.6 High-Weight Domain Remediation Plan 10.7 Full Exam Simulation Playbook
11 Chapter 11: Final Review, Test Day, and License Planning
11.1 Final Two-Week Study Plan 11.2 Reference Book, Tabs, and Allowed Materials Checklist 11.3 Pearson VUE, PRONTO, and Test-Day Rules 11.4 After the Exam: Results, Retakes, and Challenges 11.5 License Application, Work Hours, and Jurisdiction Next Steps 11.6 After Journeyman: Master, Contractor, and Continuing Education
3.1 Ohm's Law, Power, and Basic Units
Key Takeaways Explain This Topic AI
Ohm's Law relates voltage, current, and resistance, but exam questions often hide the needed value in units, nameplate data, or branch-circuit wording.
Power formulas change with direct current, single-phase alternating current, and three-phase systems; choose the formula that matches the stated system.
Calculator discipline means writing known values, converting units first, and checking whether the answer should be larger or smaller before selecting an option.
Open-book exam speed improves when formulas are practiced until the code book is used for rules and tables instead of basic arithmetic.
Last updated: May 2026
Why the basic units matter on an open-book exam
The ICC journeyman electrician exams are open book for R17, T17, and G17, but open book does not mean slow book. You may be able to look up a table or article rule, but you will not have time to relearn Ohm's Law during the exam. The calculation foundation is the language behind conductor ampacity, voltage drop, appliance loads, motor full-load current, transformer current, and service calculations.
Start every calculation by naming the quantity. Voltage is electrical pressure in volts (V). Current is flow in amperes (A). Resistance is opposition in ohms. Power can be real power in watts (W), apparent power in volt-amperes (VA), or reactive power in volt-amperes reactive (VAR). NEC load calculations commonly use VA because it works cleanly with voltage and current before the load's power factor is known.
Core formulas
- Relationship Formula Typical use
- Ohm's Law E = I x R Find voltage, current, or resistance in a simple circuit
- Current I = E / R Find amperes when voltage and resistance are known
- Resistance R = E / I Find ohms when voltage and current are known
- DC or unity power P = E x I Convert volts and amperes to watts or VA
- Power from current P = I^2 x R Heating and resistance questions
- Power from voltage P = E^2 / R Fixed-resistance load questions
Many exam references and field texts use E for voltage because electromotive force is the older term. You may also see V. Treat E and V as the same electrical quantity for these formulas.
Worked example: find current from watts
A 240-volt fixed electric heater is rated 4,800 watts. What current does it draw?
Known values: P = 4,800 W, E = 240 V. Use I = P / E.
I = 4,800 / 240 = 20 A.
That answer is the operating current of the heater, not automatically the overcurrent device size and not automatically the branch-circuit conductor ampacity. A later NEC rule may require a continuous-load adjustment or a specific fixed-heating rule. The arithmetic only gives the base current.
Worked example: find resistance
A test question says a circuit has 120 volts applied and 5 amperes flowing through a resistance load. Find the resistance.
R = E / I = 120 / 5 = 24 ohms.
A common distractor is 600, which comes from multiplying instead of dividing. Another distractor is 0.0417, which comes from I / E. If the circuit has normal building voltage and only a few amperes, a resistance of a few dozen ohms is sensible. A sanity check catches formula reversal.
Watts, VA, and power factor
For a pure resistance load, watts and VA are usually the same for exam arithmetic. For loads with coils, motors, electronic power supplies, or discharge lighting, apparent power and real power can differ. The relationship is:
- W = VA x power factor
- VA = W / power factor
If a 1,200-watt load has a power factor of 0.80, the apparent load is 1,200 / 0.80 = 1,500 VA. The current on a 120-volt circuit is 1,500 / 120 = 12.5 A, not 10 A. The exam trap is using watts directly when the question gives power factor and asks for current or conductor loading.
Unit conversion before calculation
Convert before you press equals. Kilowatts must become watts when used with volts and amperes. Milliamperes must become amperes. Horsepower questions often require a table rather than a simple watt conversion because NEC motor current rules use table full-load current values in many places. Do not substitute 746 watts per horsepower when the code rule tells you to use a motor table.
Common conversions:
- Given Convert to Example
- 1 kW 1,000 W 7.5 kW = 7,500 W
- 1 kVA 1,000 VA 15 kVA = 15,000 VA
- 1 mA 0.001 A 500 mA = 0.5 A
- 1 hp Do not assume for NEC motor current Use the required motor table when directed
- Calculator discipline
Use a four-step pattern on every calculation question. First, copy the given values with units. Second, circle or mentally tag what the question asks for. Third, choose the formula and convert units. Fourth, estimate the expected size before selecting an answer.
For example, a 3,600 VA load on 120 volts must be about 30 amperes because 120 x 30 = 3,600. If your calculator says 0.033, you divided in the wrong direction. If it says 432,000, you multiplied when you should have divided. These errors are not knowledge problems; they are exam-process problems.
NEC navigation connection
The NEC is not organized as a formula book. It gives definitions, installation rules, tables, adjustment factors, demand factors, and special calculations. Electrical theory lets you move between those rules. A branch-circuit question may begin with a VA load, require current in amperes, then require a conductor size from an ampacity table, then require an overcurrent device rule. The formula is only the first link in the chain.
For ICC R17, T17, and G17, know which NEC edition your jurisdiction selected: R17 is based on the 2023 NEC, T17 on the 2020 NEC, and G17 on the 2017 NEC. The basic math does not change, but table numbers, article text, and local amendments may. ICC provides the exam; licensing remains with the state or local jurisdiction.
Exam traps
Watch for nameplate values that are already in amperes. If the question gives 16 A at 120 V and asks for minimum circuit ampacity, do not convert to watts unless a later step needs VA. Watch for two loads at different voltages. Add currents only when they are on the same system part, and add VA when combining unlike branch loads for service or feeder sizing. Watch for rounded answers. Carry at least one extra decimal place through the work, then round according to the question or the NEC rule being applied.
Finally, answer every multiple-choice question. ICC contractor and trades exams use four-option multiple choice with one correct answer and no guessing penalty. If time is short, eliminate answers that have impossible units or unreasonable magnitude.